Carrier PACKAGE ROOFTOP 48HC- User Manual

Carrier PACKAGE ROOFTOP 48HC

Carrier PACKAGE ROOFTOP 48HC– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
Page: / 56

Table of Contents:

  • Page 2 – SAFETY CONSIDERATIONS; WARNING
  • Page 6 – INSTALLATION; Jobsite Survey; Step 1 — Plan for Unit Location; NOTE
  • Page 7 – Roof Curb Mount —; Ductwork must be attached to curb and
  • Page 9 – MAXIMUM ALLOWABLE; Step 5 — Field Fabricate Ductwork; Do not connect ductwork to unit.; PROPERTY DAMAGE HAZARD; Step 6 — Rig and Place Unit; UNIT DAMAGE HAZARD; CAUTION
  • Page 10 – Flue vent discharge must have a minimum horizontal; Step 7 — Convert to Horizontal and Connect; without; Step 8 — Install Outside Air Hood; Economizer and Two Position Damper Hood
  • Page 11 – Hood Parts Location; Economizer Hood and Two–Position; Step 9 — Units with Hinged Panels Only
  • Page 12 – UNIT MODEL; EQUIPMENT DAMAGE HAZARD
  • Page 13 – STEEL PIPE; Union
  • Page 14 – BURNER
  • Page 15 – All units must have an external trap for condensate; Step 13 — Make Electrical Connections; ELECTRICAL SHOCK HAZARD; Do not use gas piping as an electrical ground.
  • Page 16 – Units Without Single Point Box, Disconnect or HACR Option; HACR—
  • Page 17 – to be connected to a 208-v power supply, the control
  • Page 19 – NOTICE; Convenience Outlet Utilization; Maximum Intermittent use : 15 Amps 2 to 3 Hours; Convenience outlet usage rating:
  • Page 20 – Heat Anticipator Settings —
  • Page 21 – Control Connections
  • Page 22 – Adaptive Dehumidification System Humidistat Wiring; EDGE Pro THERMIDISTAT; with EDGE Pro Thermidistat Device
  • Page 23 – Comfort; Link
  • Page 28 – PremierLink
  • Page 31 – Temperature (SAT) Sensor on Small Rooftop Units; Field Connections; Table 3 – PremierLink Sensor Usage
  • Page 33 – Space Sensors —; Connect Thermostat —
  • Page 34 – Economizer Controls; COVER REMOVED
  • Page 35 – UNIT PERFORMANCE HAZARD; Io; BLACK
  • Page 37 – CCN Bus
  • Page 38 – RTU Open Control System; Fig. 68 -- 48HC Control Box Component Locations with RTU Open
  • Page 41 – Table 8 – RTU Open Controller Inputs and Outputs
  • Page 42 – Indoor Air Quality (CO
  • Page 44 – Relative Humidity Sensor; Connecting Discrete Inputs —
  • Page 45 – RTU Open Controller Integration Guide; SW3 Protocol Selection; PROTOCOL; Baud Rate Selections; BAUD RATE
  • Page 46 – Local Access; BACview; RTU Open; Cable; Handheld Connections
  • Page 47 – Table 9 – LEDs; Outdoor Air Enthalpy Control; Differential Enthalpy Control —
  • Page 48 – To wire the return air enthalpy sensor, perform the; Smoke Detectors; Completing Installation of Return Air Smoke Sensor:
  • Page 49 – HC
  • Page 53 – Legend and Notes for Tables 10 and 11; IMPORTANT
  • Page 54 – Step 14 — Adjust Factory--Installed Options; Smoke Detectors —; Step 15 — Install Accessories
  • Page 55 – I. PRELIMINARY INFORMATION; ELECTRICAL
  • Page 56 – VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS; GENERAL
Loading the manual

48HC

Single Package Rooftop

Gas Heating/Electric Cooling Unit

with Puron

r

(R --- 410A) Refrigerant

Sizes: 04, 05, 06

Installation Instructions

NOTE

: Read the entire instruction manual before starting

the installation

TABLE OF CONTENTS

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . .

INSTALLATION

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Jobsite Survey

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 -- Plan for Unit Location

6

. . . . . . . . . . . . . . . . . .

Roof Mount

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 2 -- Plan for Sequence of Unit Installation

7

. . . . . .

Curb--Mount Installation

7

. . . . . . . . . . . . . . . . . . . . .

Pad--Mount Installation

7

. . . . . . . . . . . . . . . . . . . . . .

Frame--Mount Installation

7

. . . . . . . . . . . . . . . . . . . .

Step 3 -- Inspect Unit

7

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 4 -- Provide Unit Support

7

. . . . . . . . . . . . . . . . . . .

Roof Curb Mount

7

. . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount (Horizontal Units Only)

7

. . . . . . . . . . .

Alternate Unit Support

(In Lieu of Curb or Slab Mount)

7

. . . . . . . . . . . . . .

Step 5 -- Field Fabricate Ductwork

9

. . . . . . . . . . . . . . . .

Step 6 -- Rig and Place Unit

9

. . . . . . . . . . . . . . . . . . . . .

Positioning on Curb

10

. . . . . . . . . . . . . . . . . . . . . . .

Step 7 -- Convert to Horizontal & Connect Ductwork

10

.

Step 8 -- Install Outside Air Hood

10

. . . . . . . . . . . . . . .

Economizer and Two Position Damper Hood

Package Removal and Setup — Factory Option

10

. .

Economizer Hood and Two--Position Hood

11

. . . . .

Step 9 -- Units with Hinged Panels Only

11

. . . . . . . . . .

Step 10 -- Install Flue Hood

12

. . . . . . . . . . . . . . . . . . . .

Step 11 -- Install Gas Piping

12

. . . . . . . . . . . . . . . . . . . .

Factory--Option Thru--Base Connections

(Gas Connections)

13

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 12 -- Install External Condensate Trap and Line

15

. .

Step 13 -- Make Electrical Connections

15

. . . . . . . . . . .

Field Power Supply

15

. . . . . . . . . . . . . . . . . . . . . . . .

Units with Factory--Installed

Non--Fused Disconnect or HACR

16

. . . . . . . . . . . . .

Units without Factory--Installed

Non--Fused Disconnect or HACR

17

. . . . . . . . . . . . .

All Units

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Convenience Outlets

18

. . . . . . . . . . . . . . . . . . . . . . .

HACR

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Factory--Option Thru--Base Connections

(Electrical Connections)

19

. . . . . . . . . . . . . . . . . . . .

Units without Thru--Base Connections

20

. . . . . . . . .

Field Control Wiring

20

. . . . . . . . . . . . . . . . . . . . . . .

Thermostat

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit without Thru--Base Connection Kit

20

. . . . . . .

Heat Anticipator Settings

20

. . . . . . . . . . . . . . . . . . .

Humidi--MiZer

R

Control Connections

21

. . . . . . . . . .

Humidi--MiZer -- Space RH Controller

21

. . . . . . . .

Low Ambient Control (Factory Option

23

. . . . . . . . . .

Comfort

Link Control

23

. . . . . . . . . . . . . . . . . . . . . . . .

PremierLink

t

(Factory Option)

28

. . . . . . . . . . . . . . .

Supply Air Temperature (SAT) Sensor

31

. . . . . . . . .

Outdoor Air Temperature (OAT) Sensor

31

. . . . . . .

EconoMi$er2

31

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field Connections

31

. . . . . . . . . . . . . . . . . . . . . . . . . .

Space Sensors

33

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connect Thermostat

33

. . . . . . . . . . . . . . . . . . . . . . .

Configure the Unit for Thermostat Mode

33

. . . . . .

Economizer Controls

34

. . . . . . . . . . . . . . . . . . . . . . . .

Indoor Air Quality (CO

2

sensor)

34

. . . . . . . . . . . . .

Outdoor Air Quality Sensor

34

. . . . . . . . . . . . . . . . .

Space Relative Humidity Sensor or

Humidistat Connections

35

. . . . . . . . . . . . . . . . . . . .

Smoke Detector/Fire Shutdown (FSD)

35

. . . . . . . . .

Filter Status Switch

36

. . . . . . . . . . . . . . . . . . . . . . . .

Supply Fan Status Switch

36

. . . . . . . . . . . . . . . . . . .

Remote Occupied Switch

36

. . . . . . . . . . . . . . . . . . .

Power Exhaust (output)

36

. . . . . . . . . . . . . . . . . . . . .

CCN Communication Bus

36

. . . . . . . . . . . . . . . . . .

RTU Open Control System

38

. . . . . . . . . . . . . . . . . . .

Supply Air Temperature (SAT) Sensor

41

. . . . . . . . .

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - SAFETY CONSIDERATIONS; WARNING

2 Outdoor Air Temperature (OAT) Sensor 41 . . . . . . . EconoMi$er2 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Connections 42 . . . . . . . . . . . . . . . . . . . . . . . . . . Space Temperature (SPT) Sensors 42 . . . . . . . . . . . . Indoor Air Quality (CO 2 ) Sensor 42 . ...

Page 6 - INSTALLATION; Jobsite Survey; Step 1 — Plan for Unit Location; NOTE

6 INSTALLATION Jobsite Survey Complete the following checks before installation. 1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa- tion requirements. 2. Determine unit location (from project plans) or select unit location. 3. Check for possible...

Page 7 - Roof Curb Mount —; Ductwork must be attached to curb and

7 Step 2 — Plan for Sequence of Unit Installation The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following...

Other Carrier Models