Bryant T1-NAC - Manual
Bryant T1-NAC – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – INSTALLATION; Step 1 — Thermostat Location; WARNING; CAUTION; Step 3 — Set Thermostat Configuration; Option 01 — Equipment Type
- Page 4 – WIRING DIAGRAMS
- Page 5 – Homeowner’s Guide; TROUBLESHOOTING; What if there is a green light on in the upper
- Page 7 – Bryant Heating & Cooling Systems
- Page 8 – THERMOSTAT LIMITED WARRANTY
T1--NAC
T1--NHP
LEGACY LINE--RNC
NON--PROGRAMMABLE THERMOSTAT
Installation Instructions
Designed and Assembled
in the USA.
US patents: US20060165149 A1, USD578026 SI, US6205041 B1
A07110
Legacy Line --- RNC Non --- Programmable Thermostat
NOTE
: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . .
INSTALLATION
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 — Thermostat Location
2
. . . . . . . . . . . . . . . . . . . . . . . .
Step 2— Install Thermostat
2
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 3 — Set Thermostat Configuration
2
. . . . . . . . . . . . . . . . .
Step 4 — Thermostat Operation
3
. . . . . . . . . . . . . . . . . . . . . . . .
Step 5 — Check Thermostat Operation
3
. . . . . . . . . . . . . . . . . .
WIRING DIAGRAMS
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency muse use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes and the current editions of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol
.
When you see this symbol on the unit and in the instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words
DANGER
,
WARNING
, and
CAUTION
. These words are used with the safety--alert symbol.
DANGER
identifies the most serious hazards which
will
result in
severe personal injury or death.
WARNING
signifies a hazard
which
could
result in personal injury or death.
CAUTION
is used
to identify unsafe practices which
may
result in minor personal
injury or product and property damage.
NOTE
is used to highlight
suggestions which
will
result in enhanced installation, reliability, or
operation.
INTRODUCTION
The Legacy Line--RNC Series thermostat is an electronic 24VAC,
non--programmable, manual changeover wall mount thermostat.
This thermostat uses a single setpoint to maintain and control room
temperature in both the heating and air conditioning modes. The
thermostat is designed to maintain +/-- 2
_
F accuracy. No batteries
are required; temperature, fan, mode, and installer configuration
settings are preserved with power off.
INSTALLATION CONSIDERATIONS
Air Conditioner Model
T1--NAC, Legacy Line--RNC Series Model air conditioner
thermostat, may be wired with or without connecting a common
wire between the indoor equipment and the thermostat. However, it
is recommended to use a common wire whenever possible.
Without a common wire this thermostat becomes “power stealing.”
This means it will need to steal a small amount of power from the
equipment to which it is connected.
NOTE
: Not all HVAC equipment is compatible with power
stealing type thermostats. All Bryant equipment is directly
compatible with this thermostat except the Thermostat Conversion
Kit, Part #TSTATXXCNV10. For all non--Bryant equipment,
consult the system equipment Installation Instructions before
applying this thermostat in a power stealing manner.
Heat Pump Model
T1--NHP, Legacy Line--RNC Series Model heat pump thermostat,
is compatible with all Bryant heat pump systems. It is NOT power
stealing and MUST have both the R and C terminals connected to
operate properly. This thermostat uses a green LED to indicate
auxiliary heat and emergency heat operation.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 INSTALLATION Step 1 — Thermostat Location Thermostat should be mounted: S Approximately 5 ft (1.5m) from floor. S Close to or in a frequently used room, preferably on an insidepartitioning wall. S On a section of wall without pipes or duct work. Thermostat should NOT be mounted: S Close to a windo...
4 WIRING DIAGRAMS A06566 Fig. 1 -- A/C Thermostat Typical Installation A06567 Fig. 2 -- HP Thermostat Typical Installation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. E 2012 Bryant Heating & Co...
T1--NAC T1--NHP LEGACY LINE--RNC NON--PROGRAMMABLE THERMOSTAT Homeowner’s Guide Designed and Assembled in the USA. A07110 Legacy Line --- RNC Non --- Programmable Thermostat 1. To Select the Mode: Use the H/C button to move between the choices. OFF, HEAT, COOL, or EMHT will appear on the display. EM...