Page 3 - Time Guard
Controls Upgrade Kit (036-150 Units) — The controls kit in-cludes high-pressure, loss-of-charge/low-pressure, and freezeprotection cutout switches. The high-pressure and loss-of-charge/low-pressure switches can be easily added by screwingthe switches onto Schrader-type fittings provided on the refri...
Page 4 - MODEL DESCRIPTION; LEGEND
Head Pressure Control — Kit consists of an outdoor-air ther-mostat that permits adequate head pressure control duringcooling operation at low outdoor-ambient temperatures. Refer to Trade Prices for more details or contact your localrepresentative. SUGGESTED USE: • When cooling at low-ambient outdoor...
Page 5 - ARI* CAPACITY RATINGS
ARI* CAPACITY RATINGS UNIT 558D NOMINAL TONS STANDARD CFM NET COOLING CAPACITY (Btuh) TOTAL kW SEER† EER SOUND RATING (Bels) Belt Drive Direct Drive 036 3 1200 35,000 4.0 10.0 9.7 8.7 8.2 048 4 1600 47,000 5.5 10.0 9.7 8.6 8.2 060 5 2000 57,500 6.7 10.0 9.7 8.5 8.2 UNIT NOMINAL TONS STANDARD CFM NET...
Page 8 - KO — Knockout
DIMENSIONAL DRAWING — 559F180,216 LEGEND KO — Knockout NOTES:1. Dimensions in ( ) are in millimeters. 2. Center of gravity. 3. Direction of airflow. 4. Ductwork to be attached to accessory roof curb or adapter only.5. For units with electric heat, a field-supplied 90° elbow must be installed in the ...
Page 11 - SERVICE PLATE SIZES
DIMENSIONAL DRAWING — ROOF CURB, 558D090-150 ROOF CURB ACCESSORY ‘‘A’’ UNIT SIZE 558D CRRFCURB003A00 1 8 -2 9 [356] 090-150 CRRFCURB004A00 2 8 -0 9 [610] SERVICE PLATE SIZES UNIT SIZE 558D ‘‘B’’ ‘‘C’’ ‘‘D’’ ALT DRAIN HOLE POWER CONTROL CONNECTOR PKG ACY 090-150 2 8 -8 7 ⁄ 16 9 [827] 1 8 -10 15 ⁄ 16 ...
Page 12 - DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS
DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS AND HORIZONTAL ADAPTER — 559F180-300 ACCESSORY PACKAGE NO. CURB HEIGHT DESCRIPTION ‘‘A’’ ‘‘B’’ ‘‘C’’ 308450-201 1 8 -2 9 (305) Standard Curb — 14 9 High — — — 308450-202 2 8 -0 9 (610) Standard Curb for Units Requiring High Installation — — — ...
Page 17 - SELECTION PROCEDURE (With 559F180 Example)
SELECTION PROCEDURE (With 559F180 Example) I Determine cooling and heating requirements at design conditions. Given: Cooling Capacity Required (TC) . . . . . . . . . 177,000 BtuhSensible Heat Capacity (SHC) . . . . . . . . . . 127,000 BtuhCondenser Entering-Air Temperature . . . . . . . . . . . . . ...
Page 18 - GROSS COOLING CAPACITIES
GROSS COOLING CAPACITIES 558D036 (3 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Total Sensible Total Sensible Total Sensible 900 0.11 72 42.8 20.0 2.91 40.8 19.4 3.14 38.7 18.6 ...
Page 48 - FAN RPM AT MOTOR PULLEY SETTINGS*; ELECTRIC HEAT MULTIPLICATION FACTORS
FAN RPM AT MOTOR PULLEY SETTINGS* UNIT MOTOR PULLEY TURNS OPEN 0 1 ⁄ 2 1 1 1 ⁄ 2 2 2 1 ⁄ 2 3 3 1 ⁄ 2 4 4 1 ⁄ 2 5 5 1 ⁄ 2 6 558D036† 1000 976 952 928 904 880 856 832 808 784 760 — — 558D048† 1185 1150 1115 1080 1045 1010 975 940 905 870 835 — — 558D060† 1300 1260 1220 1180 1140 1100 1060 1020 980 940...
Page 55 - OPERATING SEQUENCE
OPERATING SEQUENCE COOLING, UNITS WITHOUT ECONOMIZER — When thermo-stat calls for cooling, terminals G and Y1 are energized. The in-door (evaporator) fan contactor (IFC) and compressor contactorno. 1 (C1) are energized and evaporator-fan motor, compressorno. 1 (036-150 and 216-300) or unloaded compr...
Page 58 - Vertical Discharge Ducting; NEC — National Electrical Code; Horizontal Discharge Ducting
TYPICAL INSTALLATION — 558D090-150 Vertical Discharge Ducting NEC — National Electrical Code Horizontal Discharge Ducting 58
Page 59 - LEGEND FOR TYPICAL WIRING SCHEMATICS
TYPICAL INSTALLATION — 559F180-300 NEC — National Electrical Code NOTES:1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes. LEGEND FOR TYPICAL WIRING SCHEMATICS AHA — Adjustable...
Page 60 - APPLICATION DATA; will not
APPLICATION DATA 1. Units approved for outdoor installation only. 2. Ductwork (036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, either at-tach ductwork to unit, or use field-supplied flanges attachedto the horizontal discharge openings and attach all...
Page 61 - OPTION AND ACCESSORY LIST; Concentric Duct Air Distribution
APPLICATION DATA (cont) OPTION AND ACCESSORY LIST ITEM OPTION* ACCESSORY† Durablade Economizer (036-150; Includes Hood) X X Parablade Economizer (036-150) X Integrated Economizer (180-300) X X Manual Outdoor-Air Dampers** X X†† Controls Upgrade Kit (036-150) | X X Condenser Coil Grille (036-150) X X...
Page 62 - EVAPORATOR-FAN MOTOR PERFORMANCE
APPLICATION DATA (cont) EVAPORATOR-FAN MOTOR PERFORMANCE UNIT EVAPORATOR-FAN MOTOR UNIT VOLTAGE MAXIMUM ACCEPTABLECONTINUOUS BHP* MAXIMUM ACCEPTABLE OPERATING WATTS MAXIMUM AMP DRAW 558D036 Standard 208/230 0.34 440 2.9 460 1.4 575 1.4 Alternate 208/230 1.00 1000 5.1 460 2.3 575 2.3 558D048 Standard...
Page 63 - UNIT; Fan Performance Using Accessory
APPLICATION DATA (cont) Durablade Economizer/Two-Position Damper Barometric Relief Damper Characteristics (558D036-150 Only) Parablade Economizer Barometric Relief Damper Characteristics — 558D090-150 Parablade Economizer Barometric Relief Damper Characteristics — 558D036-072 EVAPORATOR-FAN MOTOR EF...
Page 64 - ELECTRIC HEATER CAPACITIES —
ELECTRIC HEATER CAPACITIES — 558D036-150 UNIT 558D VOLTAGE (60 Hz) ACCESSORY kW 036 208/230 (single phase) 4.46.58.7 10.5 13.0* 208/230 (3 phase) 4.46.58.7 10.516.0 460 (3 phase) 6.08.8 11.5 14.0 048 208/230 (single phase) 4.48.7 13.0*17.4*21.0* 208/230 (3 phase) 6.58.7 16.0 21.0* 460 (3 phase) 6.0 ...
Page 68 - Bryant; Air Conditioning
Bryant Air Conditioning Copyright 1996 Carrier Corporation SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Printed in U.S.A. 6/96 CATALOG NO. BY-3255-818