Bryant 580f - Manual

Bryant 580f

Bryant 580f – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
Page: / 64

Table of Contents:

  • Page 6 – When connecting the gas line to the; MAXIMUM ALLOWABLE; Fig. 4 — Unit Leveling Tolerances; NOTE; Fig. 5A — Condensate Drain Pan; Trap should be deep enough to offset maximum unit static dif-; Fig. 5B — External Trap Condensate Drain
  • Page 7 – Fig. 6 — Rigging Details
  • Page 8 – Table 1 — Physical Data
  • Page 12 – Table 2A — Electrical Data (Without Convenience Outlet)
  • Page 13 – Table 2B — Electrical Data (With Convenience Outlet)
  • Page 15 – Hood; Fig. 17 — Typical Access Panel Locations
  • Page 16 – Fig. 21 — Filter Installation
  • Page 17 – Fig. 23 — Barometric Flow Capacity
  • Page 19 – Fig. 26 — Indoor Air Quality Voltage Setting
  • Page 21 – Fig. 29 — Enthalpy Changeover Settings; CURRENT; RH —; Relative Humidity; Fig. 30 — Humidity Sensor Current vs. Humidity
  • Page 22 – L. Indoor Air Humidity Sensor; The remote potentiometer (see below) will override; P. Remote Potentiometer Occupied Minimum Position; Fig. 31 — Return Air Humidity Sensor
  • Page 23 – Fig. 32 — Demand Ventilation Control
  • Page 24 – Fig. 34 — Belt Drive Motor Mounting
  • Page 35 – Bhp; Watts —; Input Watts to Motor
  • Page 36 – GENERAL FAN PERFORMANCE NOTES; Use of a field-supplied motor may affect wire sizing. Contact your
  • Page 38 – Table 34B — Altitude Compensation* — Low NOx Units
  • Page 39 – A. Integrated Display
  • Page 40 – Table 35 — EconoMi$er+ Inputs and Outputs
  • Page 42 – Before performing Step 6, be ready to push button
  • Page 51 – TON UNIT CHARGING CHART
  • Page 52 – LOW HEAT; Fig. 45 — Burner Section Details
  • Page 54 – H. Error Code 8 — E2 Test Failure; at least 3 seconds until all LEDs flash.; L. Unit Always in Unoccupied Mode
  • Page 56 – Table 43 — Cooling Service Analysis
  • Page 57 – Fig. 48 — Typical Unit Wiring Diagram; LEGEND
  • Page 60 – APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURATION SETTINGS; Enter the job specific settings in the “Job Setting” column below.
  • Page 61 – INDEX
  • Page 62 – SERVICE TRAINING
  • Page 64 – ELECTRICAL
Loading the manual

Cancels: II 580F-36-3

II 580F-36-4

1/15/04

IMPORTANT — READ BEFORE INSTALLING

1. Read and become familiar with these installation

instructions before installing this unit (Fig. 1A and
1B).

2. Be sure the installation conforms to all applicable lo-

cal and national codes.

3. These instructions contain important information for

the proper maintenance and repair of this equipment.
Retain these instructions for future use.

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36

I. Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . 1

II. Step 2 — Field Fabricate Ductwork

. . . . . . . . . . . . . 4

III. Step 3 — Install External Trap for

Condensate Drain

. . . . . . . . . . . . . . . . . . . . . . . . . . . 4

IV. Step 4 — Rig and Place Unit

. . . . . . . . . . . . . . . . . . . 4

V. Step 5 — Install Flue Hood

. . . . . . . . . . . . . . . . . . . . 6

VI. Step 6 — Install Gas Piping

. . . . . . . . . . . . . . . . . . . 6

VII. Step 7 — Make Electrical Connections

. . . . . . . . . 10

VIII. Step 8 — Adjust Factory-Installed Options

. . . . . . 14

IX. Step 9 — Adjust Evaporator-Fan Speed

. . . . . . . . 24

PRE-START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-47

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-52

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-57

APPENDIX A — ECONOMI$ER+ LABEL

. . . . . . . . . . . 58, 59

APPENDIX B — JOB SPECIFIC ECONOMI$ER+

CONFIGURATION SETTINGS

. . . . . . . . . . . . . . . . . . . . . 60

INDEX

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that apply.

Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.

INSTALLATION

Unit is shipped in the vertical duct configuration. To convert to
horizontal configuration, remove screws from side duct open-
ing covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 2.

Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.

I. STEP 1 — PROVIDE UNIT SUPPORT

A. Roof Curb

Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 3. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory
thru-the-bottom power and gas connection package must be
installed before the unit is set on the roof curb.
If field-
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied

3

/

4

-in. pipe coupling and gas plate assembly

to mount the thru-the-roof curb connection to the roof curb.
Gas connections and power connections to the unit must be
field installed after the unit is installed on the roof curb.

If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service con-
nections to the basepan in accordance with the accessory
installation instructions.

IMPORTANT:

The gasketing of the unit to the roof curb is

critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 3. Improperly applied gasket can
result in air leaks and poor unit performance.

Curb should be level. Unit leveling tolerances are shown in
Fig. 4. This is necessary for unit drain to function properly.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.

WARNING:

Disconnect gas piping from unit when

leak testing at pressure greater than

1

/

2

psig. Pres-

sures greater than

1

/

2

psig will cause gas valve damage

resulting in hazardous condition. If gas valve is sub-
jected to pressure greater than

1

/

2

psig, it must be

replaced before use. When pressure testing field-
supplied gas piping at pressures of

1

/

2

psig or less, a

unit connected to such piping must be isolated by man-
ually closing the gas valve.

WARNING:

Before performing service or mainte-

nance operations on unit, turn off main power switch
to unit and install a lockout tag. Electrical shock could
cause personal injury.

CAUTION:

Ensure voltage listed on unit data plate

agrees with electrical supply provided for the unit.

installation, start-up and
service instructions

SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS

580F

Dura

Pac Series

Sizes 036-073

3 to 6 Tons

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 6 - When connecting the gas line to the; MAXIMUM ALLOWABLE; Fig. 4 — Unit Leveling Tolerances; NOTE; Fig. 5A — Condensate Drain Pan; Trap should be deep enough to offset maximum unit static dif-; Fig. 5B — External Trap Condensate Drain

— 6 — Do not install unit in an indoor location. Do not locate unitair inlets near exhaust vents or other sources of contami-nated air. Be sure that unit is installed such that snow will not blockthe combustion intake or flue outlet. Unit may be installed directly on wood flooring or on ClassA, B, o...

Page 7 - Fig. 6 — Rigging Details

— 7 — NOTES: 1. Dimensions in ( ) are in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Usewooden top skid when rigging to prevent rigging straps from damaging unit. 3. Unit weights do not ...

Page 8 - Table 1 — Physical Data

— 8 — Table 1 — Physical Data LEGEND *Evaporator coil fin material/condenser coil fin material. Contact your local rep- resentative for details about coated fins. †Weight of 14-in. roof curb. **Single phase/three-phase. ††Rollout switch lockout is manually reset by interrupting power to unit or rese...

Other Bryant Models

All Bryant Other