Page 2 - General
349209-JIM-H-0514 2 Johnson Controls Unitary Products General Johnson Controls Series 20 J**ZR models are either single package air conditions equipped with optional factory installed electric heaters, or single package gas-fired central heating furnaces with cooling unit. Both are designed for outd...
Page 3 - Johnson Controls Unitary Products; Inspection; Design certified by CSA as follows:
349209-JIM-H-0514 Johnson Controls Unitary Products 3 Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available during brazing operations. Inspection As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, ...
Page 4 - Nomenclature; Z R; 5-25 Ton Series 20 Model Number Nomenclature
349209-JIM-H-0514 4 Johnson Controls Unitary Products Nomenclature Z R J15 N24 A 2 A AA 2 0 1 2 4 A Z = A/C, Single Pkg., R-410A Product Category 2 = Second Generation Product Generation C00 = Cooling Only. No field installed electric heat Heat Type and Nominal Heat Capacity N24 = 240 MBH Output Alu...
Page 5 - Installation; Installation Safety Information
349209-JIM-H-0514 Johnson Controls Unitary Products 5 Installation Installation Safety Information Read these instructions before continuing this appliance installation. This is an outdoor combination heating and cooling unit. The installer must assure that these instructions are made available to t...
Page 6 - Figure 1: J15 thru 25 ZR Component Location; High Efficiency
349209-JIM-H-0514 6 Johnson Controls Unitary Products Figure 1: J15 thru 25 ZR Component Location Unit Control Board 110 Volt Convenience Outlet(“Powered” or “Non-Powered” Optional) Disconnect Location(Optional Disconnect Switch) Bottom Power and Control Wiring Entry Power Ventor Motor Electric Heat...
Page 7 - Location; Unit is designed for; Clearances; Rigging And Handling; MUST; be used; LENGTH OF FORKS MUST BE A MINIMUM OF 90 INCHES.
349209-JIM-H-0514 Johnson Controls Unitary Products 7 Location Use the following guidelines to select a suitable location for these units: 1. Unit is designed for outdoor installation only . 2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the...
Page 8 - Figure 2: Unit 4 Point Load Weight; Weights and Dimensions; Size
349209-JIM-H-0514 8 Johnson Controls Unitary Products Figure 2: Unit 4 Point Load Weight Figure 3: Unit 6 Point Load Weight Figure 4: Center of Gravity All panels must be secured in place when the unit is lifted. The condenser coils should be protected from rigging cable damage with plywood or other...
Page 9 - Figure 5: J15 thru 25 ZR Unit Dimensions Front View
349209-JIM-H-0514 Johnson Controls Unitary Products 9 Figure 5: J15 thru 25 ZR Unit Dimensions Front View Note: All entry holes should be sealed to prevent rain water entry into building. Table 3: J15 thru 25 ZR Unit Accessory Weights Unit Accessory Weight (lbs.) Shipping Operating Economizer 165 16...
Page 10 - Figure 6: J15 thru 25 ZR Unit Dimensions Rear View; Connect ductwork to the flanges on those panels.
349209-JIM-H-0514 10 Johnson Controls Unitary Products Figure 6: J15 thru 25 ZR Unit Dimensions Rear View NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the su...
Page 11 - Figure 7: J15 thru 25 ZR Unit Dimensions Rain Hood; Direction; LH View
349209-JIM-H-0514 Johnson Controls Unitary Products 11 Figure 7: J15 thru 25 ZR Unit Dimensions Rain Hood Note: ELEC/ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS/ELEC Models: A 1" clearance must be provided bet...
Page 12 - Figure 8: J15 thru 25 ZR Roof Curb; Ductwork; Fixed Outdoor Air Intake Damper
349209-JIM-H-0514 12 Johnson Controls Unitary Products Figure 8: J15 thru 25 ZR Roof Curb Ductwork Ductwork should be designed and sized according to the methods in Manual D of the Air Conditioning Contractors of America (ACCA) or as recommended by any other recognized authority such as ASHRAE or SM...
Page 13 - Figure 9: Fixed Outdoor Air Damper; Condensate Drain; Figure 10: Condensate Drain; Compressors; POE oil; in the system. This type of oil is highly
349209-JIM-H-0514 Johnson Controls Unitary Products 13 Figure 9: Fixed Outdoor Air Damper Condensate Drain Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the one-inch NPT female connection on the unit to an open drain. NOTE: Th...
Page 14 - Power Wiring Detail
349209-JIM-H-0514 14 Johnson Controls Unitary Products electrically grounded in accordance with NEC and CEC as specified above and/or local codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and...
Page 15 - Thermostat Wiring; Wire Size
349209-JIM-H-0514 Johnson Controls Unitary Products 15 Figure 11: Field Wiring Disconnect - Cooling Unit With/Without Electric Heat Thermostat Wiring The thermostat should be located on an inside wall approximately 56 inch above the floor where it will not be subject to drafts, sun exposure or heat ...
Page 16 - Figure 12: Typical Field Wiring; TYPICAL
349209-JIM-H-0514 16 Johnson Controls Unitary Products Figure 12: Typical Field Wiring THERMOSTAT 1 TERMINALS ( RCB ) REHEAT CONTROL BOARD RC RH Y1 Y2 W1 W2 G C X1 X3 X4 A1 A2 T T R Y1 Y2 W1 W2 G C OCC HUM 1 2 3 4 HUM TERMINAL BLOCK RH 3 2 1 Electronic programmable Thermostat 2ET0770010024 ( include...
Page 17 - Electrical Data
349209-JIM-H-0514 Johnson Controls Unitary Products 17 Table 8: Electrical Data J15 thru 25 ZR - Standard Drive Without Powered Convenience Outlet Size (Tons) Volt Compressors (each) OD Fan Motors (each) SupplyBlower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) 1. Minimum Circuit Ampacity...
Page 18 - J15 thru 25 ZR - Standard Drive With Powered Convenience Outlet
349209-JIM-H-0514 18 Johnson Controls Unitary Products J15 thru 25 ZR - Standard Drive With Powered Convenience Outlet Size (Tons) Volt Compressors (each) OD Fan Motors (each) SupplyBlower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) 1. Minimum Circuit Ampacity. Max Fuse 2 / Breaker 3 Siz...
Page 20 - J15 thru 25 ZR - High Static Drive With Powered Convenience Outlet
349209-JIM-H-0514 20 Johnson Controls Unitary Products J15 thru 25 ZR - High Static Drive With Powered Convenience Outlet Size (Tons) Volt Compressors (each) OD Fan Motors (each) SupplyBlower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) 1. Minimum Circuit Ampacity. Max Fuse 2 / Breaker 3 ...
Page 21 - J25ZR - Low Static Drive Without Powered Convenience Outlet
349209-JIM-H-0514 Johnson Controls Unitary Products 21 J25ZR - Low Static Drive Without Powered Convenience Outlet Size (Tons) Volt Compressors (each) OD Fan Motors (each) SupplyBlower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) 1. Minimum Circuit Ampacity. Max Fuse 2 / Breaker 3 Size (A...
Page 22 - J15 thru 25 ZR Physical Data
349209-JIM-H-0514 22 Johnson Controls Unitary Products Table 9: J15 thru 25 ZR Physical Data Component Models J15ZR J20ZR J25ZR Nominal Tonnage 15 20 25 AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (Btu) 189 243 303 AHRI net capacity (Btu) 180 236 288 EER 11.2 12.1 10.0 SEER - - - IEER 12....
Page 23 - Optional Electric Heat; J15 thru 25 ZR Physical Data (Continued)
349209-JIM-H-0514 Johnson Controls Unitary Products 23 Optional Electric Heat The factory-installed heaters are wired for single point power supply. Power supply need only be brought into the single point terminal block. These CSA approved heaters are located within the central compartment of the un...
Page 24 - Optional Gas Heat
349209-JIM-H-0514 24 Johnson Controls Unitary Products Optional Gas Heat These gas-fired heaters have aluminized-steel or optional stainless steel, tubular heat exchangers with spark ignition with proven pilot. Gas Piping Proper sizing of gas piping depends on the cubic feet per hour of gas flow req...
Page 25 - Gas Connection; Gas piping recommendations:; Lp Units, Tanks And Piping; FIRE OR EXPLOSION HAZARD; Do not use Teflon tape.
349209-JIM-H-0514 Johnson Controls Unitary Products 25 Gas Connection The gas supply line can be routed within the space and roof curb, exiting through the unit’s basepan. Refer to Figure 5 for the gas piping inlet location. Typical supply piping arrangements are shown in Figures 13 and 14. All pipe...
Page 26 - Economizer Interface Overview; • Keypad and menu navigation
349209-JIM-H-0514 26 Johnson Controls Unitary Products Check all connections for leaks when piping is completed using a soap solution. NEVER USE A FLAME. Vent And Combustion Air Two vent hoods and a combustion air hood (with screens) are shipped attached to the blower housing in the blower compartme...
Page 27 - RATEMP
349209-JIM-H-0514 Johnson Controls Unitary Products 27 Keypad The four navigation buttons illustrated in Fig. 16 are used to scroll through the menus and menu items, select menu items, and to change parameter and configuration settings. Using the Keypad with Menus To use the keypad when working with...
Page 29 - duct static set point
349209-JIM-H-0514 Johnson Controls Unitary Products 29 ductwork and to the atmosphere. Connect the tubing from the 'HIGH' pressure tap of the transducer to a static pressure tap (field supplied) in the supply duct located at a point where constant pressure is expected. To prevent an unstable signal ...
Page 30 - Factory-installed VFD; - routes power through the VFD for modulating; LINE; - routes power to the VFD but not to the motor to
349209-JIM-H-0514 30 Johnson Controls Unitary Products Factory-installed VFD The factory-installed VFD is mounted in the Blower Access Compartment above the blower assembly. The drive comes wired from the factory to include both 3-phase power and control connections (run permit signal, speed referen...
Page 32 - Figure 19: Altitude/Temperature Correction Factors; What are the corrected CFM, static pressure, and; Table 15: Altitude/Temperature Correction Factors; Air; Correction Factor
349209-JIM-H-0514 32 Johnson Controls Unitary Products Figure 19: Altitude/Temperature Correction Factors The examples below will assist in determining the airflow performance of the product at altitude. Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if ...
Page 33 - Table X: RPM Selection
349209-JIM-H-0514 Johnson Controls Unitary Products 33 Drive Selection 1. Determine side or bottom supply duct application. 2. Determine desired airflow 3. Calculate or measure the amount of external static pressure. 4. Using the operating point determined from steps 1, 2 & 3, locate this point ...
Page 34 - Table 16: Air Flow Performance - Side Duct Application; Air Flow
349209-JIM-H-0514 34 Johnson Controls Unitary Products Table 16: Air Flow Performance - Side Duct Application J15ZR (15 Ton) Side Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for addition...
Page 36 - Table 17: Air Flow Performance - Bottom Duct Application
349209-JIM-H-0514 36 Johnson Controls Unitary Products Table 17: Air Flow Performance - Bottom Duct Application J15ZR (15 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for addi...
Page 37 - Table 18: RPM Selection
349209-JIM-H-0514 Johnson Controls Unitary Products 37 J25ZR (25 Ton) Bottom Duct Air Flow (CFM) Available External Static Pressure - IWG 1 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Low Static 7.5 H...
Page 38 - Air Balance; Figure 20: Pressure Drop Across A Dry Indoor Coil Vs.; Table 20: Power Exhaust Specifications
349209-JIM-H-0514 38 Johnson Controls Unitary Products Air Balance Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be ...
Page 39 - Supply Air Drive Adjustment; Pulleys can be adjusted in half turn increments.; Operation; Cooling Sequence Of Operation; The call is passed to the; Continuous Blower
349209-JIM-H-0514 Johnson Controls Unitary Products 39 Supply Air Drive Adjustment The RPM of the supply air blower will depend on the required CFM, the unit accessories or options and the static resistances of both the supply and the return air duct systems. With this information, the RPM for the s...
Page 40 - Optional VAV Startup and Control; Figure 21: Occupied Jumper; Simplicity; No Outdoor Air Options
349209-JIM-H-0514 40 Johnson Controls Unitary Products Optional VAV Startup and Control For units with VFD and VAV control, the unit must first be put into the Occupied Mode to start operation. The default setting for all VAV units is 'Unoccupied', therefore the installer must add a jumper wire betw...
Page 43 - Compressor Protection; is utilized to prevent operation of a compressor; Flash Codes; Reheat Mode Sequence Of Operation; “Normal” Mode; All safety devices function as previously described.
349209-JIM-H-0514 Johnson Controls Unitary Products 43 controlled. On any fault, only the associated system will be affected by any safety/preventive action. The other refrigerant system will continue in operation unless it is affected by the fault as well. The unit control board monitors the temper...
Page 44 - Figure 22: Reheat Control Board; HGR
349209-JIM-H-0514 44 Johnson Controls Unitary Products Figure 22: Reheat Control Board R Y1 Y2 G W1 OCC C W2 P4 P5 P6 P3 COM HGRR HGR HUM K1 K2 K4 K3 ` MODE SELECTION JUMPER DEHUMIDISTAT HARNESS CONNECTION
Page 46 - Figure 25: System Piping Schematic; Electric Heating Sequence Of Operations; Open in
349209-JIM-H-0514 46 Johnson Controls Unitary Products Figure 25: System Piping Schematic Electric Heating Sequence Of Operations The following sequence describes the operation of the electric heat section. Single-stage heating: (applies only to 18 KW heater, all other heaters MUST use a two-stage t...
Page 47 - Gas Heating Sequence Of Operations
349209-JIM-H-0514 Johnson Controls Unitary Products 47 Electric Heat Operation Errors Temperature Limit If the UCB senses zero volts from the high temperature limit, the indoor blower motor is immediately energized. This limit is monitored regardless of unit operation status, i.e. the limit is monit...
Page 48 - Figure 26: Gas Valve Piping
349209-JIM-H-0514 48 Johnson Controls Unitary Products speed of the draft motor reaches approximately 2500 RPM, the centrifugal switch contact, located on the end of the draft motor shaft, closes to power the first stage ignition module “IC1”, thru the “RW1-1” contacts. Ignition module “IC1” will im...
Page 49 - Units; Burner Compartment
349209-JIM-H-0514 Johnson Controls Unitary Products 49 Safety Controls The UCB monitors the temperature limit switch of gas heat units. The control circuit includes the following safety controls: Limit Switch (LS) This control is located inside the gas heat compartment and is set to open at the temp...
Page 51 - Shut Down; Checking Gas Heat Input; Manifold Gas Pressure Adjustment; Seconds for
349209-JIM-H-0514 Johnson Controls Unitary Products 51 Shut Down 1. Set the thermostat to the lowest temperature setting. 2. Turn “OFF” all electric power to unit. 3. Open gas heat access panel. 4. Turn gas valve clockwise to “OFF” position (See Figure 30). Checking Gas Heat Input 1. Turn off all ot...
Page 52 - Pilot Checkout; Remove the gas piping closure panel.; Figure 29: Typical Flame; Burners are now accessible for service.; Burner Air Shutter Adjustment
349209-JIM-H-0514 52 Johnson Controls Unitary Products Pilot Checkout The pilot flame should envelope the end of the flame sensor. To adjust pilot flame, (1) remove pilot adjustment cover screw, (2) increase or decrease the clearance for air to the desired level, (3) be sure to replace cover screw a...
Page 53 - Charging The Unit; 5 Ton Charging Chart; 0 Ton Charging Chart
349209-JIM-H-0514 Johnson Controls Unitary Products 53 Charging The Unit Figure 31: J15ZR (15 Ton) Charging Chart Figure 32: J20ZR (20 Ton) Charging Chart 15 Ton Charging Chart 250 300 350 400 450 500 550 125 130 135 140 145 150 155 160 Suction Pressure (psi) Discharge Pressure (psi) 115º 105º 95º 8...
Page 54 - Troubleshooting; Cooling Troubleshooting Guide; 5 Ton Charging Chart; Use extreme care when working with live; Check the unit nameplate for the correct line
349209-JIM-H-0514 54 Johnson Controls Unitary Products Figure 33: J25ZR (25 Ton) Charging Chart Troubleshooting Cooling Troubleshooting Guide On calls for cooling, if the compressors are operating but the supply air blower motor does not energize after a short delay (the room thermostat fan switch i...
Page 57 - Gas Heat Troubleshooting Guide
349209-JIM-H-0514 Johnson Controls Unitary Products 57 2. Check for line voltage at the compressor contactor, M1, and that the contactor is pulled in. Check for loose wiring between the contactor and the compressor. 3. If M1 is pulled in and voltage is supplied at M1, lightly touch the compressor ho...
Page 59 - Unit Control Board Flash Codes
349209-JIM-H-0514 Johnson Controls Unitary Products 59 making good electrical connection. Check to make sure that the ceramic insulator on the pilot ignitors or sensors is not broken or cracked, if all are intact, replace the ignition control IC1 or IC2. The draft motor runs and the ignitor sparks a...
Page 60 - Figure 34: Unit Control Board
349209-JIM-H-0514 60 Johnson Controls Unitary Products Figure 34: Unit Control Board Table 27: Unit Control Board Flash Codes FLASH CODE DESCRIPTION GREEN LED 16 RED LED 8 RED LED 4 RED LED 2 RED LED 1 On Steady This is a Control Failure - - - - - 1 Flash Not Applicable - - - - - 2 Flashes Control w...
Page 61 - Unit Control Board Option Setup; Option Byte Setup; Ambient Lockout; Heat Delay Setup; Table 29: VAV Control Board Flash Codes
349209-JIM-H-0514 Johnson Controls Unitary Products 61 Unit Control Board Option Setup Option Byte Setup • Enter the Option Setup mode by pushing the OPTION SETUP / STORE button, and holding it for at least 2 seconds. • The green status LED (Option Byte) will be turned on and the red status LED (Hea...
Page 62 - WARRANTY STATEMENT; COMMERCIAL PACKAGE UNITS
349209-JIM-H-0514 62 Johnson Controls Unitary Products Start-Up Sheet 1034349-UCL-A-0313 START-UP & SERVICE DATA INSTRUCTION START-UP CHECKLIST Date: _______________________________________________________________________________________________________ Job Name: ________________________________...
Page 63 - SAFETY WARNINGS; ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER:
349209-JIM-H-0514 Johnson Controls Unitary Products 63 1034349-UCL-A-0313 2 Unitary Products Group SAFETY WARNINGS The inspections and recording of data outlined in this procedure are required for start-up of Johnson Controls/UPG's packaged products. Industry recognized safety standards and practice...
Page 64 - REFERENCE
349209-JIM-H-0514 64 Johnson Controls Unitary Products 1034349-UCL-A-0313 Unitary Products Group 3 REFERENCE General Inspection Completed See Notes Unit inspected for shipping, storage, or rigging damage
Unit installed with proper clearances
Unit installed within slope limitations
Refrig...
Page 65 - Operating Measurements - Air Flow; Device
349209-JIM-H-0514 Johnson Controls Unitary Products 65 1034349-UCL-A-0313 4 Unitary Products Group Operating Measurements - Air Flow ELECTRICAL DATA T1 - T2 ____________________________ Volts Control Voltage ______________________ Volts T2 - T3 ____________________________ Volts T1 - T3 ____________...
Page 66 - OPERATING MEASUREMENTS - COOLING
349209-JIM-H-0514 66 Johnson Controls Unitary Products 1034349-UCL-A-0313 Unitary Products Group 5 OPERATING MEASUREMENTS - COOLING REFRIGERANT SAFETIES OPERATING MEASUREMENTS - GAS HEATING Fuel Type:
Natural Gas
LP Gas Stage Discharge Pressure Discharge Temp. Liquid Line Temp. 1 1. Liquid tempe...
Page 67 - York International Corporation; OPERATIONAL MEASUREMENTS - STAGING CONTROLS; Verify Proper Operation of Heating/Cooling Staging Controls
Subject to change without notice. Printed in U.S.A. 349209-JIM-H-0514 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 349209-JIM-G-1213 York International Corporation 5005 York Drive Norman, OK 73069 OPERATIONAL MEASUREMENTS - STAGING CONTROLS FINAL - INSPECTION OBSERVED ...