Page 2 - Unitary Products Group; Physical and Electrical Data - 1 Phase; MODEL
036-21137-004 Rev. C (0505) 2 Unitary Products Group Physical and Electrical Data - 1 Phase MODEL H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC042S06 H2RC048S06 H4RC060S06 Unit Supply Voltage 208/230 – 1 – 60 Normal Voltage Range 187 to 252 Minimum Circuit Ampacity 1 10.1 14.1 16.5 19.7 26.2 28.5...
Page 3 - Outdoor Unit; Indoor Coil
036-21137-004 Rev. C (0505) Unitary Products Group 3 Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase Outdoor Unit H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC042S06 H2RC048S06 H4RC060S06 Unit Orifice (s) 1 53 59 63 73 78 87 – Factory R-22 Charge, lbs-oz. 4 - 9 4 - 7 5...
Page 6 - COOLING CAPACITY - With Air Handler Coils
036-21137-004 Rev. C (0505) 6 Unitary Products Group - = Not applicable. COOLING CAPACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEAT KW W RATED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOTAL SENS. 1 PH 12 SEER AC WITH N1AH / G2FD H2RC018S06 N1AHB08...
Page 7 - COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
036-21137-004 Rev. C (0505) Unitary Products Group 7 COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RATED CFM NET MBH SEER W/O TXV SEER + TXV 1 EER TOTAL SENS. H2RC018S06 525675 14,17 G1FA024S14,17 600 19.2 13.0...
Page 10 - COOLING CAPACITY - With Variable Speed Furnaces
036-21137-004 Rev. C (0505) 10 Unitary Products Group COOLING CAPACITY - With Variable Speed Furnaces UNIT MODEL VARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RATED CFM NET MBH SEER W/O TXV SEER + TXV 2 EER TOTAL SENS. 1 PH 12 SEER AC - VARIABLE SPEED 3 H2RC018S06 P1DUA12V/PV8A12****UH G1FA024...
Page 12 - SOUND POWER RATINGS; Liquid
036-21137-004 Rev. C (0505) 12 Unitary Products Group All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. ACCESSORIES* Refer to Price Manual for specific model numbers. Hard Start Kit - Provides increased starting torque for ar...
Page 13 - TYPICAL INSTALLATION; NOTE: ALL OUTDOOR WIRING
036-21137-004 Rev. C (0505) Unitary Products Group 13 TYPICAL INSTALLATION TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application MINIMUM 18” SERVICE ACCESSCLEARANCE ON ONE SIDE 60” OVERHEADCLEARANCE 10” CLEARANCECOIL AREA WEATHERPROOFDISCONNECTSWITCH THERMOSTAT TO FUR...
Page 14 - COOLING PERFORMANCE DATA; AIR CONDITIONER MODEL NO.; ENTERING AIR; Coil; KW
036-21137-004 Rev. C (0505) 14 Unitary Products Group Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature a...
Page 24 - Copyright; MATCHING INDOOR COMPONENTS; * Available with factor; FOR NON-FURNACE APPLICATIONS
Subject to change without notice. Printed in U.S.A. 036-21137-004 Rev. C (0505) Copyright © by York International Corp. 2005. All rights reserved. Supersedes: 036-21137-004 Rev. B (0105) Unitary 5005 Norman Products York OK Group Drive 73069 MATCHING INDOOR COMPONENTS G1UA1/2 CASEDUPFLOW G1HDHORIZON...