Page 2 - FIELD-INSTALLED ACCESSORIES; Power exhaust is not available as a field installed option.; TABLE OF CONTENTS
FIELD-INSTALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERSIncludes a slide-in / plug-in damper assembly with fullymodulating spring-return motor actuator capable of introducingup to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that moni...
Page 3 - RATINGS; MODEL DCG; CAPACITY RATINGS - Cooling / Electric Heating
RATINGS ® SUNLINE 2000 MODEL DCG (Gas Heating) (OPTION / ACCESS.) DCE UNITS D*CG UNITS (OPTION / ACCESSORY) THROWAWAY ALUMINIZED STEEL FEMALE Model Rating 1 Point Total Output, Mbh / kW Total Input, kW COP 2 EER 3 Sensible Output, Mbh / kW Latent Output, Mbh / kW Electric Heat4 Nominal Capacity, k...
Page 4 - COOLING CAPACITIES (m
COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITS Air On Evaporator Coil Total Cap. 1 kW Power Input 2 kW Sensible Capacity 1 , kW Entering Dry Bulb Temp., ° C m 3 /s WB ° C 32 30 28 26 24 22 @27 ° C Air Temperature on Condenser Coil 3.40 23 66.4 14.7 51 44 37 30 23 - 21 62.3 14.4 59 52 44 37 30 23 1...
Page 8 - BLOWER PERFORMANCE; w/DOWNFLOW DUCT APPLICATIONS
BLOWER SPEED, RPM MOTOR PULLEY (TURNS OPEN)* AIRFLOW 2.10 m 3 /s 2.45 m 3 /s 2.80 m 3 /s 3.10 m 3 /s 3.40 m 3 /s ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) 845 6.0 173 1.8 2.2 138 2.2...
Page 12 - BLOWER MOTOR AND DRIVE DATA
UNIT SIZE BLOWER RANGE (RPM) MOTOR 1 ADJUSTABLE MOTOR PULLEY 2 FIXED BLOWER PULLEY BELT (NOTCHED) kW/HP FRAME SIZE EFF. (%) PITCH DIA. (mm/in.) BORE (mm/in.) DESIG- NATION PITCH DIA. (mm / in.) BORE (mm/in.) DESIG- NATION PITCH LENGTH (mm/in.) DESIG- NATION QTY STD. DRIVE 180 845-1040 3.0 / 4.0 184T...
Page 13 - ELECTRICAL DATA; Cooling Only Units and Units With Gas Heat
UNIT SIZE POWER SUPPLY COMPRESSOR OUTDOOR FAN MOTOR, (#1 & #2) FLA, EACH SUPPLY AIR BLOWER MOTOR, (FLA) TOTAL UNIT AMPACITY, (AMPS) MAX. FUSESIZE 1 MIN. WIRE SIZE 2 , (mm 2 /AWG) RLA LRA 3 kW 4 HP 5.6 kW 7.5 HP 3 kW4 HP 5.6 kW7.5 HP #1 #2 #1 #2 180 380/400/415-3+N-50 19.2 9.6 146 73 2.4 8.6 - 47...
Page 14 - PHYSICAL DATA; Units With Supplemental Electric Heating
UNIT SIZE POWER SUPPLY(VOLTS) HEATER OPTION MINIMUM CIRCUIT AMPACITY (AMPS) MAXIMUM FUSE SIZE 1 MINIMUM WIRE SIZE 2 (mm 2 /AWG) MODEL OUTPUT kW STAGES AMPS 180 380-3+N-50 E018E036E054E072 11.3 22.633.845.1 1222 17.134.351.468.6 47.0 53.6 75.0 96.5 60 60 80100 10 / 816 / 625 / 435 / 2 415-3+N-50 E018...
Page 15 - UTILITIES ENTRY DATA; RETURN AIR
All dimensions are in millimeters and inches,unless otherwise specified. They are subjectt o c h a n g e w i t h o u t n o t i c e . C e r t i f i e ddimensions will be provided upon request. CLEARANCES (mm / in.) Front 914 / 36 Back 610 / 24 (Less Economizer)1245 / 49 (With Economizer) Left Side (F...
Page 18 - TYPICAL APPLICATIONS
ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITS ROOF CURB BENEFITS 2927 (115-1/4") (180) 3207 (126-1/4") (240) UNIT AND CURB APPLICATION TYPICAL APPLICATIONS 362 (14-1/4") (180)641 (25-1/4") (240) 2927 (115-1/4") (180)3207 (126-1/4") (240) * Supply and Return Air (inclu...