Page 2 - SPECIFICATIONS; Operating Ambient Temperature Range:; NEW INSTALLATION; SELECT THERMOSTAT LOCATION; Locate thermostat about 5 ft. above the floor.; ROUTE WIRES TO LOCATION; INSTALLATION; Figure 1. Routing Thermostat Wires

2 SPECIFICATIONS ELECTRICAL DATAElectrical Rating: 17 to 30vAC 50/60 Hz.0.05 to 1.5 Amps1.5 Amps Maximum Total Load (All terminals combined) Anticipation: Heating 2 to 40 (Reference Values) THERMAL DATASetpoint Temperature Range: 40 ° F to 99 ° F (4 ° C to 37 ° C) Operating Ambient Temperature Range...

Page 3 - REPLACEMENT INSTALLATION; REMOVE OLD THERMOSTAT; Move subbase out of the way. Drill mounting holes.; MV; NOTE

3 REPLACEMENT INSTALLATION REMOVE OLD THERMOSTAT 1. Shut off electricity at the main fuse box until installa-tion is complete. Verify power is off with a voltmeter. 2. Remove the front cover of the old thermostat. Withwires still attached, remove wall plate from the wall. 3. If the old thermostat ha...

Page 4 - Figure 5. Typical Wiring Diagram for Millivolt Systems; ATTACH THERMOSTAT TO SUBBASE; CAUTION; Figure 7. Attaching thermostat to subbase

4 RH MV THERMOSTAT SYSTEM W Figure 5. Typical Wiring Diagram for Millivolt Systems 6 Millivolt System 6 MV W RH Thermostat Terminal Connections From millivolt system W From millivolt system MV ATTACH THERMOSTAT TO SUBBASE POWER TO THERMOSTAT MUST BE OFF BE-FORE ATTACHING THERMOSTAT TO WALL.FAILURE T...