Summary

Page 2 - SET HEAT ANTICIPATOR; Figure 5. Anticipator adjustment; NEW THERMOSTAT OPERATION; heating/cooling system; Figure 4. Typical wiring for single transformer,; MV; RH

Set anticipator to match the setting of your old thermostat you noted in Step 3, or, the anticipator should be set to match the current rating stamped on your main heating control. The heat anticipator is adjustable from 0.15 to 1.2 amps. Adjust the anticipa-tor by rotating the contact arm (see fig....

Page 3 - TROUBLESHOOTING; Symptom

8 TROUBLESHOOTING Symptom Possible Cause Corrective Action No Heat/No Cool/No Fan 1. Blown fuse or tripped circuit breaker. Replace fuse or reset breaker. (common problems) 2. Furnace power switch to OFF. Turn switch to ON. 3. Furnace blower compartment door or Replace door panel in proper position ...