Page 3 - Important Safety Instructions; SAVE THESE INSTRUCTIONS!; • Do not install near flammable materials, fuel or chemicals.; Battery Connection Warnings; or property damage could result.; Equipment Connection Warnings; power adapters that will eliminate the plug’s ground connection.; Operation Warnings; result. Operating Mode Switch should be in the OFF position.
3T Important Safety Instructions SAVE THESE INSTRUCTIONS! This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp LiteUPS Systems. Location Warnings • Install your UPS System (whether for a mobile or stationary appl...
Page 4 - Feature Identification; Configuration DIP
4T Feature Identification Identify the premium features on your specific model and quickly locate instructions on how to maximize their use. Configuration DIP Switches: optimize UPS System operation depending on your application. See Configuration section for setting instructions. Operating Mode Swi...
Page 5 - Operation; Switch Modes
5T Operation Switch Modes After configuring, mounting and connecting your UPS System, youare able to operate it by switching between the following operatingmodes as appropriate to your situation: AUTO/REMOTE: Switch to this mode when you need constant, uninterrupted AC power for connectedlights, con...
Page 6 - Up; Configuration; Set Configuration DIP Switches
6T Select Battery Type—REQUIRED (All models) CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may bedegraded or damaged over an extended period of time. See“Battery Selection,” p. 9 for more information. Battery Type Switch Position Gel Cel...
Page 7 - Group B DIP Switches
7T Set Battery Charging Amps—OPTIONAL (function included on switch on 612 models) For traffic signal UPS applications, confirmthat the setting is on low charging to length-en the life of your batteries (especiallysmaller ones), which is advisable in trafficsignal UPS applications. By setting on high...
Page 8 - Mounting
8T Horizontal Mount (612 & 1250 models only) Using the measurements from the diagram, install two user-sup- plied ¼" (6 mm) fasteners into a rigid horizontal surface, leavingthe heads slightly raised. Slide the UPS System back over the fasteners to engage the mounting slots molded on the bot...
Page 9 - Battery Selection; Select Battery Type; Match Battery Amp-Hour Capacity to Your Application; • STEP 1: Determine Total Wattage Required
9T Battery Selection Select Battery Type Select batteries suitable for functionality within the ambient temperature ranges of your battery or traffic signal controller cabinets. Select“Deep Cycle” batteries to receive optimum performance from your UPS System. For lower initial costs in extreme clima...
Page 10 - Battery Connection; generator rather than a battery or battery bank.; must match
10T • Connect DC Wiring: Though your UPS System is a high-efficiency device, itsrated output capacityis limited by thelength and gauge ofthe cabling runningfrom the battery to the unit. Use the shortestlength and largest diameter cabling (maximum2/0 gauge) to fit your UPS System’s DCInput terminals....
Page 11 - Connection for Models with Cords and Receptacles; ISOBAR; Connection for Models with Hardwire Terminals; Connect outgoing wires to the hot (black); AC Input/Output Connection
11T To avoid overloading your UPS System, match the power requirements of the equipment you plan to run at any one time (add their total watts)with the output wattage capacity of your UPS System model (see Specifications). Do not confuse “continuous” wattage with “peak” wattageratings. If you are no...
Page 12 - Troubleshooting
12T Troubleshooting SYMPTOM PROBLEMS CORRECTIONS No AC Output (All Indicator Lights are OFF) Unit is not properly connected to utility power Connect unit to utility power. Operating Mode Switch is set to “OFF” and AC Set Operating Mode Switch to “AUTO/REMOTE”. input is present.Operating Mode Switch ...