Page 2 - UPS Location Warnings; dust or direct sunlight.; UPS Connection Warnings; UPS into itself this will damage the UPS.; Equipment Connection Warnings; external battery connector.; SAVE THESE INSTRUCTIONS; Important Safety Instructions
UPS Location Warnings • Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight. • For best performance, keep the indoor temperature between between 32º F and 104º F (0º C and 40º C). • Leave adequate space around all sides of the UPS for proper ...
Page 3 - Mounting; Installation
Rackmount 1) Loosen the wingnuts on each of the two UPSSide Supports; adjust the length of the supports tomatch the depth of your rack; tighten wingnuts. 2) Mount both UPS Side Supports in your rack onthe inside surfaces of the rack rails. Note: Both support ledges should face inward. The side suppo...
Page 4 - Connection and Start-Up; Plug your equipment into your UPS.; • Press the “ON/TEST” Switch
Connection and Start-Up Plug your UPS’s line cord into anelectrical outlet. If your model features a detachable line cord,first plug the female end into your UPS’s ACInput Receptacle. Your UPS must be connected to a dedicatedcircuit of sufficient amperage—check the“Recommended Utility Amps” rating o...
Page 5 - Optional Connections; Serial Port Connection
Optional Connections Your UPS will function properly without these connections. Serial Port Connection Using the serial cable provided, connect a serialport on your computer to the serial port of yourUPS. See Communications in the BasicOperation section of this manual to determinehow to monitor and ...
Page 6 - Front Panel Switches; This switch controls four separate UPS functions:; UPS Power ON; This switch turns power OFF at the UPS receptacles.; Front Panel Indicator Lights; Basic Operation
Front Panel Switches “ON/TEST” Switch: This switch controls four separate UPS functions: UPS Power ON To turn the UPS on, press this switch, hold it for several seconds untilyou hear a beep, then release it. The “ON LINE” LED will illuminate. UPS Self-Test During normal on-line operation, press this...
Page 7 - “LOAD ACTIVE METER” LED:
Front Panel Indicator Lights continued “BYPASS” LED: This yellow light will illuminate to indicate that the UPS’s DC/AC inverter is deactivated and the UPS is in the“Bypass” mode. During normal operation this LED will light brieflywhen the unit is plugged in, but if an internal fault or overload occ...
Page 8 - Rear Panel; External Battery Pack Connector:
Rear Panel “REPLACE BATT” LED: This red light will illuminate constantly and the UPS alarm will sound three beeps* if your UPS’smicroprocessor detects a battery fault or if your UPS fails theautomatic self-test (after you turn your UPS ON) and the UPS batteryis less than fully charged. Let the UPS s...
Page 9 - These; Communications
Rear Panel continued Output Circuit Breakers Switches (Select Models Only): These resettable circuit breakers protect your UPS from output overload. Ifone or both breakers trip, remove some of the load on the circuit(s)and allow the UPS to cool before pressing the breaker switch(es) in toreset. Inpu...
Page 10 - Troubleshooting
The UPS’s control panel lights will turn on in the sequences below to signal that the UPS ishaving operational difficulties. Lights (On/Flashing) and Condition Solution On: REPLACE BATT Let the UPS system charge for at least Condition: Replace Battery 12 hours and perform a self test using the "...
Page 12 - Battery Replacement
Under normal conditions, the original battery in your UPS will last several years. Contact Tripp Litefor information about replacement batteries. Battery replacement should be performed only by qualified service personnel. The batteries arehot-swappable: it is not necessary to turn off or disconnect...
Page 13 - ) Place the UPS horizontal with its control panel on the right side.
Battery Replacement (continued) A D C F When replacing the batteries on a SU1500RTXL2U, SU1500RTXL2UHV, SUINT1500RTXL2U,SU2200RTXL2U, SU2200RTXL2UHV, SUINT2200RTXL2U, SU3000RTXL2U, SU3000RTXL2UHV or SUINT3000RTXL2U, qualified service personnel should refer to“Battery Warnings” in the Safety section ...
Page 14 - Storage and Service; Storage; Specifications
Storage and Service First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS outlets, thendisconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid batterydrain. If you plan on storing your UPS for an extended period of time, fully recharge the UPSba...