Page 2 - Important Safety Warnings; UPS Location Warnings; UPS Connection Warnings; Equipment Connection Warnings
2 Important Safety Warnings SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline 3-Phase UPS Systems (50kVA and above) and their batteries. All UPS connection and maintenance mu...
Page 4 - Power Module Features; Buttons
4 Power Module Features There are two separate UPS system modules: a power module and a 348V DCbattery module. Familiarize yourself with the location and function of the featureson each module before installing and operating your UPS system. The powermodule is described below. The 348V DC battery mo...
Page 5 - Installation; Installation Checklist
Installation Follow all warnings listed in the Safety section prior to installation. The following checklist provides a general guide rather than a complete outlineof procedures. Installation Checklist K The floor area where the UPS will be installed has enough supporting strength. See “Floor Weight...
Page 6 - Electrical Connection
6 Electrical Connection • Connection Checklist • Recommended Cable Sizes • Terminal Wiring Diagrams • Parallel Wiring Diagrams Follow all warnings listed in the Safety section prior to hardwire terminal connection. The following checklist provides a general guide rather thana complete outline of pro...
Page 7 - Terminal Wiring Diagrams
7 Electrical Connection (continued) Terminal Wiring Diagrams The following wiring diagrams are organized according to VA. Within each VA grouping, there is a “single loop” connection option (where onlyone input source is used) and a “double loop” connection option (where two input sources are used)....
Page 8 - Single UPS Operation; • Operational Modes; Parallel Wiring Diagrams
8 Single UPS Operation The diagrams and procedures in this section apply to a single UPS Power Module connected to a single equipment load. Note: all diagrams assumethe presence of two separate AC sources supplying two separate inputs: a mains source supplying rectifier input and a reserve source su...
Page 10 - Shutdown Procedure
10 Single UPS Operation (continued) After following all warnings listed in the Safety section and precautions listed above, start-up UPS according to the following procedure: Step 1. Turn on (close) the “RESERVE INPUT” Breaker. The LCD Screen will display “Bypass Mode”. Step 2. Turn on (close) the “...
Page 16 - LCD Display Navigation
16 LCD Display Navigation The LCD Screen displays a wide variety of operational conditions as well asprovides managers with the ability to set operational parameters and view eventlogs. The LCD Screen will display a block diagram of the current operating mode.The Normal Mode is provided as an exampl...
Page 17 - “Parameter Setting” Sub-Menu
17 LCD Display Navigation (continued) “Parameter Setting” Sub-Menu This sub-menu allows you to set UPS operational parameters. A password is required to access this sub-menu. Note: The default password is 0 0 0 0.To change the password, select the “Password Setting” screen in this sub-menu. Also Not...
Page 18 - “System Control” Sub-Menu
18 LCD Display Navigation (continued) “System Control” Sub-Menu This sub-menu allows you to directly control UPS operation. A password is required to access this sub-menu. Note: The default password is 0 0 0 0.To change the password, select the “Password Setting” screen in the “Parameter Setting” su...
Page 19 - “Other Information” Sub-Menu
19 LCD Display Navigation (continued) “Other Information” Sub-Menu This sub-menu allows managers to view a variety of additional UPSSystem information. UPS Status Code Note: a UPS Status Code is displayed in the upper-right corner of the screen in the following display. Use the chart below to determ...
Page 20 - Communications
20 Communications Dry-Contacts Remote Emergency Power Off (EPO) This feature is only for those applications that require connection to a facility's Emergency Power Off (EPO) circuit. When the power module isconnected to this circuit, it enables emergency shutdown of the output.
Page 21 - Ethernet Power; GENERATOR CONTACT
21 Communications (continued) RS-232 Port/Ethernet Port/SNMP Card Slot The RS-232 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite power management software. TheRS-232 port uses RS-232 communications to report UPS status and power conditions. Contact Tri...
Page 22 - UPS Parallel Communication Ports; TERMINAL RESISTOR FOR RS-485; UPS Parallel Communication Port
22 Communications (continued) RS-485 Ports These ports connect multiple UPS power modules in a parallel connection. UPS Parallel Communication Ports These ports allow multiple UPS power modules to communicate while in a parallel configuration. TX485+ TX485- RX485+ RX485- RS-485 Port RS-485 Port TERM...