Page 2 - Introduction; High Efficiency Output
2 Introduction Congratulations! You’ve purchased the most advanced, feature-rich integrated inverterand battery charger on the market. Your APS provides your equipment with utility-supplied ACpower when it is available, and during blackouts, overvoltages and brownouts, your APS automatically switche...
Page 3 - -Stage Battery Charger; Voltage Regulation; continued
3-Stage Battery Charger Your APS recharges your battery faster than conventional chargers because its three-stagecharger profile (Bulk, Absorption and Float) areoptimized, regardless of the type of battery you use(Wet or Gel).* In addition, the advanced chargingsystem protects against over-charge an...
Page 4 - Important Safety Instructions; SAVE THESE INSTRUCTIONS; batteries if they are not kept well ventilated.; Equipment Connection Warnings; There are no user-serviceable parts inside.
4 Important Safety Instructions SAVE THESE INSTRUCTIONS This manual contains important instructions and warnings that should be followed duringthe installation, operation and storage of all Tripp Lite APS Systems. APS Location Warnings • Install your APS indoors, away from excess moisture or heat, d...
Page 5 - Configuration; BATTERY TYPE / VOLTAGE POINT; Configuration Dip Switch Settings; Up
5 Configuration DIP SWITCH GROUP A (All models) BATTERY TYPE / VOLTAGE POINT Using a small tool, set the 4 “Battery Type / Voltage Point” Configuration DIP Switches, GroupA (located on the front panel of your APS; see Diagram 1, p. 36) to select battery type and setthe voltage range outside of which...
Page 6 - DIP SWITCH GROUP B; LOAD SHARING/EQUALIZE BATTERY CHARGE; • Load Sharing; Battery Charger Limiting Points; Charger limiting takes effect the; LEAST LIMITING; Charger limiting begins at
6 DIP SWITCH GROUP B (Available on Select Models) LOAD SHARING/EQUALIZE BATTERY CHARGE Using a small tool, set the “Load Sharing” Configuration DIP Switches, #1 and #2 of Group B(located on the front panel of your APS; see Diagram 1, p. 36). DIP Switch #3, Group B shouldbe kept in the “UP” position ...
Page 7 - • Equalize Battery Charge; Battery Charge; Equalize Down; • Limit Battery Charger; Battery Charger; Full Charging Power
7 • Equalize Battery Charge (DIP Switch #3, Group B) This DIP Switch is momentarily engaged to begin the process of equalizing the internal resistanceof your battery’s cells. This can extend the useful life of certain types of batteries; consult withyour battery's manufacturer to determine if your b...
Page 8 - Selecting Battery Type
8 Mounting (Optional) (See Diagram 2, p. 36) Battery Selection Select a battery or system of batteries that will provide your APS with proper DC voltage and anadequate amp hour capacity.* Select ‘Deep-Cycle’ batteries to enjoy optimum performance fromyour APS. Batteries of either Wet-Cell (vented) o...
Page 9 - Battery Connection; Connect your APS’s positive DC Terminal directly to a fuse.; Standard
9 Battery Connection 1. Connect your APS’s positive DC Terminal directly to a fuse. Tripp Lite recommends that you install a recognized component fuse block and fuse within18 inches of the battery. The fuse's rating must equal or exceed the Minimum DC FuseRating listed in your APS model’s specificat...
Page 10 - HARDWIRE PROCEDURE; AC Connection; Before AC connection, match the power requirements of your
10 APS systems must be connected to a grounded, permanent wiring system. For most installations,the negative battery conductor must be bonded to the grounding system at one (and only one)point in the system. All installations must comply with national and local codes and ordinances. When figuring th...
Page 11 - APS after it has shut down due to overload or overheating.; AC Output Electrical Connection; Switches, Indicator Lights & Other Features; Set Operating Mode Switch
11 AC Connection continued Simply plug your equipment into the unit’s AC receptacles. If adapters must be used, chooseadapters that provide a connection to ground. • Switch to “AUTO/REMOTE” when you are using connected equipment. ADVANTAGE: Uninterruptible power supply. Provides battery backup power...
Page 14 - Maintenance
14 Limited Warranty Maintenance & Service Your APS model requires no maintenance but should be kept dry at all times. Periodically checkall cable connections both at the unit and at the battery. Clean and tighten connections as necessary. If returning your APS to Tripp Lite, please pack the APS ...
Page 15 - Troubleshooting
15 Try these remedies for common APS problems before calling for help. Call Tripp Lite Customer Service at (773)869-1234 before returning your APS for service. SYMPTOM PROBLEMS CORRECTIONS APS does not provide APS not properly connected to Connect APS to utility power. AC output (AC input present) u...
Page 16 - Specifications
16 Specifications (Corded Models) CORDED MODELS: APSINT1012 Weight: 11.9 Kg INVERTER Continuous power (@ 20° C): 1000 W Surge power (5 seconds): 2000 W Efficiency (Full Load): 88% Minimum DC Fuse Rating: 170A DC Input Current @ Nominal V DC Full Load 95A No Load 2.6A* Nominal Input Volts: 12 VDC DC ...
Page 21 - Corded Model • Modelo con Cable
39 1. Operating Mode Switch (All models) 2. DIP Switch Group A (All models) 3. DIP Switch Group B (Select models only) 4. “LINE” (All models) 5. “INV” (Inverting—all models) 6. “LOAD” (All models) 8. “BATTERY HI/MED/LO” (All models) 9. DC Input Terminals (All models) 10. AC Receptacles (Corded model...
Page 22 - Hardwired Model • Modelo con Toma Directa al Circuito
40 OUTPUT/NEUTRA OUTPUT/HOT GROUND INPUT/NEUTRA INPUT/HOT “FOR USE WITH COPPER WIRE ONLY” Diagrams/Esquemas 9b 1. Operating Mode Switch (All models) 2. DIP Switch Group A (All models) 3. DIP Switch Group B (Select models only) 4. “LINE” (All models) 5. “INV” (Inverting—all models) 6. “LOAD” (All mod...