Page 2 - Adding or Replacing Internal Batteries; Important Safety Warnings
2 SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline 3-Phase 20kVA and 30kVA UPS Systems. UPS Location Warnings • Install your UPS in a controlled environment.• Install your U...
Page 3 - This button turns the UPS System's inverter ON.; This button turns the UPS System's inverter OFF.; “EMERGENCY POWER OFF” Button:; These cool and ventilate the inside of the UPS.
2. Control Panels 3 Note: Familiarize yourself with the location and function of the features on your UPS system before installing and operating it. “ON” Button: 1. This button turns the UPS System's inverter ON. “OFF” Button: 2. This button turns the UPS System's inverter OFF. Note: If the UPS Syst...
Page 4 - Internal Battery Packs:; Battery System Connectors:; Accepts battery cartridge fuses.
4 1 2 3 4 5 6 7 Individual models may vary slightly from diagram. 2.2 Battery Access Panel (Cover Removed) 2. Control Panels (continued) Internal Battery Packs: 1. These supply backup runtime to connected equipment. Each pack consists of two strings (one positive and one negative). The number of inc...
Page 5 - Manual Bypass Switch:
Individual models may vary slightly from diagram. 5 Manual Bypass Switch: 1. This dial is used to put the UPS in “BYPASS” mode, which must be done before performing any maintenance on the UPS with the connected load supported. (See section 5, Operation (Special Conditions) , for step-by-step instruc...
Page 6 - RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY; Mounting bracket installation is required.; If the mounting brackets are not installed, the; Important Safety Warnings; WIRING SELECTION; Mounting Bracket Installation
6 Move your UPS over short distances using its wheels. Note: The wheels are not designed to provide long-term support for the UPS system after final installation. Mounting bracket installation is required. DANGER! RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY The UPS System's wheels are not des...
Page 7 - WIRING CONNECTION; Installation; Turning the UPS On
7 WIRING CONNECTION Connect your wiring to the input and output terminal blocks located on the rear panel of your UPS (see figure below). CAUTION! Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source. Ensure that cable...
Page 8 - Was Too High, Now Nominal; LCD Display Select Button
8 Momentarily press the “SELECT” button on the front panel to browse through different power readings on the LCD Display. BYPASS OUTPUTR: XXXV R: XXX.XVS: XXXV S: XXX.XVT: XXXV T: XXX.XV (Bypass & Output Voltage) OUTPUT LOAD R: XXX% XXX.XA S: XXX% XXX.XA T: XXX% XXX.XA (Output Load & Current...
Page 9 - “Output” and “Bypass” LEDs will be illuminated.; SWITCHING UPS TO “BYPASS” MODE; Inverter On Warnings
9 Condition LCD Display Message Overload Shutdown ON BYPASSOVERLOAD 150%SHUTDOWN...VERSION: XXXXXXX UPS Output Short Circuit ON BYPASSSHORT CIRCUIT!SHUTDOWN...VERSION: XXXXXXX Overtemperature ON BYPASSHIGH TEMP!SHUTDOWN...VERSION: XXXXXXX DC BUS Overvoltage ON BYPASSDC BUS O.V.P.!SHUTDOWN...VERSION:...
Page 10 - Dry Contact Interface
3 V + - 10 This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses RS-232 communications to report UPS status and power conditions. Using this port, Tripp Lite software can monitor and manage network power and automatical...
Page 11 - Use assistants as needed.; CHECK BATTERY PACK VOLTAGE BEFORE COMPLETING INSTALLATION; Operation of Manual Bypass Switch; Adding or Replacing Internal Batteries
X 123456 X 11 This optional feature is only for those applications which require connection to a facility's Emergency Power Off (EPO) circuit. When the UPS System is connected to this circuit, it enables emergency shutdown of the output. Using a user-supplied cable, connect the UPS System's EPO port...
Page 12 - Internal Battery Pack Wiring Diagram
UPS System Battery Back Connector White wire Blue wire UPS System Battery Back Connector Fuse Block Bracket Red wire (+)Black wire (–) 12 Qualified service personnel should familiarize themselves with the battery pack wiring diagram prior to adding or replacing batteries. The battery module can acce...
Page 13 - RED
13 Place the UPS System in Bypass Mode or completely turn it off, depending on preference. (See section 5.4, Operation of Manual Bypass Switch , or 4.2, Turning the UPS Off .) 1 Remove battery access panel, located on the FRONT of the UPS system. 2 2 Disconnect the RED and BLACK cables attached to e...
Page 14 - Slide the battery string with the; cable into an empty slot within; BLACK; Remove the fuse block bracket.
14 Slide the battery string with the RED cable into an empty slot within the battery compartment as shown. Make sure that the string is oriented as shown in the diagram 7A . Note: If the auxiliary battery connector is in the way, remove its mounting screw and position the cable to allow adequate roo...
Page 16 - OBSERVE PROPER POLARITY!
16 Your SmartOnline 3-Phase UPS System is covered by the limited warranty described below. Extended warranty (2-, 3- and 4-year) and start-up service programs are available. For more information, call Tripp Lite Customer Service at (773) 869-1234. 3-Phase UPS System Limited Warranty Seller warrants ...
Page 18 - Input
200901 138 93-2624 18 Model: SU30K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz Voltage Correction Range 88-144/166-250V AC Input Current (Per Phase, On-Line) 90A Inrush Current <300A Power Factor (Full Load) >0.95 Efficiency (Full Load/On-Line...