Page 2 - Warnings and Cautions
© 2005 American Standard Inc. UNT-SVX07A-EN About This ManualLiterature Change History Use this manual for UniTrane fan-coilsand Force Flo cabinet heaters. This is theseventh revision of this manual. Itprovides specific installation, operation,and maintenance instructions for “ZO”and later design se...
Page 3 - contents; Installation .....................................................................2
UNT-SVX07A-EN 3 contents Cross reference to related publications/information for UniTrane™ fan-coil & ForceFlo™ equipment:• Rover™ Installation, Operation and Programming Guide, EMTX-SVX01D-EN• Tracer™ ZN510 Unit Controller, CNT-IOP-1• Tracer™ ZN520 Unit Controller, CNT-SVX04A-EN• UniTrane™ Fan-...
Page 4 - General; Smaller unit footprint
4 UNT-SVX07A-EN Figure I-GI-1. UniTrane fan-coil unit components. Vertical cabinet model is shown. General UniTrane fan-coil and Force Flo units areintended for single zone applications.These units have load capabilities of 200to 1200 cfm. See Figure I-GI-1 for unitcomponents. Fan-coil units are ava...
Page 5 - Installation; Digit 4 — development sequence “B”; extended end pocket; Digits 10, 11 — design sequence; Model Number Description
UNT-SVX07A-EN 5 Installation generalinformation FC B B 020 1 C P0 A 0 G 1 0 A A 2 M 000 0 0 1 0 0 0 A A 000 000 0 0 0 0 A 0 0 1 5 10 15 20 25 30 35 40 4 4 Digits 1, 2 — unit typeFC = fan-coilFF = force flo Digit 3 — cabinet typeA = vertical concealedB = vertical cabinetC = horizontal concealedD = ho...
Page 6 - Digits 37, 38 — future cntrl functions; ”standard vertical recessed panel
6 UNT-SVX07A-EN J = 2-way, modulating, 0.7 Cv (50 psig)*K = 3-way, modulating, 0.7 Cv (50 psig)* L = 2-way, modulating, 1.1 Cv (60 psig)*M = 3-way, modulating, 1.1 Cv (60 psig)*N = 2-way, modulating, 2.3 Cv (60 psig)*P = 3-way, modulating, 2.7 Cv (60 psig)*Q = 2-way, modulating, 3.3 Cv (60 psig)*R =...
Page 8 - Available Models
8 UNT-SVX07A-EN Installation generalinformation Available Models model A vertical concealed model B vertical cabinet model C horizontal concealed model D horizontal cabinet model E horizontal recessed model F wall hung cabinet model L low vertical concealed model K low vertical cabinet model J slope...
Page 9 - Factory-Installed Piping Packages
UNT-SVX07A-EN 9 Installation generalinformation Factory-Installed Piping Packages Note: This figure shows piping package components and basic arrangement. It is notan accurate pictorial of what factory-installed piping packages look like.
Page 10 - Vertical Concealed, Model A
10 UNT-SVX07A-EN Installation dimensions& weights Vertical Concealed Unit Dimensions & weights, in-lbs. UnitSize 02-03 04 06 08 10-12 A 2’-8 11 / 16 ” 3’-1 11 / 16 ” 3’-11 3 / 16 ” 4’-7 11 / 16 ” 6’-2 11 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 1’-10...
Page 11 - Vertical Cabinet, Model B
UNT-SVX07A-EN 11 Installation dimensions& weights Vertical Cabinet Unit Dimensions, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-9 5 / 16 ” 3’-2 5 / 16 ” 3’-11 3 / 16 ” 4’-8 5 / 16 ” 6’-3 5 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 3 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 7 5 / 8 ” 7 1 / 8 ” 8 7 /...
Page 12 - Horizontal Concealed, Model C
12 UNT-SVX07A-EN Installation dimensions& weights Horizontal Concealed Unit Dimensions, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-8 11 / 16 ” 3’-1 11 / 16 ” 3’-11 3 / 16 ” 4’-7 11 / 16 ” 6’-2 11 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 1’-10 13 / 16 ” ...
Page 13 - Horizontal Cabinet, Model D
UNT-SVX07A-EN 13 Installation dimensions& weights Horizontal Cabinet Unit Dimensions, in-lbs. unitsize 02-03 04 06 08 10-12 A 2’-9 5 / 16 ” 3’-2 5 / 16 ” 3’-11 3 / 16 ” 4’-8 5 / 16 ” 6’-3 5 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 7 5 / 8 ” 7 1 / 8 ” 8 7...
Page 14 - Horizontal Recessed, Model E
14 UNT-SVX07A-EN Installation dimensions& weights Horizontal Recessed Unit Dimensions, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-11 13 / 16 ” 3’-4 13 / 16 ” 4’-2 5 / 16 ” 4’-10 13 / 16 ” 6’-5 13 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 1’-10 13 / 16 ” ...
Page 15 - Vertical Wall Hung Cabinet, Model F
UNT-SVX07A-EN 15 Installation dimensions& weights Vertical wall hung cabinet unit dimensions & weights, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-9 5 / 16 ” 3’-2 5 / 16 ” 3’-11 13 / 16 ” 4’-8 5 / 16 ” 6’-3 5 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C...
Page 16 - Vertical Recessed, Model H
16 UNT-SVX07A-EN Installation dimensions& weights Vertical Recessed Unit Dimensions, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-8 11 / 16 ” 3’-1 11 / 16 ” 3’-11 3 / 16 ” 4’-7 11 / 16 ” 6’-2 11 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / 16 ” C 1’-10 13 / 16 ” 2’-...
Page 17 - Vertical Slope Top, Model J
UNT-SVX07A-EN 17 Installation dimensions& weights Vertical Slope Top, Model J Vertical Slope Top Unit Dimensions, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-9 5 / 16 ” 3’-2 5 / 16 ” 3’-11 13 / 16 ” 4’-8 5 / 16 ” 6’-3 5 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” 3’-8 5 / 16 ” 5’-3 5 / ...
Page 18 - Low Vertical Concealed, Model K
18 UNT-SVX07A-EN Installation dimensions& weights Low Vertical Concealed Unit Dimensions, in-lbs. unit size 03 04 06 A 3’-5 7 / 16 ” 4’-2 15 / 16 ” 4’-11 7 / 16 ” B 2’-2 1 / 4 ” 2’-11 3 / 4 ” 3’-8 1 / 4 ” C 2’-3 15 / 16 ” 3’-0 13 / 16 ” 3’-9 15 / 16 ” D 1’-10 5 / 16 ” 2’-7 13 / 16 ” 3’-4 5 / 16 ...
Page 19 - Low Vertical Cabinet, Model L
UNT-SVX07A-EN 19 Installation dimensions& weights Low Vertical Cabinet Unit Dimensions, in-lbs. unit size 03 04 06 A 3’-10 15 / 16 ” 4’-8 7 / 16 ” 5’-4 15 / 16 ” B 2’-2 1 / 4 ” 2’-11 3 / 4 ” 3’-8 1 / 4 ” C 11 7 / 16 ” 1’-1 5 / 16 ” 11 7 / 16 ” D 2’-0” 2’-6” 3’-6” E 2’-0 1 / 4 ” 2’-9 3 / 4 ” 3’-6...
Page 20 - Inverted Vertical Cabinet, Model M
20 UNT-SVX07A-EN Installation dimensions& weights Inverted Vertical Cabinet, Model M Inverted vertical cabinet unit dimensions & weights, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-9 5 / 16 ” 3’-2 5 / 16 ” 3’-11 13 / 16 ” 4’-8 5 / 16 ” 6’-3 5 / 16 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / ...
Page 21 - Inverted Vertical Recessed, Model N
UNT-SVX07A-EN 21 Installation dimensions& weights Inverted Vertical Recessed, Model N Inverted vertical recessed unit dimensions & weights, in-lbs. unit size 02-03 04 06 08 10-12 A 2’-3 7 / 8 ” 2’-8 7 / 8 ” 3’-6 3 / 8 ” 4’-2 7 / 8 ” 5’-9 7 / 8 ” B 1’-9 5 / 16 ” 2’-2 5 / 16 ” 2’-11 13 / 16 ” ...
Page 26 - Wall Box
26 UNT-SVX07A-EN Installation dimensions& weights Wall Box Dimensions Unit Size Dimensions Internal Ref. Only A x B Supports 02 - 03 24 3 / 8 x 4 3 / 4 1 04 24 3 / 8 x 7 1 / 2 1 06 33 1 / 8 x 7 1 / 2 2 08 37 1 / 2 x 7 1 / 2 3 10 -12 58 1 / 4 x 7 1 / 2 4 CLEARANCEFOR DRAINAGE CONTINUOUSMORTAR RIB...
Page 27 - Projection Panel
UNT-SVX07A-EN 27 Installation dimensions& weights Projection Panel, All Unit Sizes C 2” 2 1 / 2 ” 3” 3 1 / 2 ” 4” 4 1 / 2 ” 5” 5 1 / 2 ” 6” D 1 1 / 8 “ 1 5 / 8 “ 2 1 / 8 “ 2 5 / 8 “ 3 1 / 8 “ 3 5 / 8 “ 4 1 / 8 “ 4 5 / 8 “ 5 1 / 8 “ E 8 5 / 8 “ 8 1 / 8 “ 7 5 / 8 “ 7 1 / 8 “ 6 5 / 8 “ 6 1 / 8 “ 5 ...
Page 28 - WARNING; Receiving and Handling; Cover the entire unit with a canvas; Installation Preparation
28 UNT-SVX07A-EN Installation pre-installationconsiderations WARNING Hazardous Voltage w/Capacitors! Disconnect all electric power, includingremote disconnects and discharge allmotor start/run capacitors beforeservicing. Follow proper lockout/tagout procedures to ensure thepower cannot be inadverten...
Page 29 - Service Access; Verify the unit size and tagging with the
UNT-SVX07A-EN 29 pre-installationconsiderations Installation Service Access Service access is available from the fronton vertical units and from the bottom onhorizontal units. Cabinet and recessedunits have removable front or bottompanels to allow access into the unit. SeeFigure I-PC-1 for recommend...
Page 30 - Duct Connections; Piping Considerations
30 UNT-SVX07A-EN mechanicalrequirements Installation Duct Connections Install all air ducts according to NationalFire Protection Association standards forthe Installation of Air Conditioning andVentilating Systems (NFPA 90A and 90B).Install all air ducts according to theNational Fire Protection Asso...
Page 32 - connections
32 UNT-SVX07A-EN mechanicalrequirements Installation External Insulating RequirementsInsulate and vapor seal surfaces colderthan surrounding air dew-point a toprevent unplanned condensation. Tranerecommends field-insulation of thefollowing areas to prevent potentialcondensate problems:1. Supply and ...
Page 33 - If the piping package has modulating
UNT-SVX07A-EN 33 mechanicalrequirements Installation Balancing The Manual Circuit SetterValveThe manual circuit setter valve is anoptional end valve supplied on the returnpipe of the factory piping package. Thevalve allows the operator to regulatewater flow through the hydronic coil,balance the wate...
Page 35 - Steam Piping
UNT-SVX07A-EN 35 mechanicalrequirements Installation Steam Piping CAUTIONCoil Damage! In all steam coil installations, thecondensate return connections mustbe at the low point of the coil toensure condensate flows freely fromthe coil at all times. Failure to do somay cause physical coil damage fromw...
Page 36 - Unit Wiring Diagrams
36 UNT-SVX07A-EN electricalrequirements Installation Unit Wiring Diagrams Specific unit wiring diagrams areprovided inside each unit and can beeasily removed for reference.Use thesediagrams for connections or troubleanalysis. Wiring diagrams are attachedon the inside of the front panel of verticalca...
Page 41 - Installing the Unit; Vertical Units
UNT-SVX07A-EN 41 installationprocedure Installation Installing the Unit Follow the procedures below to install theunit properly. Reference the “Dimensionsand Weights” section for specific unitdimensions and mounting hole locations. Vertical Units CAUTIONElectrical Wiring! Do not allow electrical wir...
Page 42 - The trim ring assembly cannot; CAUTION
42 UNT-SVX07A-EN installationprocedure Installation Note: The trim ring assembly cannot accomodate unlevel ceilings. Figure I-IP-1. Installing the trim ring assembly on horizontal recessed units. Note: On sizes 8, 10, & 12 center installa- tion position and use 2 or 3.5-inch bolts,whichever is b...
Page 43 - Wall-Mounted Control Options
UNT-SVX07A-EN 43 Installation Figure I-IP-4. Zone sensor withsetpoint knob, on/cancel, & commjack. Figure I-IP-3. Zone sensor with on/canceland comm jack. Figure I-IP-2. Zone sensor with off/auto/high/low fan speeds, setpointknob, on/cancel, and comm jack. Figure I-IP-5. Zone sensor only, instal...
Page 45 - Installation Checklist
UNT-SVX07A-EN 45 installationprocedure Installation Checklist The following checklist is only anabbreviated guide to the detailedinstallation procedures given in thismanual. Use this list to ensure allnecessary procedures are complete. Formore detailed information, refer to theappropriate sections i...
Page 46 - Device Addressing
46 UNT-SVX07A-EN pre-startuprequirements Installation Device Addressing LonTalk devices are given a uniqueaddress by the manufacturer. Thisaddress is called a Neuron ID. Each TracerZN510 and ZN520 controller can beidentified by its unique Neuron ID, whichis printed on a label on the controller’slogi...
Page 47 - Pre-Startup Checklist
UNT-SVX07A-EN 47 Pre-Startup Checklist Complete this checklist after installingthe unit to verify all recommendedinstallation procedures are completebefore unit startup. This does not replacethe detailed instructions in theappropriate sections of this manual.Disconnect electrical power beforeperform...
Page 48 - Refer to the Trane publication,; startup; than 55°F and less than 85°F.
48 UNT-SVX07A-EN Tracer™ ZN510 & ZN520 Unit Startup Refer to the Trane publication, CNT-IOP-1 Installation, Operation and ProgrammingGuide for Tracer ZN510 and CNT-SVX04A-EN for Tracer ZN520. Thefactory pre-programs the Tracer ZN510and ZN520 with default values to controlthe temperature and unit...
Page 49 - Operation; General Information
UNT-SVX07A-EN 49 Operation generalinformation Figure O-GI-3. Tracer ZN010 board Figure O-GI-2. Fan speed switch General Information Relay BoardThe relay board is a new component onall models (except those with a unit-mounted, line-voltage fan speed switch)that replaces all the loose wires in thecont...
Page 50 - Fan Mode Switch Operation; Tracer ZN520 Operation
50 UNT-SVX07A-EN Fan Mode Switch Operation OffFan is turned off, two-position damperoption spring-returns closed. Hi, Med, LoFan runs continuously at the selectedspeed. The two-position damper optionopens to an adjustable mechanical stopposition. Tracer ZN010 & ZN510Operation OffFan is off; cont...
Page 51 - input values to detemine initial values.; Binary Inputs; Binary Outputs
UNT-SVX07A-EN 51 Operation sequence ofoperation Sequence of OperationTracer ZN010 and ZN510 Note: this section applies only to unitswith a Tracer ZN010 or ZN510 controller. Power-Up SequenceWhen 24 VAC power is initially applied tothe Tracer ZN010 or ZN510, the followingsequence occurs:1. All output...
Page 53 - • By pressing the zone sensor’s timed
UNT-SVX07A-EN 53 Operation sequence ofoperation Tracer ZN520 Sequence ofOperation The Tracer ZN520 operates the fan in thefollowing modes:1) occupied2) unoccupied3) occupied standby4) occupied bypass5) Tracer Summit with supply fan control OccupiedWhen the controller is in the occupiedmode, the unit...
Page 54 - Cooling Operation; ZN520 controller attempts to; Heating Operation; During heating mode, the Tracer
54 UNT-SVX07A-EN Operation sequence ofoperation Cooling Operation The heating and cooling setpoint highand low limits are always applied to theoccupied and occupied standbysetpoints. During the cooling mode, theTracer ZN520 controller attempts to maintain the space temperature at theactive cooling s...
Page 55 - Fan Mode Operation; ZN520 controller offers additional; ZN520 does not support fan
UNT-SVX07A-EN 55 Operation sequence ofoperation Fan Mode Operation For multiple fan speed applications, theTracer ZN520 controller offers additional fan configuration flexibility. Separatedefault fan speeds for heating and coolingmodes can be configured. The fan runscontinuously for requested speeds...
Page 57 - building
UNT-SVX07A-EN 57 Operation sequence ofoperation Note: If the unit is in the unoccupiedmode, the dehumidification routine willnot operate. Data SharingBecause this controller utilizesLonWorks™ technology, the controllercan send or receive data (setpoint, heat/cool mode, fan request, spacetemperature,...
Page 60 - Diagnostics
60 UNT-SVX07A-EN Maintenance diagnostics Table M-D-1 . Tracer ZN520 Diagnostics Diagnostic Fan Other Outputs (Note 1) Condensate overflow Off Valves Closed, Fresh air damper Closed, electric heat Off,Baseboard heat Off Low temperature detection Off Valves Open, Fresh air damper Closed, electric heat...
Page 64 - Position 2 indicates Tracer ZN520.
64 UNT-SVX07A-EN Figure M-T-1. Resistance temperature curve for the zone sensor, entering water temperaturesensor, and discharge air sensor. Thermisitor = 10k Ω Ω Ω Ω Ω at 77°F. Maintenance troubleshooting Troubleshooting the RelayBoard The relay board serves as a commoninterface to all of the stand...
Page 65 - Red SERVICE LED; second
UNT-SVX07A-EN 65 Maintenance troubleshooting Troubleshooting Tracer ZN010, ZN510 & ZN520 Figure M-T-1. The Tracer ZN010 board Red SERVICE LED Green STATUS LED Yellow COMM LED Red SERVICE LEDDuring normal operation, the LED is offcontinuously when poweris applied to the controller. If the LED is ...
Page 67 - Maintenance; Maintenance Procedures; Remove the overflow drain line to the; Main Drain Pan
UNT-SVX07A-EN 67 Maintenance maintenanceprocedures Maintenance Procedures Perform the following maintenanceprocedures to ensure proper unitoperation. WARNING Live Electrical Components! During installation, testing, servicing,and troubleshooting this equipment, itmay be necessary to work with liveel...
Page 71 - CSTI Fan Speed Switch
UNT-SVX07A-EN 71 typical wiringdiagram Maintenance CSTI Fan Speed Switch
Page 72 - CSTI Non Fan Speed Switch
72 UNT-SVX07A-EN typical wiringdiagram Maintenance CSTI Non Fan Speed Switch
Page 73 - Line voltage fan speed switch
UNT-SVX07A-EN 73 typical wiringdiagram Maintenance Line voltage fan speed switch
Page 74 - Tracer ZN010 with electric heat
74 UNT-SVX07A-EN typical wiringdiagram Maintenance Tracer ZN010 with electric heat
Page 75 - Tracer ZN510 with main and auxilliary valves
UNT-SVX07A-EN 75 typical wiringdiagram Maintenance Tracer ZN510 with main and auxilliary valves
Page 76 - ZN520 with 2-stage electric heat
76 UNT-SVX07A-EN typical wiringdiagram Maintenance ZN520 with 2-stage electric heat
Page 80 - US
a business of American Standard Inc.www.trane.com For more information contactyour local office or e-mail us [email protected] Literature Order Number File Number Supersedes Stocking Location Trane has a policy of continuous product improvement and reserves the right to change design and specifica...