TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page iii Issue 10 SAFETY WARNING In the interests of health and safety, when using or servicing this equipment the following instructions must be noted and adhered to: Only skilled or instructed personnel with relevant tech...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page vi Issue 10 TABLE OF CONTENTS 1 INTRODUCTION ................................................................................................. 1 1.1 PURPOSE ................................................................
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page ix Issue 10 6.3.1 General ........................................................................................................ 169 6.3.2 Configuring the Integral OTU PCB ...............................................
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page x Issue 10 FIGURE 29 - PHASES IN STAGES FOR EXAMPLE 6 .............................................. 127 FIGURE 30 - OUTSTATION PCB STATUS LEDS ..................................................... 133 FIGURE 31 - OUTS...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 1 Issue 10 1 INTRODUCTION 1.1 PURPOSE This document is a guide for professional Installation and Maintenance personnel. It describes how to install, commission and maintain the TC12 Instation and Outstation. 1.2 SCOPE ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 2 Issue 10 1.5 ISSUE STATE AND AMENDMENTS Issue 1 - First formal issue Issue 2 - Significant changes this issue are listed below: Table 3 and Table 6 Modem PCB and OTU PCB Receive threshold switch settings for –39 dBm ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 6 Issue 10 Instation The Instation comprises of one or more Traffic control computers (TCC) and one or more Instation Transmission Units (ITUs). The ITU cabinets are 32U high with grey panelling and a smoked glass fron...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 7 Issue 10 Digital Output Rack The Digital output rack contains one Instation rack Power Supply Card and between one and sixteen Digital Output boards, each capable of driving 64 LEDs at up to 30 V 25 mA. There are two...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 9 Issue 10 Figure 2 - System Connection for two ITU Racks
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 10 Issue 10 2 TC12 INSTATION 2.1 SPECIFICATION 2.1.1 Mains voltage ranges The Instation will work over: 98 – 132 V RMS 198 – 264 V RMS Note . The voltage range of the PC used in the Instation should be checked in the m...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 11 Issue 10 2.1.5 Size and Weight Figure 3 - TC12 Cabinet - External Dimensions FRONT SIDE 585 1625 1540 875 All dimensions in mm Weight: Cabinet 111 Kg ITU Rack 8.4 Kg Digital Output Rack 8.3 Kg Note : The weight of t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 12 Issue 10 2.2 INSTALLATION Safety Notes on TC12 Instation Only authorised/trained personnel are allowed to have access behind the doors/panels of the TC12 Instation Cabinet. Users/operators must not attempt to access...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 19 Issue 10 The software installation procedure is as follows: SAFETY NOTE The PC should be plugged directly into the mains, and not via the mains distribution panel on the Instation, since the Instation has not underg...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 21 Issue 10 (10) If the indications for the DIGI I/O and IMD cards are as expected, move across to the 'Install' menu, select the 'Yes' option and hit return. The TC12 Software will now be installed on the Hard disk of...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 22 Issue 10 2.2.3 Systems Fault Indication Panel (SIP) The SIP (part number 667/1/22667/000) is 6U high and is screwed to the Instation racking in front of the PC. If the Audible alarm on the system fault indication pa...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 23 Issue 10 2.2.4.1 PSU PCB (inc. Digi I/O, SIP (local and remote), Watchdog and TC8 cables) See Figure 7 for a diagram of the board layout showing the position of connectors, LEDs, switches, volume control. SAFETY NOT...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 25 Issue 10 Figure 7 - PSU Board Layout 1 (TOP) 14 PL5 1 (TOP) 14 PL6 1 (TOP) 14 PL7 1 (TOP) 14 PL8 MAINSSOCKET 1 50 PL4 1 50 PL3 50 PL2 1 1 20 PL1 1 26 PL9 1 10 PL10 GND +12V +5V +5V GND AGND -12V TP4 TP5 TP6 TP7 TP8 ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 26 Issue 10 Figure 8 - PSU Board Switch Settings
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 27 Issue 10 Setting the Voltage Range of the PSU The Power supply fitted to every PSU board used in the system (part number 667/7/22631/000, manufactured by Daren Electronics PLC type PP40-30). An internal link in this...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 28 Issue 10 1. SW1 - Mode Select switch Ensure that the Mode Select switch is set correctly; see Table 1 for settings. One of the modes shown is selected on a 7-way DIL switch. Note NO other settings are to be used in ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 29 Issue 10 Connector PL1 The 24-way cable connects the top header (PL1) on the Modem PCB to four 25-way 'D' connectors on the IMD distribution panel, as follows: Modem PCB 1 -> 'D' connectors 1-4 on the distributio...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 30 Issue 10 Figure 10 - Modem PCB Layout 1 (TOP) 24 PL124 Way toIMD panel 1 (TOP) 14 PL214 Way toPSU card S1 PL337 Way ‘D’to MDF orTransformerPCB. 1 (TOP) 37 S2 S3 S4 S5 S6 S7 ModeSelect 0 1 LineLevel LineLevel 2/4 Wir...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 31 Issue 10 Table 1 - Modem PCB Mode Select Switch (SW1) SWITCH NUMBER MODE 1 2 3 4 5 6 7 (Eng use only) !MC0 !MC1 !MC2 !MC3 !MC4 CCITT V.23 M2 1200 BPS HALF DUPLEX 0 1 0 0 1 1 0 CCITT V.23 M2 1200 BPS HALF DUPLEX WITH...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 32 Issue 10 Table 2 - Modem PCB Line Level Switches (SW2, 3, 6 and 7) SWITCH NUMBER OUTPUT POWER 1 2 3 4 5 6 7 8 0dBm 1 0 0 0 - - 1 1 -3dBm 1 0 0 1 - - 1 1 -6dBm 0 1 0 0 - - 1 1 -9dBm 0 1 0 1 - - 1 1 -10dBm 0 0 1 0 - -...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 34 Issue 10 2.2.4.3 Transformer PCB and Modem/Transformer Cable Figure 10 shows the layout of the Transformer PCB. Ensure that the correct variant has been supplied e.g. 666/1/02245/000 for the UK. 666/1/02245/000 or 6...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 35 Issue 10 Figure 11 - Transformer PCB Layout 1 (TOP) 37 1 (TOP) 14 PL214 Way toModem PCB S1 PL137 Way ‘D’to MDF. 1 (TOP) 37 S2 S3 S4 PL3 37 Way ‘D’to MDF. Variant Figure 12 - ITU 19" Rack (Rear View) PSU ITU Rack...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 36 Issue 10 2.2.5 Digital Output Rack, PCBs and PSUs The digital output rack is the same size as the ITU rack except that 17 card guides are fitted. These take one PSU PCB and between 1 and 16 Digital Output PCBs. The ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 37 Issue 10 Switch S1 PCB Address Set the switch on the card closest to the PSU PCB to 0, the next card to 1 and so on up to F if 16 boards are fitted. Connectors PL1 and PL2 These connectors are used to take the digit...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 39 Issue 10 Connector PL4 Connect cable 667/1/22744/000, a 14 way cable with 17 sockets, to PL5 of the PSU PCB and to PL4 of all the Digital Output PCBs in the rack. Connector PL5 Connect cable 667/1/22717/000 to PL5. ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 44 Issue 10 2.3 COMMISSIONING 2.3.1 Safety Tests on the TC12 Instation 2.3.1.1 Test Equipment Required Multimeter (e.g. Fluke 77 or similar). Comark Insulation Meter 1905 (or similar capable of 1000 V). Clare R133R10 E...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 45 Issue 10 Cabinet Side Cover stud left hand side Cabinet Side Cover stud right hand side Cabinet Top Cover Cabinet rear door Metal Part of front door along hinged side SIP Panel IMD Panel Master Switch Panel at the r...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 46 Issue 10 2.3.1.8 RCD Tests Turn the Instation master Switch OFF. Connect the Instation to the mains. Switch the Instation master Switch ON. Plug the RCD Tester into a mains socket at the front of the Instation. Set ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 47 Issue 10 2.4 MAINTENANCE 2.4.1 Status LEDs LEDs are provided on the front edge of the Modem Board and PSU Board to provide basic status information. The position of these LEDs and their functions are shown in Figure...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 48 Issue 10 Figure 16 - Modem and PSU PCB Status LEDs LP1 (RED LED) - +12v LP2 (RED LED) - -12v LP3 (RED LED) - +5v LP4 (YELLOW LED) - MODEM 1 TRANSMIT (TX1) LP5 (GREEN LED) - MODEM 1 RECEIVE (RX1) LP6 (YELLOW LED) - M...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 49 Issue 10 This controls what signals can cause the low frequency audio alarm to sound. If it is incorrectly set, the alarm may sound for reasons other than those expected or may not sound when expected. (3) S3 - Audi...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 50 Issue 10 b) 2 wire system but with 4 wire selected in error: No reply message will be received. Only the yellow LED for the modem will come on. (4) SW5 - Transformer Select Switch a) On board transformers required b...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 51 Issue 10 2.4.6.2 PC Failure Symptom Possible Reason PC not Powered PC Switched off. Power cable disconnected/faulty. Mains plug fuse blown Master switch panel off/fuse blown. PC faulty. SIP PC 1 LED ON Digi I/O card...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 54 Issue 10 2.4.8.4 Active tasks, RX/TX packets and time events, Key to Press 'A' This screen, as its name suggests, shows the processes going on within the Instation against time, each dot represents 400ths of a secon...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 58 Issue 10 2.4.8.12 Link Statistics, Key to Press 'L' This screen gives details of the Ethernet link to the host UTC TCC. The addresses of the Instation on the Ethernet ADDRESS and MULTICAST ADDRESS The type of driver...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 59 Issue 10 2.4.8.15 Received Characters IMD, Key to Press 'R' This screen displays the data received from OTUs on IMD 0 port 0. It displays each OTUs reply on a separate line on the screen OTU 0 at top. This screen on...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 60 Issue 10 Figure 17 - Master Switch Panel Fuses MASTER SW CABINET RCD FS1 5A FRONT 13A SKT FS2 5A REAR 13A SKT FS3 5A MAINS SKT B FS4 5A MAINS SKT C FS5 5A MAINS SKT D FS6 5A MAINS SKT E FS7 10A WALL MAP PSU Master S...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 62 Issue 10 3 TC12 OUTSTATION 3.1 SPECIFICATION 3.1.1 Mains voltage ranges The Outstation will work over: 85 – 264 V RMS Note the power supply used is auto-ranging over the above voltage range. 3.1.2 Mains frequency ra...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 64 Issue 10 Figure 18 - OUTSTATION PCB LAYOUT 1 (T OP ) 1 (T OP ) P L2 40 Way for 32 buffered input s 34 P L4 34 Way for 16 Relay out put s & T ransmit Confirm out put 40 Serial Number LP 7 +5V LED Line Jack Socket...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 67 Issue 10 BATTERY ON BATTERY OFF ON OFF BAT S2 Information on the silk screen Figure 20 - OTU Lithium Battery On / Off Switch (S2) 1 4 - WIRE 2 - WIRE 2WS4 A 4W Information on Silk Screen OPERATION OPERATION Figure 2...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 68 Issue 10 Table 5 - OTU Line Level Switch (S3) OUTPUT POWER SWITCH NUMBERS 1 2 3 4 5 6 0 dB 1 0 0 0 -3 dB 1 0 0 1 SEE BELOW -6 dB 0 1 0 0 -9 dB 0 1 0 1 -10 dB 0 0 1 0 -13 dB 0 0 0 0 -16 dB 0 0 0 1 Å Æ RECEIVE THRESHO...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 69 Issue 10 The GRX handset command (see section 3.3.3.8) must be used together with the above jumper positions in order to activate the desired communications interface. 3.2.3 Connectors and Cables 3.2.3.1 PSU Cable -...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 72 Issue 10 3.2.3.5 Input/Output Cable Connect the Input/Output Cable (part number 667/1/22693/000) to 40-way connector PL2 and 34-way connector PL4. Note. When pushing the connectors into PL2 and PL4 the OTU PCB must ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 76 Issue 10 Figure 27 - Freestanding Outstation Inputs
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 78 Issue 10 3.2.4 Lamp Monitor Unit Connections NOTE. RED LAMP MONITORING is not approved by the Department of Transport and should not be used. If the installation uses the lamp monitoring facility then Current and vo...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 79 Issue 10 Table 6 - Outstation Processor PCB - PL1 50-way connector to LMU inputs. PIN NAME PIN NAME 1 LMU Input 1+ 27 LMU Input 14+ 2 LMU Input 1- 28 LMU Input 14- 3 LMU Input 2+ 29 LMU Input 15+ 4 LMU Input 2- 30 L...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 82 Issue 10 Voltage Monitoring Transformer A Voltage monitoring transformer (part number 667/7/25172/000) is used per Outstation when equipped with LMU facilities. The red and black wires connect to the lamp supply mai...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 83 Issue 10 Leaving phase delays. Use of phases that are not fixed in the stage. b) Using voltage sense transformers to produce a suitable logic signal direct from the lamp drive voltage. Note: If voltage sensors are u...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 84 Issue 10 Number of Current Sensors Number of phases (include vehicle, green arrow and pedestrian phases +___ Number of pedestrian phases with wait indicators +___ Number of switched sign drives +___ Number of separa...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 86 Issue 10 3.3 COMMISSIONING 3.3.1 Safety Tests on the TC12 Outstation 3.3.1.1 Test Equipment Multimeter (e.g. Fluke 77 or similar). Comark Insulation Meter 1905 (or similar capable of 1000 V). Clare R133R10 Earth Con...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 87 Issue 10 PCB Mounting plate PCB Frame Rack Cross members Rack Side plate Case of power supply Power supply 0 V (pin 4 on OTU PSU 14-way connector, see Figure 18). All earthed points on any other equipment that may h...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 88 Issue 10 terminal connected to the Controller are in the correct position and are the correct value. Checking OTU Input wiring: Attach a handset to the controller and enter controller handset commands to set the sta...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 92 Issue 10 45 = Any lamp failure 46 = Any Red failure Note: These bits are also set if the lamps are switched off at the controller. If dual controller monitoring is configured switching either controller lamps off wi...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 93 Issue 10 3) There will be a separate bit allocated for each loop monitored by HIOCC. There is a maximum of eight loops in total. Eight new reply bit functions have been allocated, as above. 3.3.3.14 OTU output bit s...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 96 Issue 10 3.3.3.24 DFM time limit (GMG) GMG {input byte select: 0-11} {input bit select: 0-7} = {group select: 0-7,255} Comment: Used to select the DFM time limits set up by GMA and GMI for the input specified. The d...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 104 Issue 10 For sensors monitoring a phase or wait indicator, the value entered defines the phase identity, i.e. 0=phase A, 1=phase B, 2=phase C etc. For sensors monitoring a vehicle and a pedestrian phase together, t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 111 Issue 10 Comment: Displays the lamp supply in volts. If no second lamp supply is defined KEV will display ‘KEV 1:N/A’. 3.3.3.60 Display LMU Aspect Learn Status (KAS) KAS (sensor number: 1-23) (aspect pattern number...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 113 Issue 10 7 Upload / Download framing errors 8 Upload / Download block CRC errors 9 Upload / Download good blocks 10 Upload / Download good messages Test / Maintenance Commands 3.3.3.67 Flow Counters (GCU) GCU (Unit...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 115 Issue 10 3.3.3.73 Override Digital Outputs Timeout (GOT) GOT=(1-254 minutes, 255 disable timecount) Comment: Displays the current timeout value, normally one minute. With a special PLD (667/1/12399/106 - VMS + LMU)...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 117 Issue 10 3.3.3.87 Remote Handset Mode GRH = { 0 or 1 } ( 0 ) Comment: Customises the Remote Handset facility. Not normally changed from its default of zero. The value of '1' disables the delay used by the OTU to he...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 119 Issue 10 3.3.4 Examples of Lamp Monitor Unit Configuration Using the Handset NOTE. RED LAMP MONITORING on the Freestanding OTU is not approved by the Department of Transport and should not be used. The LMU is confi...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 127 Issue 10 Figure 29 - Phases in Stages for Example 6 PHASE STAGE 1 STAGE 2 STAGE 3 STAGE 4 A (Traffic) B (Traffic) C (Traffic) D (Traffic) E (Traffic) F (Traffic) G (G/Arrow) H (PED) UTC REPLY G1 G2 G3 G4 Phases A t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 130 Issue 10 3.3.5 TCSU TC12 OTU Commissioning Procedure Reset OTU and select TCSU default configuration data. Enter the following commands: GME=249 (Access code) LRN=53 } CNN=117 } (Reset Codes) TKE=191 } Remove Mains...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 132 Issue 10 3.4 MAINTENANCE 3.4.1 Status LEDs LEDs are provided on the front edge of the board to provide basic status information. The position of these LEDs and their functions are shown in Figure 30. The +5 V LED s...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 133 Issue 10 Figure 30 - Outstation PCB Status LEDs LP 7 (GREEN LED) - +5v LP 2 (RED LED) - SYST EM FAIL LP 3 (RED LED) - W AT CHDOG FAIL LP 4 (GREEN LED) - T RANSMIT CONFIRM LP 5 (GREEN LED) - CARRIER DET ECT / RX DAT...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 136 Issue 10 retaining screws line up with large holes in the slots for the screws. The power supply can be taken off by moving it sideways. Power Supply Tests If the power supply is suspected as being faulty, check th...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 138 Issue 10 4 TC12 INSTATION TEST SET 4.1 SPECIFICATION 4.1.1 Mains voltage and frequency ranges The Instation test set will work over: 98 – 132 V RMS @ 47-63 Hz 198 – 264 V RMS @ 47-63 Hz Note. The voltage range of t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 147 Issue 10 4.5 USING THE TEST SET FOR FAULT FINDING ON TC12 SYSTEM 4.5.1 General By connecting the test set into the TC12 system both at the Instation and Outstation and using the three modes available, it should be ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 148 Issue 10 "RECALL" and enter relevant filename or choose from directory of "DATA" directory, and recall it (Press enter whilst on filename field). ELSE Go to "SYSTEM SET UP" and select "O...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 154 Issue 10 4.6 USING THE TEST SET AS A MONITOR FOR THE INSTATION PC Exit from any software currently being used on the test set PC. At the C: prompt, type TERM <CR>. This will activate the batch file TERM.BAT (...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 155 Issue 10 4.7 USING THE TEST SET AS HANDSET Exit from any software currently being used on the test set PC. At the C: prompt, type TERM <CR>. This will activate the batch file LITEMNS.BAT (which should be in t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 156 Issue 10 4.8 MAINTENANCE OF INSTATION TEST SET 4.8.1 Recommended Spares Switching the Test Set off, using the rocker switch on the front panel, does NOT guarantee isolation from the mains. The mains plug must only ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 157 Issue 10 5 TC12 OUTSTATION TEST SET 5.1 SPECIFICATION 5.1.1 Mains voltage and frequency ranges The Outstation test set will work over: 100/120/220/230/240 VAC all +10%,-13% Different internal connections are necess...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 158 Issue 10 5.2 USING THE OUTSTATION TEST SET The Outstation Test Set (part number 667/1/22657/000) is supplied with six cable forms (part number 667/1/22658/000 to /005). The Outstation Test Set is designed to simula...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 159 Issue 10 A CONNECTION FAULT indicator is lit if the test cable is incorrectly connected. The mains lead is connected directly to the OTS. Figure 32 - Outstation Test Set Front Panel FU SE O FF ON M odem M ode M ode...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 160 Issue 10 Figure 33 - Outstation Test Set Connections OTU OTU Input/Output Cable667/1/22693/000 OUTSTATION TEST SET OTU Test Set Cable667/1/22658/000 OR 667/1/22658/001 40 Way Plug 34 Way Plug CONTROLLER 40 Way Plug...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 165 Issue 10 Set the Mode switch to the CONTROLLER position. (If the connection fault is lit return the switch to OFF and check that the plugs are fully inserted before proceeding). Set up the required patterns for wor...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 167 Issue 10 6 INTEGRAL OUTSTATION TRANSMISSION UNIT (OTU/LMU) 6.1 GENERAL OVERVIEW This section describes the Integral OTU/LMU. This is an additional PCB that can be used in the TC12 System. It can be fitted in T400 o...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 168 Issue 10 6.2 SPECIFICATION 6.2.1 Mains voltage and frequency ranges The Integral OTU PCB is powered from the Controller power supply unit. The working voltage and frequency ranges are equal to those specified for t...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 170 Issue 10 The cover must ALWAYS be fitted before any cables are installed, and should NEVER be removed whilst the telephone cable (from socket SK1 on the PCB) is connected to the telephone network. Figure 34 - Integ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 171 Issue 10 2. S2 - Lithium Battery On/Off Switch Set the Lithium Battery Switch (S2) to ON (see Figure 34). 3. S3 - Line Level Switch Ensure that the Line Level switch (S3) is set to the required line levels. These a...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 172 Issue 10 Table 8 - Integral OTU Line Level Switch (S3) ← Switch Number → Output Power SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 0 dBm 1 0 0 0 -3 dBm 1 0 0 1 -6 dBm 0 1 0 0 -9 dBm 0 1 0 1 -10 dBm 0 0 1 0 -13 dBm 0 0 0 0 -16 dBm...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 174 Issue 10 network termination unit). In order to prevent the cable being disconnected from the PCB by accident the PCB cover fits around the end of the plug on the cable in order to retain it. 6.3.3.3 Connection of ...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 175 Issue 10 Figure 35 - LMU Input Connector 60 Way Connector to LMU Inputs PLB PIN SIG NAME BERG PIN PLB PIN SIG NAME BERG PIN 1 LMU input 1 + 3 * 25 LMU input 13 + 27 2 LMU input 1 - 4 26 LMU input 13 - 28 3 LMU inpu...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 176 Issue 10 Current Transformers Each controller phase or illuminated indicator that is to be monitored requires one current sensor as detailed below. The table also indicates which lamp feeds are passed through the c...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 178 Issue 10 Voltage Monitoring Transformer A Voltage monitoring transformer (part number 667/7/25172/000) is used per Outstation when equipped with LMU facilities. The red and black wires connect to the lamp supply ma...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 179 Issue 10 6.4 COMMISSIONING 6.4.1 Commissioning Procedure after Power Up 1. Initialisation The operator can initialise just the Integral OTU, just the Controller, or both together by using the appropriate handset co...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 180 Issue 10 Check that the status LEDs illuminate correctly, see section 6.5.1. 6.4.2 Configuration Using the Handset With the Controller and OTU powered up, connect a handset terminal to the Controller Main Processor...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 181 Issue 10 Section 3.3.3 Subsection No Command Section 3.3.3 Subsection No. Command 42 KRD 92 GMC 43 KRE 93 GBE 44 KRG 94 GMO 46 KLV 47 GCD 48 GDI 3 The PC in the TC12 Instation Test Set can be used as a handset term...
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 191 Issue 10 6.5 MAINTENANCE 6.5.1 Status LEDs LEDs are provided on the front edge of the board to provide basic status information. The position of these LEDs and their functions are shown in Figure 34. A System fail ...
Siemens Manuals
-
Siemens HF35M630/01
User Manual
-
Siemens HF35M630/01
Installation Manual
-
Siemens 1015N-2MFM-1A
Manual
-
Siemens 108
User Manual
-
Siemens 11
User Manual
-
Siemens 1168
User Manual
-
Siemens 120 Series
User Manual
-
Siemens 125-1957
User Manual
-
Siemens 125-3584T
User Manual
-
Siemens 125-5033
User Manual
-
Siemens 140
User Manual
-
Siemens 175V
User Manual
- Siemens 1800C User Manual
-
Siemens 18inc Freezer Tower with Dispenser
User Manual
-
Siemens 18inc Wine Tower
User Manual
-
Siemens 1G03QB 630G
User Manual
-
Siemens 2 D SP
User Manual
-
Siemens 2000
User Manual
- Siemens 2005C User Manual
-
Siemens 2010 Tango
User Manual