Page 2 - Introduction; NSTALLATION; Read the Safety Guide before installing the UPS.; Unpacking; XLTW; models; Specifications; to 95% relative humidity
2 Introduction The APC ® by Schneider Electric Smart-UPS ® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic ...
Page 3 - Wiring and Connecting the UPS; VA
3 Wiring and Connecting the UPS 5000 VA XLI MODELS O NLY : H ARDWIRING I NSTRUCTIONS • Wiring must be performed by a qualified electrician. • Install a high magnetic 30/32 A utility circuit breaker. • Adhere to all national and local electrical codes. • Use #10 AWG gauge (5 mm 2 ) wire. 1. Switch th...
Page 5 - serial com; See the APC Web site,
5 B ASIC C ONNECTORS serial com The serial connector is to be used for interfacing with APC PowerChute software and terminal emulation software. Use only cables approved by APC. Any other interface cable will be incompatible with the UPS connector. normal bypass Manual bypass enables the user to man...
Page 6 - UPS; Avoid using extension cords.; Do not
6 C ONNECTING E QUIPMENT AND P OWER TO THE UPS 1. Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models). 2. Avoid using extension cords. • 3000 VA XLJ/XLT/XLI/XLTW and 5000 VA XLJ/XLT/XLTW models : Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle...
Page 7 - PERATION; RT; Indicator Description; Troubleshooting; Feature Function
7 O PERATION Load S MART -UPS RT F RONT D ISPLAY Battery Charge Indicator Description Online The Online LED illuminates when the UPS is drawing utility power and performing double conversion to supply power to connected equipment. On Battery The UPS is supplying battery power to the connected equipm...
Page 8 - Battery Charge
8 Feature Function Cold Start When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment. The UPS will emit two beeps. During the second beep, release the button. Self-Test Automatic: The UPS performs a self-test automatically when turned...
Page 9 - Manufacture date
9 U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW ER C HUTE SOFTW ARE , OPTIONAL S MART S LOT ACCESSORY CARDS , OR T ERMINAL M ODE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Automatic Self-Test On start-up and every 14 days, thereafter On start-...
Page 11 - EPO; CL2: Class 2 cable for general use
11 C ONNECTING THE EPO (E MERGENCY P OWER O FF ) O PTION The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to National and local electrical codes when wiring the EPO. The EPO switch is internally powered by the UPS for use with non-powered switch circu...
Page 12 - Server
12 T ERMINAL M ODE TO C ONFIGURE UPS P ARAMETERS 3000 VA models: Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing to use PowerChute ® software or an optional Network Management Card. Connect the serial cable to the serial com connector on the back o...
Page 14 - Start
14 • Press 2 and ENTER to change the Battery Settings. • Type in the number of external battery packs (four battery modules per pack), and press ENTER. (Number of packs: 1 = 1 SURT192XLBP, 2 = 2 SURT192XLBP etc.) • Press 3 and ENTER to accept the changes. • Press ESC multiple times (5) to return to ...
Page 15 - Replacing the Battery Module; for information on
15 M AINTENANCE AND T RANSPORT Replacing the Battery Module This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your dealer or contact APC at the W...
Page 16 - Disconnecting the Battery for Transport; Shut down and disconnect any equipment attached to the UPS.
16 R EPLACING B ATTERY MODULES X Y Z [ \ ] ^ _ Disconnecting the Battery for Transport Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS. 1. Shut down and disconnect any equipment a...
Page 17 - for assistance with complex UPS problems.; Replace Battery
17 T ROUBLESHOOTING , S ERVICE , AND W ARRANTY I NFORMATION Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON Battery not connected prop...
Page 18 - normal
18 P ROBLEM AND P OSSIBLE C AUSE S OLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of operation, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS,...
Page 19 - Service; Limited Warranty
19 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com . • N...
Page 20 - APC Worldwide Customer Support; Global support searching APC Knowledge Base and using e-support.
20 R ADIO F REQUENCY W ARNINGS This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial...