Page 3 - Safety Information; Important Information; DANGER; WARNING; result in death or serious injury.; CAUTION; result in minor or moderate injury.; NOTICE; alert symbol shall not be used with this signal word.
Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential...
Page 4 - Notices; FCC Part 15 Notice; receiver is connected.; FCC Part 68 Notice
Notices FCC Part 15 Notice This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment gene...
Page 5 - There are no user serviceable parts in this equipment.; Network Compatibility Notice for the Internal Modem
telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC if you believe it is necessary. The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of this equipme...
Page 7 - Table of Contents
930-112-01-D.00 PowerLogic TM EM4000/EM4800 Series 11/2013 Table of Contents ©2013 Schneider Electric All Rights Reserved i Table of Contents PowerLogic configuration tool ..................................................................... 1 System Set-up and Description .............................
Page 9 - PowerLogic configuration tool; System Set-up and Description; meters; Configuration and Programming
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 1 PowerLogic configuration tool This document describes how to configure the PowerLogic EM4000/EM4800 Series meters, using the PowerLogic configuration tool. It includes the following configuratio...
Page 10 - Figure 1: Programming Switch location; Table 1: Programming access to meter parameters
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 2 ©2013 Schneider Electric All Rights Reserved Figure 1: Programming Switch location Table 1 lists the programming capabilities associated with each parameter in combination with the programming switches. After the meter has been programmed,...
Page 11 - Display Navigation; and right
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 3 Display Navigation The display on the front of the meter provides status information for each circuit, and general information for metering. The PowerLogic meter has three buttons for navigating...
Page 12 - Normal Mode; Diagnostics Mode
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 4 ©2013 Schneider Electric All Rights Reserved Normal Mode In Normal mode, the Display button scrolls through the information for each meter. The left and right arrow buttons select the previous or next meter points respectively. The fol...
Page 13 - Communications Connections; If you are configuring the meter at an installation site, see the; Direct Connection Ethernet Requirements; To connect a PC directly to the PowerLogic meter:
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 5 • Ethernet port MAC address• Firmware revision• Potential transformer ratio Communications Connections If you are configuring the meter at an installation site, see the PowerLogic EM4000 Series ...
Page 14 - Network Connection Ethernet Requirements; To connect the PowerLogic meter to the network:
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 6 ©2013 Schneider Electric All Rights Reserved 7. Assign the PC a static IP address such that the first three segments are the same as the default IP address, and the last segment is different from the default IP address. For example, 169.25...
Page 15 - Configuring the Meters; Login; Use the following procedure to log in to the meter.; User Name; The main window displays as shown in Figure 3.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 7 4. Re-install the inner cover.5. Using a CAT 5 Ethernet patch cable, connect the meter and the PC to a local Ethernet switch. 6. Re-install the outer cover. 7. Restore power. When control power ...
Page 16 - Figure 3: Configuration tool main window; Connecting to a Meter
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 8 ©2013 Schneider Electric All Rights Reserved Figure 3: Configuration tool main window Connecting to a Meter The configuration tool automatically detects and lists the PowerLogic meters on the same network segment as the PC. The configurati...
Page 18 - Enter the IP address of the meter to be configured, then click; Figure 6: Main configuration window with configured parameters; Unit Field Configuration Tab
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 10 ©2013 Schneider Electric All Rights Reserved 2. Enter the IP address of the meter to be configured, then click Connect. The configuration tool main window appears populated with the current programming information for the selected meter. ...
Page 19 - Table 2: Unit Field Configuration tab parameters
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 11 Table 2: Unit Field Configuration tab parameters Field Parameter Description Unit Field Configuration Current IP Address The current IP address for the unit .This parameter is read only and can...
Page 20 - Report Parameters; The; Report; section in the main configuration window has six tabs:; tab allows the user to configure how often the meter is to send; Figure 7: Intervals tab in the Report section
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 12 ©2013 Schneider Electric All Rights Reserved Report Parameters The Report section in the main configuration window has six tabs: • Intervals tab allows the user to configure the recording interval at which meter data is collected, and the...
Page 21 - Example; : Selecting a Recording Interval of 5 minutes with Sliding Window; Figure 8: Types tab in the Report section
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 13 Example : Selecting a Recording Interval of 5 minutes with Sliding Window Demand enabled and 3 Sub-intervals, creates a demand calculation every 5 minutes based on the previous 15 minutes. This...
Page 22 - Table 4: Types tab configuration parameters
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 14 ©2013 Schneider Electric All Rights Reserved Table 4: Types tab configuration parameters NOTE: If parameters are grayed out, they are not available on the variant or firmware revision of the meter being configured. Parameter Description W...
Page 23 - Figure 9: Reporting Schedule tab in the Report section; Table 5: Reporting Schedule tab configuration parameters
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 15 Figure 9: Reporting Schedule tab in the Report section Table 5: Reporting Schedule tab configuration parameters NOTE: When selecting a Daily report schedule, the Start Time must occur before th...
Page 24 - Figure 10: Calculations & Format tab in the Report section; Table 6: Calculations & Format tab configuration parameters
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 16 ©2013 Schneider Electric All Rights Reserved Figure 10: Calculations & Format tab in the Report section Table 6: Calculations & Format tab configuration parameters Parameter Description Power Factor Sign Format IEEE In the display...
Page 25 - Figure 11: BACnet tab in the Report section; Table 7: BACnet tab configuration parameters
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 17 Figure 11: BACnet tab in the Report section Table 7: BACnet tab configuration parameters Parameter Description Device ID Set the BACnet device ID by entering a a numeric ID between 0 and 419430...
Page 26 - Figure 12: Comms tab in the Report section
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 18 ©2013 Schneider Electric All Rights Reserved Figure 12: Comms tab in the Report section
Page 27 - Table 8: Comms tab configuration parameters; Manufacturing Tab; Manufacturing; tab allows the user to define the metering configuration for the
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 19 Table 8: Comms tab configuration parameters NOTE: The Modbus and RTU Adapter Comms Option parameters are valid only when a Modem module or an RTU adapter module is present. The RTU Adapter para...
Page 28 - Table 9: List of supported PowerLogic metering configurations; Figure 13: Manufacturing tab
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 20 ©2013 Schneider Electric All Rights Reserved Table 9: List of supported PowerLogic metering configurations To view the manufacturing information for a specific meter, select a model number from the Model # pull-down list shown in Figure 1...
Page 31 - Figure 15: Badge Numbering pane; button - selecting this button resets all registers for all; Send PC Time; button - selecting this button configures the meter with the
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 23 Figure 15: Badge Numbering pane Reset Buttons • Reset Dial Readings button - selecting this button resets all registers for all energy types and pulse counts to zero. This function takes effect...
Page 32 - Delivered Watt Hours; Pulse Probes Tab; NOTE: The Pulse Probe settings are not active unless
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 24 ©2013 Schneider Electric All Rights Reserved • Adjust Dial Reading button - selecting this button allows the operator to set all of the following energy type registers to the same fixed initial value: • Delivered Watt Hours • Received Wat...
Page 33 - Figure 16: Pulse Probes tab
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 25 Figure 16: Pulse Probes tab
Page 34 - Completing the Meter Configuration; To complete the meter configuration:; Unit; in the menu bar, then select; Save
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 26 ©2013 Schneider Electric All Rights Reserved Completing the Meter Configuration Once you have defined all of the configurable parameters, the PowerLogic meter is ready to be programmed. To complete the meter configuration: 1. Click Unit i...
Page 35 - Send; from the drop-down menu; File loaded successfully!; should appear in; Figure 18: Sending the configured settings to the meter
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 27 2. Click Unit in the menu bar, then select Send from the drop-down menu to transmit the configuration settings from your PC to the selected PowerLogic meter. The confirmation message File loade...
Page 37 - User notes
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 29 User notes