Page 2 - Schneider Electric IT Corporation Legal Disclaimer
Schneider Electric IT Corporation Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific developmen...
Page 3 - Contents
Contents EcoBreeze System Installation i General Information ................................................................... 1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Inspecting the Equipment . . . . . . . . . . . . . ...
Page 5 - General Information; Safety; DANGER; WARNING; CAUTION
1 EcoBreeze System Installation General Information Safety Read and adhere to the following important safety considerations when working with this cooling unit. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Turn off all power supplying this equipment before working on the equipment. All e...
Page 6 - Inspecting the Equipment; Storing the equipment before installation
EcoBreeze System Installation 2 Inspecting the Equipment Inspect for missing components. All shipped loose components are identified by part number and description on the bill of lading. Ensure each item is present before accepting delivery of the unit. Filing a claim. If damage has occurred, or if ...
Page 7 - Model Identification; Model identification label location
3 EcoBreeze System Installation Model Identification Model identification label location Frames Modules Other components SKU Description ACECFR20101SEn* 6 m (20 ft) ISO Frame 400/3/50ACECFR20200SEn* 6 m (20 ft) ISO Frame 480/3/60ACECFR20201SEn* 6 m (20 ft) ISO Frame 600/3/60ACECFR40101SEn* 12 m (40 ...
Page 8 - Access Door and Panel Operation
EcoBreeze System Installation 4 Access Door and Panel Operation Module access doors and panels have latches with a locking mechanism. Secondary door latches are provided on doors on compartments that have positive air pressure to prevent the doors from opening quickly if a door is opened while the u...
Page 9 - Component Identification; Item
5 EcoBreeze System Installation Component Identification * Version shown is the 12 m (40 ft) model. Item Description Quantity 20 ft Quantity 40 ft EcoBreeze Frame and Module assembly* 1 1 Remote display interface 1 1 Frame electrical panel latch tool 4 4 Module access door latch tool 4 8 W...
Page 10 - EcoBreeze Frame and Modules; Item Description
EcoBreeze System Installation 6 EcoBreeze Frame and Modules Item Description ISO corner fittings Return air inlets Module anchor brackets Module Tension rods and mounts Screw-jack mounting points Water drain outlet Water supply inlets Frame main power enclosure Frame power distri...
Page 11 - Module — front
7 EcoBreeze System Installation Module — front Remote display interface na3665a SUPPLY BLOWER ACCESS COIL ACCESS COIL ACCESS Item Description Condenser coil Sprayer head and mist eliminator access door Water coupling and water strainer access door Air filter and DX evaporator coil access doo...
Page 12 - Site Preparation; Incoming power supply requirements; Ductwork; Supply water requirements.; connection” on page 18.; Foundation; NOTICE
EcoBreeze System Installation 8 Site Preparation Incoming power supply requirements N OTE : This equipment requires three-phase electrical service. Electrical service must conform to national and local electrical codes. The equipment must be grounded. N OTE : To facilitate routing of main power supp...
Page 13 - Environment; more frequent service intervals.; Piping/plumbing diagram
9 EcoBreeze System Installation Environment N OTE : Locating the EcoBreeze system near areas of increased airborne debris may result in more frequent service intervals. Piping/plumbing diagram Item Description Item Description Clear T-strainer Check valves Two-way motorized valve* Pump line ...
Page 14 - Refrigeration
EcoBreeze System Installation 10 Refrigeration Each EcoBreeze Module contains its own closed refrigeration circuit. No field connections are required. Item Description Shut-off Water pressure reducing valve (if necessary) Backflow preventer Water hammer arrestor Alternate water supply (if ...
Page 15 - Service access
11 EcoBreeze System Installation Service access Install a service platform (not supplied) to facilitate maintenance activities. Regular maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to remove, maneuver, and install Modules and components. N OTE : Consider local ...
Page 16 - Weights and Dimensions; Frame; Weight
EcoBreeze System Installation 12 Weights and Dimensions Frame Frame (fully populated with Modules) Weight (dry) ACECFR20101SE4, ACECFR20200SE4, ACECFR20201SE4 7 863 kg (17,300 lb) ACECFR40101SE8, ACECFR40200SE8, ACECFR40201SE8 14 290 kg (31,440 lb) Frame (with Modules and water) Weight (wet) ACECFR2...
Page 17 - Installation; Lifting and Rigging
13 EcoBreeze System Installation Installation Lifting and Rigging EcoBreeze Frame. The EcoBreeze Frame is not equipped with forklift pockets. Lift and rig only from the four upper ISO corner blocks on each EcoBreeze Frame using a crane. Recommended horizontal sling angles are greater than 45 degrees...
Page 18 - Mechanical Connections; Position the EcoBreeze; EcoBreeze Frame Install Kit instructions.
EcoBreeze System Installation 14 Mechanical Connections Install the EcoBreeze Frame per the EcoBreeze Frame Install Kit instructions. Position the EcoBreeze N OTE : The power and plumbing connections for the EcoBreeze Frame are located on the end where the unpacking sheet is placed on the protective...
Page 19 - Unwrap the equipment
15 EcoBreeze System Installation Unwrap the equipment NOTICE DAMAGE TO EQUIPMENT • Do not remove the plastic wrap until the EcoBreeze Frame is placed on its permanent supports and you are prepared to install the return air ductwork. If the plastic is removed, ensure that the return air plenums on to...
Page 20 - Remove the tension rods; Remove the tension rods and brackets.
EcoBreeze System Installation 16 Remove the tension rods Tension rods are installed diagonally across each Module bay to provide support during shipping. 1. Release tension on the rods by loosening the nuts on the ends of the tension rods. 2. Using an M12 wrench, remove the eight bolts securing the ...
Page 21 - Lower Module drop-down box
17 EcoBreeze System Installation Lower Module drop-down box 1. Open the lower-right door on each Module. 2. For shipping, the drop-down box is secured upside down inside the Module. Remove the screws securing the drop-down box (a). NOTE: The screws will be re-used to install the drop-down box. 3. Tu...
Page 22 - Open the damper on the supply air transition.; Water supply connection; possible to provide a redundant water supply.
EcoBreeze System Installation 18 6. Locate the insulation strips packed in the ship-loose kit.7. Remove the backing from the insulation and apply the insulation around the air transition ducts. 8. Open the damper on the supply air transition. Water supply connection N OTE : There are two water suppl...
Page 23 - Drain
19 EcoBreeze System Installation Connect the water supply to the two 3/4-inch water supply fittings on the EcoBreeze Frame. If necessary, make the connections using the appropriate fittings from the pipe adapter kit. See “Component Identification” on page 5. Drain Connect the external 2-in. drain li...
Page 24 - towards the wastewater drain.
EcoBreeze System Installation 20 N OTE : Separate the drain line from the EcoBreeze Frame and the external drain line by a 50 mm (2 in.) air gap in order to prevent back up of contaminated water into the cooling system. N OTE : Pitch the external drain piping at a minimum of 25 mm (1 in.) per 3048 m...
Page 25 - Electrical Connections; The electrical connections required are the following:; and local electrical codes.
21 EcoBreeze System Installation Electrical Connections The electrical connections required are the following: • Power to Frame• Control (remote display interface) • Communication - Building Management System (BMS) - optional Make all electrical connections in accordance with applicable industry gui...
Page 26 - Power supply to EcoBreeze Frame; the main power enclosure.; A service loop is factory-installed in the main power enclosure.
EcoBreeze System Installation 22 Power supply to EcoBreeze Frame 1. Use a punch tool to create an access hole as needed for power supply wires entering the main power enclosure. 2. Attach the conduit connector to the access hole on the main power enclosure. N OTE : A service loop is factory-installe...
Page 27 - Remote display interface; The remote display interface enclosure contains the; For outdoor applications, use weather-proof conduit connectors.; Connect shield wire to GND.
23 EcoBreeze System Installation Remote display interface See EcoBreeze remote display installation instructions for additional information. The remote display interface enclosure contains the LCD display that is used to control the EcoBreeze from a remote location. The EcoBreeze connects to the rem...
Page 28 - remote display interface enclosure.
EcoBreeze System Installation 24 3. Wire the expansion bus to the 124, 125, and 126 contacts on the terminal block in the remote display interface enclosure. G4 K4N4 124125126 188 189 190 192 193 194 195 196 197 198 na3576a AC POWER (85-265 VAC, 50/60 Hz) ANALOG INPUT (4-20mA OR 0-10 VDC) DAMPER END...
Page 29 - Building Management System
25 EcoBreeze System Installation Building Management System The Modbus interface allows the EcoBreeze System to communicate with a building management system (BMS). The Modbus connection is available in two locations on the Modbus hub: • RJ-45 In port• 3-wire on terminal block For an RJ-45 connectio...
Page 32 - Worldwide Customer Support
Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www.apc.com/support/contact . 6/2014 990-3976D-001 © Schneider Electric is owned by Schneider Electric Industries S.A.S., or its affiliated companies. All other trademar...