Samsung MIM-E03AN - Manuals
Samsung MIM-E03AN Air Conditioner – User Manual, Installation Manual in PDF format online.
Manuals:
User Manual Samsung MIM-E03AN
Installation Manual Samsung MIM-E03AN
Summary
Contents Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Product specifications . . . . . . . . . . . . . . . . . . . . . ...
Safety precautions Carefully follow the precautions listed as below because they are essential to guarantee the safety of SAMSUNG product . WARNING • Always disconnect a power supply of Air-Water Heat Pump before servicing it or accessing components inside the unit . • Verify that installation and t...
Product specifications Item Description MIM-E03 ✴ N Wired remote controller Temp . Sensor Temp . Sensor for DHW Tank (15m, YEL) (1EA) Temp . Sensor for Mixing Valve (15m, BLU) (1EA) Temp . Sensor for Heater (15m, BLK) (1EA) Smart Grid cable (Red, 2 m, 1EA) Flow Switch (1EA, 2m) Sensor holder (2EA, O...
Main components Model name MIM-E03 ✴ N Detail components Parts Qty . Main PBA 1 ELCB- Rated current : 30A - Leakage current : 30mA 1 Grounding screw 8 Rubber 4 Base plate 1 Top cover plate 1 Case screw 2 Weight (Net) 3 .5 kg Packing size (W x H x D) 329 mm x 439 mm x 168 mm ❋ ❋ Flow Switch Set Point...
Installing the unit Installing the remote controller Dimension 120 124 63 .8 19 .5 (Unit : mm) 6 EHS MONO Kit-EU_IM_05388A-04_EN.indd 6 2016-06-23 오후 3:42:56
Installation 1 . Push the two hooks at the bottom of your Wired Remote Controller at the same time, and then pull up the front cover to separate it from the rear cover . ❋ ❋ Push the two hooks at the same time . NOTE • Insert a flat head screwdriver into the square groove in the upper area of the ho...
Installing the unit 3 . Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect communication cables(F3, F4), making sure these cables have reasonable length, to the terminal at the back of the cover . 10 mm or more 10 mm or more 50 mm or more 1...
Wiring works • Field-supplied electrical components such as power switch, circuit breakers, wires, terminal blocks, etc must be properly chosen with compliance with national legislation or regulation . • Switch off the power supply before making any connections .• All field wiring and components mus...
Selecting solderless ring terminal f f Select a solderless ring terminal of a connecting power cable based on a nominal dimensions for cable . f f Cover a solderless ring terminal and a connector part of the power cable and then connect it . Silver solder Nominal dimensions for cable (mm2) 1.5 2.5 4...
Wiring works How to connect your extended power cables 1 . Prepare the following tools . Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) Spec MH-14 20xØ6 .5(HxOD) Width 19mm 70xØ8 .0(LxOD) Shape 2 . As shown in the figure, peel off the shields from the rubber and w...
5 . Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape . Three or more layers of insulation are required . f f Method 1 40 mm Insulation tape f f Method 2 Insulation tape 35 mm 6 . Apply heat to the contraction tube to contract it ....
Wiring works Selection for the power and booster heater wire terminal f f Connect the cables to the terminal board using the solderless ring terminal . f f Use certified and verified cables . f f Connect using a driver which is able to apply the rated torque to the screws . f f If the terminal is lo...
Grounding work f f Grounding must be done by a qualified installer for your safety . Grounding the power cable f f The standard of grounding may vary according to the rated voltage and installation place of a heating pump . f f Ground the power cable according to the following . Installation place P...
Wiring works Power and communication with outdoor unit Power Wire ELCB Communication Wire N L • Be careful when connecting L, N . CAUTION Connecting the power wire 1 . Connect ‘Live’ and 'Neutral’ power line with ‘L, N’ of a ELCB .2 . Connect ‘L,N’ of a ELCB with ‘A1 and A2’ in TB-A . 3 . Connect ‘P...
Connecting the communication wire f f Connect ‘outdoor unit’s F1&F2’ with ‘control kit’s F1&F2 in TB-C’ by 2 core cable . Outdoor Unit (at Control Plate) Control Kit Communication with a wired remote controller (1 unit) Wired Remote Controller (Master) Communication with a wired remote contr...
Wiring works Temp. Sensor for DHW, Backup heater and a water Flow S/W Relay External wiring to control a switch of relay by a installer Temp . sensor for DHW Flow s/w Temp . sensor for backup heater Connecting a temp. sensor wire into DHW 1 . Put the sensor side of a temp . sensor wire into the desi...
DHW tank Switch box layout DHW Tank Temp . (15m) CNS042(YEL) ❋ ❋ Use a correct sensor pocket which is fit for the DHW tank sensor(OD Ø6) . If the gap between the supplied sensor and DHW tank sensor pocket is big, use thermal grease . 19 ENGLISH EHS MONO Kit-EU_IM_05388A-04_EN.indd 19 2016-06-23 오후 3...
DHW tank Electrical connections Procedure • Switch off the power supply before making any connections .• Use a thermal grease in thermistor pocket after installing electric connections . WARNING Connections to be made in the electrical box of DHW tank 1 . Connect the booster heater power supply and ...
Connection of the solar circulation pump / DHW Thermostat for DHW tank Description No. of wires Max. A Thickness Supply Scope Solar pump / DHW Thermostat 2+ground 10 mA 0 .75mm 2 H05RN-F or H07RN-F Field supply (230 V~, Input) SOLAR PUMP / DHW Thermostat (L) SOLAR PUMP / DHW Thermostat (N) Controlle...
Problem Possible cause Solution Heating is not working Heating element or internal electrical wiring is out of order . Check if there is any power on the power supply on the connector of the heating element between black and yellow/green wires . If this is OK, press the reset button on the fuse/safe...
Booster heater Booster heater Recommended wire specification Load Power Supply Power Cable Max. Length mm 2 , wires m Use Booster Heater (Max. 3kW) 1Ø, 220-240V, 50Hz 4 .0 / 3 L < 10m 6 .0 / 3 10m < L ❈ Code designation IEC: 60245 IEC 57/ CENELEC: H05RN-F Connecting a booster heater (PTC heate...
Wiring works Backup heater Relay or Magnetic Contactor Wire Connecting a relay or a magnetic contactor for a backup heater (Not Directly connect a backup heater) 1 . Connect a "relay or a magnetic contactor" with "CNP003,CNP001,CNP002" . f f When a backup heater mode is "ON" ...
Specification table Part Specification Tab-Terminal (output) Step1 : CNP003, CNP001Step2 : CNP003, CNP002 Connection load Relay or Magnetic contactor for a control signal Output(CNP003,CNP001 or (CNP003,CNP001)+(CNP003,CNP002) AC 230V (MAX 0 .5A) Backup boiler Connection of the back-up boiler Descri...
Wiring works Connection guide of additional pump Case 1) INV. pump Connect the PWM control external type pump to PWM terminal block and power cable to the external contact terminal .The maximum number of additional pump installation is one inverter pumps (Input power 100W) .1 . Power supply (INV . P...
Case 2) AC pump The maximum number of additional pump installation is one AC pumps (Input power 100W) .1 . Power supply (AC Pump) Live additional pumpNeutral additional pump B7 B8 LN M/C PCB Terminal block Neutral additional pump Live additional pump B7 B8 Pump Power • Terminal of this product is fo...
Wiring works Connection of the 2-way valve Description No. of wires Max. A Thickness Supply Scope Motorized 2-way valve to shut off UFH loops during cooling . 2+ground 22 mA > 0 .75 mm 2 , H05RN-F or H07RH-F Field supply (230 V~, Output) N L1 N L2 * Connection of 2 wires 2-way valve In case of no...
Wiring works Example zone#1 only : cooling mode zone#2 only : cooling mode zone#1, zone#2 : cooling mode Room thermostat N L Room thermostat N L Room thermostat N L zone#1 only : heating mode zone#2 only : heating mode zone#1, zone#2 : heating mode Room thermostat N L Room thermostat N L Room thermo...
Example of RX1 (Danfoss) f f In manual of a RF receiver RX1 and RX2 N L 1 2 3 4 Terminal 1 RX2 only Electronics Zone 2 on Zone 1 on Zone 1 off Com f f Example of wiring works N L 1 2 3 4 19 20 21 22 23 24 Control kit RF receiver (RX1) Cool (zone#1) Cool (zone#2) Heat (zone#1) Com Heat (zone#2) 31 EN...
Wiring schematics Wiring diagram 33 ENGLISH EHS MONO Kit-EU_IM_05388A-04_EN.indd 33 2016-06-23 오후 3:43:06
Self-test mode of wired remote controller Use of self-test mode 1 . When using the self-test mode of the wired remote controller, press the [<] and [>] buttons for more than 3 seconds . 2 . You can operate the self-test mode as follows . f f Load list: When pressing the corresponding button, you can...
f f Thermostat 1, 2, and solar heat panel are displayed as below when you set them with an control kit . Thermostat 1 (Zone 1), Thermostat 2 (Zone 2), Solar heat panel (ON/OFF) f f Timer button: Whenever you press the button, the sensor value will be displayed in order . TW1(In)sensor TW2(Out1) sens...
Troubleshooting If the unit has some problem to work properly, some error codes will be displayed on the controller .The following table described the explanation of error codes on the LCD display . Thermistor f f Check its resistance . 10kohm@25 °C (Control kit), 200kohm@25 °C (DHW Tank, Solar) f f...
Communication Display Explanation Communication error between remote controller and the Control kit Tracking error between remote controller and the Control kit Memory(EEPROM) Read/Write Error(Wired remote Controller data error) E601, E604 E654 MEMORY(EEPROM) Read/Write Error (Wired controller data ...
Error codes If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT main PBA or LCD of the wired remote controller . Display Explanation Error Source 101 CONTROL KIT / OUTDOOR UNIT wire connection error CONTROL KIT, OUTDOOR UNIT 162 EEPROM Error CONTROL KIT ...
Mixing Valve Installation of mixing valve Under Floor Radiator TW4 Balancing Vessel (Mixing tank) When two different zones are used with different temperature, adjust the temperature of discharge water to high temperature water and control the amount of bypass to provide low temperature water by app...
Mixing Valve ex) Heating <#4041=1> <#4041=2> Tw2 Ta FCU WL #4042 Floor temp Tw2 Ta FCU WL Floor WL ❋ ❋ The mixing valve is controlled based on the FCU WL value . ❋ ❋ As the #4044 value increases and the #4045 value decreases, the control speed increases . (Temperature hunting may occur i...
Concrete curing function When pipes of floor heating are installed, operation for reinforcing concrete curing is applied . (Period of operation: 23 days) Entering procedure 1 . After turning off the DIP switch K3 (3rd switch of SW03) of control kit (Default ON), turn off and turn on the control kit ...
Installation option setting f f Set the control kit installation option with remote controller option . The procedure of option setting High Temp Button High Fan Button Mode change Low Temp Button Low Fan Button Entering mode for option setting Option setting mode 45 ENGLISH EHS MONO Kit-EU_IM_05388...
Installation option setting Entering mode to set option 1 . Remove batteries from the remote controller . 2 . Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button . 3 . Check if you have entered the option setting status . Changing a particular optio...
47 ENGLISH COMMISSION REGULATION (EU) No 813/2013 I) ECODESIGN REQUIREMENTS FOR SPACE HEATER II) A Model(s) : AE050JXYDEH B Air-to-water heat pump : yes C Water-to-water heat pump : no D Brine-to-water heat pump : no E Low-temperature heat pump : no F Equipped with a supplementary heater : no G Heat...
68 COMMISSION DELEGATED REGULATION (EU) No 811/2013 i) PRODUCT FICHE (ENERGY LABELLING OF SPACE HEATERS) ii) a Supplier's name or trademark Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. b Supplier's model identifier AE090JXYDE...
69 ENGLISH PRODUCT FICHE (ENERGY LABELLING OF PACKAGES OF SPACE HEATER) iii) a Supplier's name or trademark Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. Samsung Electronics Co., Ltd. b Supplier's model identifier AE090JXYDEH AE090JXYDGH AE120JXYDEH AE120J...
Samsung Air Conditioners Manuals
-
Samsung AM022TNVDKH/TK
User Manual
-
Samsung AQ07S8GE
User Manual
-
Samsung AQ07S8GE
Manual
-
Samsung AQ09FAX
User Manual
-
Samsung AQ09JWAX
User Manual
-
Samsung AQ12FAN
User Manual
-
Samsung AQ12JWAN
User Manual
-
Samsung AQ18FENSER
User Manual
-
Samsung AR09TXHYBWKN/AR09TXHYBWKX
User Manual
-
Samsung AVMGH052EA4
User Manual
-
Samsung AVMKH026EA4
User Manual
-
Samsung AW05B0LA/AW0519
User Manual
-
Samsung AW07A0SE/AW07A1SE
User Manual
-
Samsung AW126JB/127JB
User Manual
-
Samsung AW-1407B
User Manual
-
Samsung AWH126JE
User Manual
-
Samsung F-AR09BXGYCWK1
User Manual
-
Samsung F-AR09FSSSCWK1
User Manual
-
Samsung F-AR12BXGYCWK1
User Manual
-
Samsung F-AR12FSSSCWK1
User Manual