Page 2 - Contents; Safety Information
2 English Contents For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g. REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_corner.html Safety Information 3 General information 3 Installing the u...
Page 3 - English; Saf; General information; WARNING
3 English Saf e ty Inf ormation WARNING ŷ Hazards or unsafe practices that may result in severe personal injury or death. CAUTION ŷ Hazards or unsafe practices that may result in minor personal injury or property damage. Carefully follow the precautions listed below because they are essential to gua...
Page 4 - This appliance can be used by; Installing the unit; – It may cause electric shock or fire due to poor
4 Safety Information English Saf e ty Inf ormation ŷ This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the applian...
Page 5 - Installation Procedure; Installation location requirements; CAUTION; CAUTION
5 English Installation Pr ocedur e Installation Procedure Step 1 Choosing the installation location Installation location requirements ŷ Do not place the outdoor unit on its side or upside down. Failing to do so may cause the compressor lubrication oil to run into the cooling circuit and lead to a s...
Page 6 - A Type; Minimum clearances for the outdoor unit
6 Installation Procedure English Installation Pr ocedur e ŷ Install the unit in a place where water can drain smoothly. ŷ If you have any difficulty finding installation location as prescribed above, contact your manufacturer for details. ŷ Be sure to clean the sea water and the dust on the heat exc...
Page 7 - Louver specifications.; Moving the outdoor unit with wire rope; Move the outdoor unit.; Step 2 Fixing the outdoor unit in place
7 English Installation Pr ocedur e 300 or more 300 or more 500 or mor e 500 or mor e CAUTION ŷ The outdoor unit must be installed according to the specified distances in order to permit accessibility from each side, to guarantee correct operation, maintenance, and repair of the unit. The components ...
Page 8 - – The screws do not damage the copper pipe.; NOTE; Air conditioning system examples
8 Installation Procedure English Installation Pr ocedur e CAUTION ŷ Install a drain outlet at the lowest end around the base for outdoor unit drainage ŷ When installing the outdoor unit on the roof, waterproof the unit and check the ceiling strength. ŷ Make sure that the wall can support the weights...
Page 9 - Connecting the main power cable; When using ELB for 1 phase and 3 phase
9 English Installation Pr ocedur e When using earth leakage circuit breaker (ELCB) for a 3-phase, 4-wire system (3P4W) MCCB ELCB ELB Main power cable Communication cableOutdoor-to-indoor power cable Earthing Outdoor Unit Indoor Unit OR CAUTION ŷ If the outdoor unit is installed in a location vulnera...
Page 10 - Main power terminal block specifications
10 Installation Procedure English Installation Pr ocedur e CAUTION ŷ You should connect the power cable into the power cable terminal and fasten it with a clamp. ŷ The unbalanced power must be maintained within 2% of supply rating. If the power is unbalanced greatly, it may shorten the life of the c...
Page 13 - Connect the rated cables only.; Must keep the cable in a protection tube.
13 English Installation Pr ocedur e Nominal dimensions for cable (mm²) Nominal dimensions for screw (mm) B D d1 E F L d2 t Standard dimension (mm) Allowance (mm) Standard dimension (mm) Allowance (mm) Standard dimension (mm) Allowance (mm) Min. (mm) Min. (mm) Max. (mm) Standard dimension (mm) Allowa...
Page 14 - Prepare the following tools.; : Push the core wire into the sleeve from
14 Installation Procedure English Installation Pr ocedur e Outdoor-to-indoor power and communication cables specifications Indoor power supply Power supply Max/Min (V) Indoor power cable 1 ĭ , 220-240V, 50 Hz ±10% 2.5 mm² Ĺ , 3 wires Communication cable 0.75 to 1.5 mm², 2 wires ŷ Power supply cords ...
Page 15 - Three or more layers of insulation are required.; – Incomplete wire connections can cause electric
15 English Installation Pr ocedur e ŷ After compressing it, pull both sides of the wire to make sure it is firmly pressed. Compress it 4 times. 5 mm Compress it 4 times. 5 mm Method 1 Method 2 5 Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the in...
Page 16 - Step 5 Connecting the refrigerant pipe; Items; Outer diameter
16 Installation Procedure English Installation Pr ocedur e Step 5 Connecting the refrigerant pipe Items Maximum allowable length Outdoor unit models AC071KX4DKH AC090KX4DKH AC100KX4DKH AC100KX4DNH AC120KX4DKH AC120KX4DNH AC140KX4DKH AC140KX4DNH Main pipe (L1) 50 m 75 m Max. height difference between...
Page 17 - Slide a flare nut on to the pipe and modify the flare.
17 English Installation Pr ocedur e CAUTION ŷ After connecting the pipes with knock-out treatment, plug the space around the pipes. ŷ After connecting the pipes, proceed exactly as directed in the guide to prevent interference with the internal parts. Step 6 Optional: Cutting and flaring the pipes 1...
Page 18 - Step 7 Installing oil traps; Check the following list and install an oil trap.
18 Installation Procedure English Installation Pr ocedur e Step 7 Installing oil traps Check the following list and install an oil trap. ŷ Based on cooling operation, install it on the gas side pipe only. ŷ Install the oil trap only in between the outdoor unit and the first branch joint and it shoul...
Page 19 - Turn off the vacuum pump.; Calculating the quantity of refrigerant to
19 English Installation Pr ocedur e 4 Open the valve of the low pressure side(A) of manifold gauge anticlockwise. A(Gas) B(liquid) Outdoor Unit Vacuum Pump 5 Purge the air from the system using vacuum pump for about 10 minutes. ŷ Close the valve of the low pressure side of manifold gauge clockwise. ...
Page 20 - : The factory refrigerant charge of the product.; GWP: Global Warming Potential; Calculating the quantity of refrigerant to add
20 Installation Procedure English Installation Pr ocedur e Indoor Unit Outdoor Unit Liquid side stop valve(service port)Gas side stop valve(service port) Balance Ref Vacuum pump Important information regulation regarding the refrigerant used This product contains fluorinated greenhouse gases. Do not...
Page 21 - When installing the outdoor unit only; Step 10 Performing the gas leak test; LEAK TEST WITH NITROGEN (before opening valves)
21 English Installation Pr ocedur e When installing the outdoor unit only Model Interconnection pipe length (m) 0 to 30 30 to 40 40 to 50 50 to 60 60 to 70 70 to 75 AC071KX4DKH +20 g/m over 5m AC090KX4DKH 0 +50 g/m over 30 m AC100KX4DKH +50 g/m over 30 m AC100KX4DNH +50 g/m over 30 m AC120KX4DKH +50...
Page 22 - Step 12 Insulating the refrigerant pipes; Select the insulation of the refrigerant pipe.
22 Installation Procedure English Installation Pr ocedur e 4 Ensure that the drained water runs off correctly and safely. 80 mm 13 mm 5 Be sure to plug the rest of drain holes not connected with drain plugs using drain caps. Drain cap (4EA) Drain plug (1EA) Drain cap (5EA)Drain plug (2EA) ŷ When ins...
Page 23 - Step 13 Checking the earthing
23 English Installation Pr ocedur e Pipe Pipe size Insulation Type (Heating/Cooling) Remarks Standard [Less than 30°C, 85%] High humidity [over 30°C, 85%] EPDM, NBR Liquid pipe Ø6.35~Ø9.52 9 t 9 t Internal temperature is higher than 120°C Ø12.7~Ø19.05 13 t 13 t Gas pipe Ø6.35 13 t 19 t Ø9.52~Ø19.05 ...
Page 24 - Outdoor
24 Installation Procedure English Installation Pr ocedur e 2 Check the indoor unit. a Check that you have connected the power and communication cables correctly. (If the power cable and communication cables one mixed up or connected incorrectly, the PCB will be damaged.) b Check that the thermistor ...
Page 26 - DIP switch option; Setting the address manually
26 Installation Procedure English Installation Pr ocedur e 7 DIP switch option ON 1 2 3 4 1 2 3 4 ON SW507 SW508 ŷ DIP switch (SW507) option On (default) Off Switch 1 Auto address (high level controller) Manual address (*1) (high level controller) Switch 2 Disable snow prevention control Enable snow...
Page 27 - Extr; Extra Procedures; Pumping down refrigerant; Pumping down; Using the stop valve; Opening the stop valve
27 English Extr a Pr ocedur es Extra Procedures Pumping down refrigerant Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area. 1 Remove the cap from the low pressure side. 2 Turn the low pressure side valve clockwise to close and connect a pressu...
Page 28 - Closing the stop valve; Tighten the cap securely.
28 Extra Procedures English Extr a Pr ocedur es NOTE ŷ Do not apply excessive force to the stop valve and always use special instruments. Otherwise, the stopping box can be damaged and the back sheet can leaks. ŷ If the watertight sheet leaks, turn the axis back by half, tighten the stopping box, th...
Page 29 - Troubleshooting; Appendix
29 English Appendix Troubleshooting The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. No. Error Code Meaning ...
Page 31 - Technical specifications
31 English Appendix Technical specifications Model Net weight Net dimension (W × D × H) AC071KX4DKH/EU 50.5 kg 880 mm × 310 mm × 798 mm AC090KX4DKH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC100KX4DKH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC100KX4DNH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC120KX4DKH/EU 80.0 ...
Page 32 - PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS)
32 Appendix English Appendix COMMISSION DELEGATED REGULATION (EU) No 626/2011 i) PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS) ii) A Supplier's name - Samsung Electronics Co.. Ltd. B Model name (Indoor/Outdoor) - AC071KN4DKH / AC071KX4DKH AC090KN4DKH / AC090KX4DKH AC100KN4DKH / AC100KX4DKH C ...
Page 40 - mismo consulte siempre a un profesional.
40 Appendix English Appendix [Spanish-ES] 1 Las fugas de refrigerante contribuyen al cambio climático. Cuanto mayor sea el potencial de calentamiento global (GWP) de un refrigerante, más contribuirá a dicho calentamiento su vertido a la atmósfera. Este aparato contiene un líquido refrigerante con un...
Page 41 - , durante um período de 100 anos. Nunca tome a iniciativa de intervir
41 English Appendix [Portuguese-PT] 1 A fuga de fluido refrigerante contribui para as alterações climáticas. Os fluidos refrigerantes com menor potencial de aquecimento global (PAG) contribuem menos para o aquecimento global do que os fluidos refrigerantes com maior PAG, em caso de fuga para a atmos...
Page 42 - výrobok a vždy sa obráťte na odborníka.
42 Appendix English Appendix [Polish-PL] 1 Wycieki czynników chłodniczych przyczyniają się do zmiany klimatu. W przypadku przedostania się do atmosfery czynnik chłodniczy o niższym współczynniku ocieplenia globalnego (GWP) ma mniejszy wpływ na globalne ocieplenie niż czynnik o wyższym współczynniku ...
Page 43 - pe o perioadă de 100 de ani. Nu încercați să
43 English Appendix [Romanian-RO] 1 Scurgerea de agent frigorific contribuie la schimbările climatice. Dacă s-ar scurge în atmosferă, agenții frigorifici cu un potențial de încălzire globală (GWP) mai redus ar contribui într-un mod mai puțin semnificativ la încălzirea globală decât un agent frigorif...
Page 44 - under
44 Appendix English Appendix [Danish-DA] 1 Kølemiddeludslip medvirker til klimaforandringerne. Slipper kølemidlet ud i atmosfæren, bidrager det mindre til den globale opvarmning, hvis dets potentiale for global opvarmning (GWP) er lavt, end hvis det er højt. Dette apparat indeholder en kølevæske, hv...
Page 46 - Memo