Page 2 - Contents
These instructions are provided to assure the proper installation and operation of Raypak boilers. Should questions arise regarding the specifications, installa- tion, operation or servicing of these boilers, we suggest that the local Sales representative or the factory be consulted. 2 3 1. RECEIVIN...
Page 4 - INSTALLATION PROCEDURES
3. INSTALLATION PROCEDURES CODE REQUIREMENTS Installation must be in accordance with local codes , or, in the absence of local codes, with the latest editions of the National Fuel Gas Code , ANSI Z223.1 , and the National Electrical Code , ANSI/NFPA 70. In Canada installations must conform with the ...
Page 5 - two; If louvers, grills or screens are used on the; wood
2) When the boiler is installed in a confined space such as a utility room or closet (Models 0030,0042and 0066 only), where all air is supplied from inside the building, the boiler room must be provided with two openings, each one having a minimum net free area, in square inches as follows: Model Sq...
Page 6 - These boilers must not be connected into; ANSI; Roof Pitch
The weight of the vent stack or chimney must not rest on boiler draft hood. Support must be provided in compliance with applicable codes. The boiler top anddraft hood must be readily removable for maintenance and inspection. Vent pipe should be adequately sup- ported to maintain proper clearances fr...
Page 8 - MOUNTING; do not; to the side of the vent.; Hole in Vent Damper Blade; INSTALLING THE VENT DAMPER IN HORIZONTAL
8 MOUNTING On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent. The vent damper is set up for a continuous pil...
Page 9 - contacts
9 VENT DAMPER NORMAL OPERATION SUMMARY For safe, efficient operation, the vent damper and all flue product carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources. Check vent damper operation as follows: 1. When the b...
Page 10 - Sediment Trap Gas Valve; MODEL NAT PRO NAT PRO NAT PRO NAT PRO; System
The gas valve is provided with pressure taps to measure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres-sure. WATER CONNECTIONS & SYSTEM PIPING The pipe size for water connections is shown on page 3. Typical piping systems are shown on pages 11 to 13....
Page 11 - the chilled medium from entering the boiler.; TYPICAL PIPING
Systems with multiple zones may require an additional circulator. Consult manufacturers data for valve pressure drops. When an indirect water heating system is used, it is recommended that a separate circulator beinstalled to meet the required flow and pressure drop conditions of the indirect water ...
Page 14 - WIRING DIAGRAM KEY; If it is necessary to replace any of the original; ELECTRICAL WIRING
14 WIRING DIAGRAM KEY Fig.# 8096.2 The room thermostat should be installed in accordance with the manufacturer's instructions. The thermostat heat anticipator should be set at 1.0 ampere (automatic ignition) and 0.60 ampere (standing pilot) for single zone installations. For multi-zone applications,...
Page 15 - See page 14 wiring diagram key information.; WIRING DIAGRAM: STANDING PILOT 24 V 2 STAGE
Fig. # 2223e See page 14 wiring diagram key information. 15 WIRING DIAGRAM: STANDING PILOT 24 V 2 STAGE MODELS 90, 135 & 180
Page 16 - *REFER TO INSTALLATION/OPERATING INSTRUCTIONS
16 WIRING DIAGRAM:INTERMITTENT IGNITION DEVICE (IID) MODELS 30, 42, & 66 See page 14 wiring diagram key information. *REFER TO INSTALLATION/OPERATING INSTRUCTIONS AND WIRING DIAGRAM SUPPLIED WITH VENT DAMPER. VENT DAMPER OPTIONAL ON CANADIAN MODELS.
Page 18 - WIRING DIAGRAM: Dual Zone Honeywell Valve
WIRING DIAGRAM: Single Zone Taco Valve WIRING DIAGRAM: Dual Zone Taco Valve WIRING DIAGRAM: Dual Zone Honeywell Valve NOTE: Maximum three (3) zone valves per one (1) 40 VA transformer. NOTE: Maximum five (5) zone valves per one (1) 40 VA Transformer. Fig. # 2230e Fig. # 2229e Fig. # 2228e 18
Page 22 - SERVICING PROCEDURES; GENERAL LOCATION OF CONTROLS; CONTROL BOX COMPONENT; SEQUENCE OF OPERATION
4. SERVICING PROCEDURES GENERAL LOCATION OF CONTROLS Fast Response Temperature Sensor CONTROL BOX COMPONENT LOCATIONS MODELS 135 & 180 2-Staged Controller Relay Fig.# 8195.1 Ignition Module (Auto Ignition Only) 22 Fig.# 8195.4 SEQUENCE OF OPERATION INTERMITTENT IGNITION DEVICE (IID) Boilers equi...
Page 23 - Circulator motor supplied with the boiler does
START-UP PROCEDURES SECTION 1 . Filling the System Fill system with water. Purge all air from the system using purge valve sequence. After system is purged of air, lower system pressure. Open valves for normal system operation, fill system through feed pressure regulator to minimum 12 PSI. Manually ...
Page 24 - SECTION 3. Lighting the Boiler; Liquefied petroleum gas is heavier than air; For Standing Pilot Models; If you do not follow these instructions; BEFORE LIGHTING
24 SECTION 3. Lighting the Boiler Safe lighting and other performance criteria were met with the gas manifold and control assembly pro- vided on the boiler when the boiler underwent tests specified in ANSI-Z21.13a 1983 Standard. CAUTION: Liquefied petroleum gas is heavier than air and sinks to the g...
Page 27 - DO NOT; Testing the Ignition Safety Shutoff.
3 2 1 S E T P I L O T O N O F F PILOT ADJ PILOT KEY CAUTION: Should overheating occur or the gas supply fails to shut off, DO NOT turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the boiler. Failure to observe this precaution may ag...
Page 28 - Modulating burner flame varies in height from
Fig. #8964 PILOT BURNER FLAME (STG PILOT UNITS) NORMAL INSPECTION PROCEDURES First and third month after initial start up and then on an annual basis. If problems are found, refer to Trouble Shooting Guide for additional directions. 1. Remove top of boiler and inspect heat exchanger for soot and exa...
Page 31 - TROUBLE SHOOTING GUIDE; IMPORTANT NOTICE; equipment nor attempt repairs according to these instructions.
5. TROUBLE SHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some...
Page 33 - Make sure electrical power to the boiler is disconnect-
ADJUSTMENTS/REPLACEMENTS OF COMPONENTS DANGER - SHOCK HAZARD Make sure electrical power to the boiler is disconnect- ed to avoid potential serious injury or damage to com- ponents. 1. Gas Valve Replacement a) Shut off electrical power and gas supply to the boiler. b) Remove gas piping to gas valve i...
Page 34 - CAUTION; To avoid damage to electrical components; REPLACEMENT PARTS LIST; To supply the correct part it is important that you
j) Reverse above procedure to re-install. 9. Fast Response Temperature Sensor Module Replacement a) Shut-off electrical power to the boiler. b) Remove control cover screws and open control compartment. c) Disconnect wiring connections to the board. d) Carefully pull out the control board from the ny...
Page 36 - LIEU OF HSI IGNITION.
36 BOILERS MANUFACTURED AFTER AUGUST 11, 1994 WITH SERIAL #9408116901 OR LATER, HAVE IID IGNITION IN LIEU OF HSI IGNITION.