Raypak 2072B-2342B - Manual
Raypak 2072B-2342B – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Project Name / Date
1
FINNED WATER-TUBE POOL HEATERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes gas-fired, copper finned-tube pool heaters.
B. Related
Sections
Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. Electrical – Division 23 09 33
1.2 REFERENCES
A. ANSI Z21.10.3/CSA 4.3
B. ASME, Section IV
C. 2006 UMC, Section 1107.6
D. ANSI/ASHRAE 15-1994, Section 8.13.6
E. National Fuel Gas Code
F. NEC
G. ASME CSD-1, 2006
1.3 SUBMITTALS
A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)
B. Wiring
diagram
C. Warranty
information
D. Installation and operating instructions
1.4 QUALITY
ASSURANCE
A. Regulatory
Requirements
1. ANSI Z21.10.3/CSA 4.3
2. Local and national air quality regulations for low NOx (0-30 PPM NOx emissions) pool heaters
B. Certifications
1. CSA
2. ASME HLW Stamp and National Board Listed
3. ISO
9001
1.5 HEAT
EXCHANGER
WARRANTY
A. Limited ten-year warranty from date of installation
B. Limited twenty-year thermal shock warranty from date of installation
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Raypak,
Inc.
1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;
Fax: (800) 872-9725; Web site: www.raypak.com
2. Product: Hi Delta
®
copper finned-tube pool heater(s)
2.2 POOL
HEATERS
A. General
Catalog No.: 6000.62
Effective: 9-15-08
Replaces: 6-1-08
HI DELTA
®
, TYPE WHP - MODELS 2072B-2342B
SUGGESTED SPECIFICATIONS
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.