Kidde TM0098 - Manuals

Kidde TM0098 – Manual in PDF format online.

Manuals:

1 Page 1
2 Page 2
3 Page 3
4 Page 4

Summary

Page 2 - Preparation and Precautions

TM0098 Page 2 of 4 Issue 1.00 2.0 Preparation and Precautions When performing a hot wire test, ensure that all local standards, practices and regulations areunderstood and have been adhered to where applicable. Also, ensure that the detection equipmentbeing proved/tested is isolated from both the lo...

Page 3 - Applicable code wire burn recommendations:; seconds for 2 metres; Preparation and Connection of the Test Wire; If in doubt, please seek guidance from a; Smoke Test; The test wire becomes very hot during

TM0098 Page 3 of 4 Issue 1.00 It is recommended that the accuracy of the burn period is confirmed using a stopwatch with the redindicator on the timer before conducting any live tests. Applicable code wire burn recommendations: • BS6266:1992 recommends a burn time of 60 seconds for one metre wire le...

Page 4 - References; BS6266:2002 (which cross references to the BFPSA Code of Practice); Specifications; Hot Wire Test Box; Compliance

TM0098 Page 4 of 4 Issue 1.00 The current to the wire is turned off automatically after the set period is complete. Smoke will havebeen generated and the time for it to be detected should be recorded to ensure that transport andalarm times are within the local regulatory requirements. 7. References ...