• For mobile home installation, select locations carefully to avoid thermal barriers that may form at the ceiling. For more details, see MOBILE HOME INSTALLATION below. • When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall (see Diagram A). • When mounting t...
• Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to operate, or a shock hazard. • Make certain alarms are wired to a continuous (non-switched) power line. NOTE: Use standard UL listed household wire (18 gauge or larger as required by loca...
4. OPERATION AND TESTING OPERATION: The smoke alarm is operating once A.C. power is applied, fresh batteries are installedand testing is complete. When the smoke alarm ionization chamber senses products of combustion,the horn will sound a loud (85db) temporal alarm until the sensing chamber is clear...