Page 2 - Johnson Controls Unitary Products; LIMITATIONS; SECTION III: UNIT INSTALLATION; LOCATION; GROUND INSTALLATION; Ambient Air Temperature; NOTICE
1031452-UIM-B-0513 2 Johnson Controls Unitary Products LIMITATIONS The unit should be installed in accordance with all National, State andLocal Safety Codes and the limitations listed below: 1. Limitations for the indoor unit, coil, and appropriate accessoriesmust also be observed. 2. The outdoor un...
Page 3 - LIQUID LINE FILTER-DRIER; Apply with Models
1031452-UIM-B-0513 Johnson Controls Unitary Products 3 LIQUID LINE FILTER-DRIER The air conditioning unit’s copper spun filter/dryer is located on the liq-uid line. PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora-tor coil using field supplied refrigerant grade ...
Page 4 - Connect the refrigerant lines using the following procedure:; SECTION IV: ORIFICE INSTALLATION; Install Schrader Valve Core as follows:
1031452-UIM-B-0513 4 Johnson Controls Unitary Products Connect the refrigerant lines using the following procedure: 1. Remove the cap and Schrader core from both the liquid and vaporservice valve service ports at the outdoor unit. Connect low pres-sure nitrogen to the liquid line service port. 2. Br...
Page 5 - SECTION V: TXV INSTALLATIONS; SECTION VI: EVACUATION
1031452-UIM-B-0513 Johnson Controls Unitary Products 5 SECTION V: TXV INSTALLATIONS The following are the basic steps for installation. For detailed instruc-tions, refer to the Installation Instructions accompanying the TXV kit.Install TXV kit as follows: 1. Relieve the holding charge by pulling off...
Page 6 - SUPERHEAT CHARGING METHOD -; SECTION VIII: ELECTRICAL; GENERAL INFORMATION & GROUNDING
1031452-UIM-B-0513 6 Johnson Controls Unitary Products SUPERHEAT CHARGING METHOD - PISTON INDOOR 1. Operate system until temperatures and pressures stabilize (mini-mum of 10 minutes). 2. Measure and record indoor wet bulb (WB) temperature using asling psychrometer and the outdoor dry bulb (DB) tempe...
Page 7 - FIELD CONNECTIONS CONTROL WIRING
1031452-UIM-B-0513 Johnson Controls Unitary Products 7 FIELD CONNECTIONS CONTROL WIRING 1. Route low voltage wiring into bottom of control box as shown inFigure 6. Make low voltage wiring connections inside the low volt-age box per Figures 7 - 11. 2. The complete connection diagram and schematic wir...
Page 8 - Single Stage Air Conditioner
1031452-UIM-B-0513 8 Johnson Controls Unitary Products For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in theProduct Catalog Section. FIGURE 8: Thermostat Chart - Single Stage AC with PSC Air Handler AC 1A Sing...
Page 12 - SECTION IX: INSTRUCTING THE OWNER; MAINTENANCE
1031452-UIM-B-0513 12 Johnson Controls Unitary Products SECTION IX: INSTRUCTING THE OWNER Assist owner with processing warranty cards and/or online registration.Review Owners Guide and provide a copy to the owner and guidanceon proper operation and maintenance. Instruct the owner or the opera-tor ho...
Page 13 - SECTION X: WIRING DIAGRAM
1031452-UIM-B-0513 Johnson Controls Unitary Products 13 SECTION X: WIRING DIAGRAM FIGURE 12: Wiring Diagram
Page 14 - NOTES
1031452-UIM-B-0513 14 Johnson Controls Unitary Products NOTES
Page 15 - SECTION XI: START UP SHEET; Air Conditioning and Heating Start-Up Sheet; Owner Information
1031452-UIM-B-0513 Johnson Controls Unitary Products 15 SECTION XI: START UP SHEET Air Conditioning and Heating Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Name Address City State or Province Zip or Postal Code Indoor Unit Model # Indoor Unit Serial # Indoo...
Page 16 - York International Corp.
Subject to change without notice. Published in U.S.A. 1031452-UIM-B-0513 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 1031452-UIM-A-0413 York International Corp. 5005 York Drive Norman, OK 73069 Supply static after indoor coil (in w.c.") Return Static (in w.c."...