Valve and Actuator Manual

977

Actuators and Positioners Section

Product Bulletin

VA-8051

Issue Date 0988

© 1988 Johnson Controls, Inc.

1

Part No.14-548-9 Rev. A
Code No. LIT- 977305

VA-8051 Electric Valve Actuator

Floating Control, 50 lb. Force

The VA-8051 synchronous,
motor-driven actuator provides
floating control of valves with up
to 3/4 in. stroke in heating,
ventilating, and air conditioning
applications. This compact,
non-spring return actuator has a
50 lb. force and is compatible
with a 3-wire, 24 VAC signal.
A

±

12 VDC signal from a

DSC-8500 may be used with a
VA-8000-104 drive card to
position the VA-8051. A
3400 ohm (nominal) position
feedback potentiometer is also
included for remote position
indication to meters or a
DSC-8500. The VA-8051 can be
ordered factory coupled to
VB Series Valves. See AV-8051
bulletin for code numbers.

Operation

A controller sends 24 VAC to
the up or down terminal on the
circuit board depending on the
desired movement of the valve.
This signal causes the motor to
rotate in the proper direction,
and through the lead screw and
lever, move the valve up or
down. When the controller stops
sending a signal, the valve
remains in place.

When the controller closes the
valve, a shutoff force will build
up. When this force reaches
50 lbs., the lever activates a
force sensor which stops the
motor. Field calibration of the
force sensor is not required. The
actuator maintains the shutoff
force even if power to the
controller is lost. When the
controller signals the valve to
move in the opposite direction,
the shutoff force will be reduced
and the valve will modulate.

The internal position feedback
potentiometer is connected to
the R, W, and S terminals.
Specifically, the wiper is
connected to W. The wiper will
be at the R end when the
actuator is retracted and at the
S end when the actuator is fully
stroked.

Specifications

Product

VA-8051-1 Electric Valve Actuator

Control Mode

Floating Control, 3-W ire

Supply Voltage

24 VAC + 6 V, -4V, 200 mA, 50/60 Hz

Power Consumption

6 VA

Feedback

3400 Ohms

±

25%, 20 VDC Max Input Voltage

Shutoff Force

50 lb. Force Minimum

Stroke Time

1/2 in. Stroke: Approx. 65 Sec
3/4 in. Stroke: Approx. 90 Sec

Ambient Operating Temperature

0 to 140

°

F (-18 to 60

°

C), 90% RH Max,

85

°

F Max Dew Point

Ambient Storage Temperature

-40 to 150

°

F (-40 to 65

°

C)

Media Temperature

Water: 190

°

F (88

°

C)

Steam (with Insulator Kit): 280

°

F (138

°

C)

VA-8000-101 Steam Insulator Kit

Accessories

VA-8000-102 Valve Position Indicator Kit
VA-8000-104 Auxiliary Interface Board

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.

Fig. 1: VA-8051-1 Connected to VB-3754

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Wiring

2 VA-8051 Product Bulletin Wiring All wiring must be in accordancewith applicable electrical coderequirements. Input lines to theactuator must be wired correctlyfor the valve to move in theproper direction.

Page 3 - Retrofit Installation; Do not use on

VA-8051 Product Bulletin 3 Wiring is to a terminal striplabeled DWN (Down), COM(Common) and UP,respectively. Wiring is to theterminals labeled R (Retractedend), W (Wiper), and S (Strokedend) for the feedbackpotentiometer.(See Fig. 6). Retrofit Installation ! CAUTION: Do not use on valves having a st...

Page 5 - Repair Information

VA-8051 Product Bulletin 5 Repair Information Field repairs must not be made.For a replacement VA-8051,contact the nearest JohnsonControls branch office. Application and DrawingIdentification Fig. 3: Isometric Drawing Fig. 4: VA-8051-1 Dimensions in./mm. Fig. 5: Internal View