Johnson Controls M9220-GGX-3 - Manual
Johnson Controls M9220-GGX-3 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Dimensions
- Page 3 – Removable Coupler; Table 1: Accessories and Replacement Parts (Order Separately); Crank arm
- Page 4 – To reposition the actuator hub, proceed as follows:; Figure 2: Side A of Actuator; Applying excessive torque to the; Figure 4: Changing the Position of the Coupler
- Page 5 – Mounting the Actuator
- Page 6 – Figure 7: Damper Position Icons; Figure 8: One Stroke Limiting Stop
- Page 7 – Wiring; CAUTION: Risk of Electric Shock; Make all wiring connections in; Figure 9: Auxiliary Switch Wiring Diagram for; Figure 10: Control Wiring Diagrams
- Page 8 – Setup and Adjustments; Direction of Action; To calibrate the control input range, proceed as follows:; Figure 11: Nominal Feedback Signal Relative to; Rotation Position; Figure 12: Mode Selection; RA
- Page 9 – Follow these guidelines for tandem operation:; must; be configured as; Figure 13: Tandem Connection; Figure 14: Tandem Selector Switch; Master
- Page 10 – Repairs and Replacement; Figure 16: Switch Point Settings
- Page 11 – Technical Specifications; 0VA Minimum per Actuator
- Page 12 – NEMA 2 (IP54) for All Mounting Orientations
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions
1
Applications
The M9220-GGx-3 Proportional Electric Actuators are
direct-mount, spring return electric actuators that
operate on AC/DC 24V power. These bidirectional
actuators do not require a damper linkage, and are
easily installed on dampers with 1/2 to 3/4 in. or 12 to
19 mm round shafts, or 3/8 and 1/2 in. or
10, 12, and 14 mm square shafts using the standard
shaft clamp included with the actuator. An optional
M9220-600 Jackshaft Coupler Kit is available for
3/4 to 1-1/16 in. or 19 to 27 mm round shafts, or
5/8 and 3/4 in. or 16, 18, and 19 mm square shafts.
A single M9220-GGx-3 Series Proportional Electric
Spring Return Actuator provides a running and spring
return torque of 177 lb·in (20 N·m). Two or three like
models mounted in tandem deliver twice or triple the
torque (354 lb·in [40 N·m] or 531 lb·in [60 N·m]).
Integral line voltage auxiliary switches are available on
the GGC models to indicate end-stop position or to
perform switching functions within the selected rotation
range.
Installation
The M9220-GGx-3 Proportional Electric Spring Return
Actuators mount directly to the surface in any
convenient orientation using two M3 x 9.5 mm
self-drilling sheet metal screws and the anti-rotation
bracket (parts included with the actuator). No additional
linkages or couplers are required. Electrical
connections are color-coded and identified with
numbers permanently marked on the actuator cable.
A tag on the actuator cable identifies the electrical
connections, and wiring details are also included on the
actuator housing.
Parts Included
•
proportional electric spring return actuator with
coupler
•
anti-rotation bracket
•
manual override crank
•
two M3 x 9.5 mm self-drilling sheet metal mounting
screws
•
two No. 10-32 x 9/16 in. thread-forming conduit
screws
Special Tools Needed
•
torque wrench with 3/8 in. (10 mm) socket
•
digital voltmeter or M9000-200 Commissioning
Tool
•
flat blade screwdriver
IMPORTANT:
Use this M9220-GGx-3 Proportional
Electric Spring Return Actuator only to control
equipment under normal operating conditions.
Where failure or malfunction of the electric actuator
could lead to personal injury or property damage to
the controlled equipment or other property,
additional precautions must be designed into the
control system. Incorporate and maintain other
devices such as supervisory or alarm systems or
safety or limit controls intended to warn of, or protect
against, failure or malfunction of the electric
actuator.
IMPORTANT:
Do not install or use this
M9220 GGx-3 Proportional Electric Spring Return
Actuator in or near environments where corrosive
substances or vapors could be present. Exposure of
the electric actuator to corrosive environments may
damage the internal components of the device, and
will void the warranty.
M9220-GGx-3
Proportional Electric Spring Return Actuators
Installation Instructions
Part No. 34-636-1697, Rev. B
Issued February 4, 2009
Supersedes June 20, 2006
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions 2 Dimensions Figure 1: M9220-GGx-3 Proportional Electric Spring Return Actuator Dimensions, in. (mm) A 4 (102) 10-5/16 (262) 2-3/16 (56) F IG :M 9 21 0 _ 9 2 20 _ d im en 1-3/4 (44) 1/8 (3) 3-3/16 (81) 3/4 (19) 2-3/1...
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions 3 Accessories Mounting The M9220-GGx-3 Proportional Electric Spring Return Actuators can be easily installed on dampers with 1/2 to 3/4 in. or 12 to 19 mm round shafts, or 3/8 and 1/2 in. or 10, 12, and 14 mm square ...
M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions 4 Counterclockwise (CCW) Spring Return Direction – Clockwise (CW) Powered Operation For CCW spring return direction, mount the actuator to the damper shaft so that Side A of the actuator is away from the damper as il...