Page 2 - DIMENSIONS
—2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.2. MI...
Page 3 - RECOMMENDED TUBE DIAMETERS; CERTIFICATION APPLIES ONLY
—3— RECOMMENDED TUBE DIAMETERS * For tube sets greater than 50 ft, consult Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using Puron® Refrigerant. CHECK-FLO-RATER® PISTON * Piston listed is for any approved non-capillary tube coil combination. Piston is shipped with outdoo...
Page 4 - SPECIFICATIONS
—4— SPECIFICATIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating Weight (Lb) 168 178 188 198 ELECTRICAL Unit Volts—Hertz—Phase 208/230-60-1 Operating Voltage Range* 187-253 Compressor— Rated Load Amps 10.3 13.5 15.4 17.9 Locked Rotor Amps 51.0 61.0 73.0 100.0 Condenser Fan ...
Page 5 - SPECIFICATIONS Continued
—5— SPECIFICATIONS Continued * Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure. † If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of n...
Page 8 - COMBINATION RATINGS
—8— COMBINATION RATINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT. CAP. BTUH FACTORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.5 11.0 11.0 9.95 CC5A/CD5AA018 17,000 NONE 10.5 11.0 11.0 9...
Page 9 - COMBINATION RATINGS Continued
—9— COMBINATION RATINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT. CAP. BTUH FACTORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.5 — 11.5 10.40 CE3AA030 23,800 TDR 11.5 — 11.5 10.60 CK5...
Page 14 - EER; TXV
—14— * Tested combination. † In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Bryant furnaces are equipped with T...
Page 15 - DETAILED COOLING CAPACITIES*
—15— DETAILED COOLING CAPACITIES* See notes on page 22. EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBt...
Page 17 - DETAILED COOLING CAPACITIES* Continued
—17— DETAILED COOLING CAPACITIES* Continued See notes on page 22. EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Ca...
Page 23 - CONDENSER ONLY RATINGS*; SST
—23— CONDENSER ONLY RATINGS* See notes on page 25. SST °F CONDENSER ENTERING AIR TEMPERATURES °F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.9073.70 0.77 15.0083.10 0.92 14.2092.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.40 120.80 1.71 10.40 130.20 1.95 9.30 139.50 2.20 35 TCG SDT KW ...
Page 24 - CONDENSER ONLY RATINGS* Continued
—24— CONDENSER ONLY RATINGS* Continued See notes on page 25. SST °F CONDENSER ENTERING AIR TEMPERATURES °F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.7077.00 1.99 30.9086.20 2.23 29.1095.40 2.49 27.30 104.60 2.77 25.40 113.80 3.09 23.50 122.90 3.43 21.50 132.00 3.79 19.40 140.90 4.19 35 ...
Page 25 - SYSTEM DESIGN SUMMARY; Do not apply capillary tube indoor coils to these units.
—25— SYSTEM DESIGN SUMMARY 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).3. Maximum outdoor operating a...
Page 26 - MATCHED SYSTEM
Page 28 - GUIDE SPECIFICATIONS; GENERAL
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No. 5259-100 9-01 GUIDE SPECIFICATIONS GENERAL System Des...