Page 2 - LEGEND
WARNING: Before performing service or maintenance operations on system, turn off main power to unit andinstall lock-out tag. Turn off accessory heater powerswitch if applicable. Electrical shock could cause severeinjury or death. CAUTION: Puron® (R-410A) systems operate at higher pressures than stan...
Page 3 - Connections
pre-programmed table of airflows.The unit must be configured to operate properly with systemcomponents with which it is installed. To successfully configure abasic system (see information printed on circuit board label locatednext to select pins), move the 6 select wires to the pins whichmatch the c...
Page 5 - EASY SELECT; PIN CONNECTOR
(1.) If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closescircuits R to G, R to Y/Y2 and R to O—The unit deliverssingle speed cooling airflow. c. COOLING MODE-DEHUMIDIFICATION (1.) If indoor temperature is above temperature set point and hum...
Page 6 - Fig. 10—ThermidistatTM Wiring for
(4.) ENH (enhanced) selection provides a 30 sec. cooling & heat pump on delay with no airflow, plus 150 seconds at 70percent airflow and no off delay for added comfort. Thiswill minimize cold blow in heat pump operation and couldenhance system efficiency. f. CONTINUOUS FAN—SELECT DESIRED FAN SPE...
Page 11 - If the burners do not light, this lighting sequence is
remains on for 4 minutes. Observe that compressor,outdoor fan and indoor blower motors start after the callfor Cooling. At the end of 4 minutes, the cooling cyclestops and the MODE reverts back to OFF. The IndoorBlower continues to run for the time selected on the EasySelect™ board after OFF icon is...
Page 12 - Scroll
blower motor stops. The unit is in a ‘‘standby’’ condition, waitingfor the next ‘‘call for cooling’’ from the room thermostat. The 5minute compressor delay also applies to heat pump heating mode. ELECTRICAL DATA & SCHEMATICS—ICM FIOP I. PHYSICAL DATA & ELECTRICAL SCHEMATICS Use the Physical ...
Page 14 - Fig. 14—ICM FIOP Electric Schematic—Unit 583B
Fig. 14—ICM FIOP Electric Schematic—Unit 583B C01035 —14—
Page 15 - TABLE 4—ICM FIOP PHYSICAL DATA—UNIT 683B
TABLE 4—ICM FIOP PHYSICAL DATA—UNIT 683B THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 024040 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 310 324 324 321 321 380 380 COMPRESSORS Quantity Scroll ...
Page 17 - Fig. 15—ICM FIOP Electric Schematic—Unit 683B
Fig. 15—ICM FIOP Electric Schematic—Unit 683B C01101 —17—
Page 18 - TABLE 7—ICM FIOP PHYSICAL DATA—UNIT 702B
TABLE 7—ICM FIOP PHYSICAL DATA—UNIT 702B THIS DATA APPLIES TO 702B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb) 270 291 299 321 326 399 COMPRESSOR Scroll REFRIGERANT (R-410A) Quantity (lb) 5.0 5.5 6.9 9.0 9.5 ...
Page 19 - TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA
TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA UNIT SIZE 702B V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.05.4/7.2 7...
Page 20 - Fig. 16—ICM FIOP Electrical Schematic—702B
Fig. 16—ICM FIOP Electrical Schematic—702B C01037 —20—
Page 21 - TABLE 9—ICM FIOP PHYSICAL DATA—UNIT 602B; SCROLL COMPRESSOR
TABLE 9—ICM FIOP PHYSICAL DATA—UNIT 602B THIS DATA APPLIES TO 602B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 602B024 602B030 602B036 602B042 602B048 602B060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 299 320 328 350 355 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REF...
Page 22 - TABLE 10—602B WITH ICM FIOP ELECTRICAL DATA
TABLE 10—602B WITH ICM FIOP ELECTRICAL DATA UNIT SIZE 602B V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.05.4/7.2 ...
Page 23 - Fig. 17—ICM FIOP Electrical Schematic—602B
Fig. 17—ICM FIOP Electrical Schematic—602B c01036 —23—
Page 24 - SMALL CABINET
TABLE 11–583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY) DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 024 COOLING † 745 675 – 835 750 690 940 8...
Page 27 - TABLE 23—ELECTRIC HEATER MULTIPLICATION FACTORS
TABLE 21—ICM FIOP WET COIL PRESSURE DROP (IN. WG) UNIT SIZE STANDARD CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 024 0.005 0.007 0.010 0.012 0.015 – – – – – – – – – – – 030 – 0.007 0.010 0.012 0.015 0.018 0.021 0.024 – – – – – – – – 036 – – – 0.019 0.023 0....
Page 28 - ICM QUICK REFERENCE GUIDE; QUICK REFERENCE GUIDE; SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES; according to Installation Instructions.; • Option 17 - Select programmable or non-programmable mode.; Thermidistat Control Configurations; EASY SELECT BOARD; TABLE 24—TROUBLESHOOTING CHART; SYSTEM
ICM QUICK REFERENCE GUIDE c01034 EASY SELECT HEATER/MOTOR AUX HEAT KW/CFM 0-30 1075 SEC1 SEC2 J1 AC/HP SIZE 036 030 024 018 AC HP-COMFORT HP-EFF NOM HI ENH LO SYSTEM TYPE AC/HP CFM ADJUST ON/OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0-20 875 0-10 72...