Page 3 - Overview; Inventory
SBP20K Series User Manual 1 Overview The APC ® by Schneider Electric service bypass panel (SBP), provides utility power to connected equipment during UPS maintenance. Inventory Read the Safety Guide before installing the UPS . Inspect the SBP upon receipt. Notify the carrier and dealer if there is d...
Page 4 - Specifications; Electrical Specifications; Environmental Specifications
SBP20K Series User Manual 2 Specifications Electrical Specifications Note: The table above represents the electrical ratings of the SBP and not those of the UPS. UPS wire specifications may vary. The SBP requires a minimum wire size of 25 mm 2 and a maximum wire size of 50 mm 2 . Refer to the UPS us...
Page 5 - Front panel
SBP20K Series User Manual 3 Front panel Rear panels Callout Description Equipment outlets Equipment outlet circuit breakers Utility input power hardwire access Output power hardwire access SBP20KRMI4U SBP20KRMT4U SBP20KP Test Test Normal Bypass Normal Load protected Load not protected Load not prote...
Page 6 - Installation; Stack configuration
SBP20K Series User Manual 4 Installation Stack configuration Rack-mount configuration Always place the SBP above the external battery packs and the UPS. Four ornamental screws (supplied), must be used to secure each tie bracket to the units, (see diagram). Install rails in rack For details on rail i...
Page 7 - Wall-mount configuration
SBP20K Series User Manual 5 Wall-mount configuration Secure the wall-mount brackets to the unit using eight ornamental screws (supplied), four in each bracket. Secure the SBP to the wall. Select screws (not supplied), that are appropriate for the weight of the unit and the mounting surface material....
Page 8 - Hardwire the SBP; Hardwiring must be performed by a qualified electrician.
SBP20K Series User Manual 6 Hardwire the SBP Hardwiring must be performed by a qualified electrician. Adhere to all national and local electrical codes. Switch the utility circuit breaker off. Remove the terminal block access panel located on top of the unit. On all models , remove the access panel ...
Page 9 - Hardwire the UPS; Refer to the UPS user manual for detailed instructions.
SBP20K Series User Manual 7 Hardwire the UPS Refer to the UPS user manual for detailed instructions. SBP20KRMI4U SBP20KRMT4U SBP20KP L2/N L1 N L3 L2 L1 N L3 L2 L1 L2/N L1 L2/N L1 L2/N L1 L2/N L1 L2/N L1 N L3 L2 L1 N L3 L2 L1
Page 10 - Operation; Reconnect SBP to UPS
SBP20K Series User Manual 8 Operation Normal mode While the SBP operates in normal mode, power is supplied to connected equipment from the UPS providing protection from power variations and disturbances. Test mode 1. Switch the UPS to Bypass mode. Verify that no UPS fault conditions exist. In the ev...
Page 11 - Troubleshooting; Contact information
SBP20K Series User Manual 9 Troubleshooting Use the table to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex problems. Contact information Customer support for this or any other APC product is available at no charge in any of the fo...
Page 12 - Transport the unit; Two-Year Factory Warranty; Terms of warranty
SBP20K Series User Manual 10 Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com . a....
Page 13 - Exclusions
SBP20K Series User Manual 11 Exclusions APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation or testing. Further, APC shall ...