Page 3 - Contents
Contents 150/175kW Modular PDU Installation i Overview .......................................................................... 1 Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 5 - Overview; Important Safety Information; DANGER; WARNING; CAUTION; CAUTION; NOTICE
1 150/175kw Modular PDU Installation Overview Important Safety Information Read the instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on th...
Page 6 - Disclaimer
150/175kw Modular PDU Installation 2 Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Sch...
Page 7 - Additional Safety Information
3 150/175kw Modular PDU Installation Additional Safety Information Before you begin Verify that the system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the National Electrical Code in the U.S.A., for instance). If high-poten...
Page 8 - About This Manual; Related Documents
150/175kw Modular PDU Installation 4 About This Manual This manual is intended for users of the specified APC equipment. It contains important safety warnings and instructions, gives an introduction to the display interface and provides detailed information for proper use of the equipment. Related D...
Page 9 - Installation; Electrical Safety; SAVE THESE INSTRUCTIONS!; Inrow Installation
5 150/175kw Modular PDU Installation Installation Electrical Safety SAVE THESE INSTRUCTIONS! This document contains important instructions that should be followed during installation of the 150/175kW Modular Power Distribution Unit (PDU). Inrow Installation Maintain 36” hot aisle spacing. DANGER HAZ...
Page 11 - Install Input Power Cables
7 150/175kw Modular PDU Installation Install Input Power Cables Top entry installation 1 Open the front door. Unlatch and swing the display interface and bracket out towards the front door. 2 Loosen the captive screws and remove the top safety panel. 3 Loosen the captive screws and remove the front ...
Page 13 - Power In
9 150/175kw Modular PDU Installation 3 Take the cables that are preinstalled in the Side Car and route them through the left side into the PDU. pdx0879a Power In To PDU
Page 14 - Install Subfeed Cables
150/175kw Modular PDU Installation 10 Install Subfeed Cables 1 Open the rear doors. 2 Remove the subfeed safety panel. 3 Loosen the four captive screws on each of two rear dedicated cover plates. Drill holes in the plates for conduits and re-install the plate with the conduits installed. Note: Remov...
Page 15 - Install User Input/Output Contacts
11 150/175kw Modular PDU Installation Install User Input/Output Contacts Note: Contact wires from external signaling, alarming, and sensing devices may be connected to the interface board to allow the controller to monitor these devices and to also control outside devices through the output contacts...
Page 17 - Install the Communication Cable
13 150/175kw Modular PDU Installation Install the Communication Cable 1 Connect the CAT-5 cable for StruxureWare Central or your local area network to the RJ45 connection coupling on top of the PDU. 2 Inside the PDU enclosure, a second CAT- 5 cable is connected to the other side of RJ45 coupling. 3 ...
Page 20 - Options; Shielding Troughs
150/175kw Modular PDU Installation 16 Options Shielding Troughs 1 Snap an APC-provided trough into slots on the roof of the PDU. The tabs at the base of the trough must fit securely into the slots. Note: Properly align the PDU trough with troughs installed on top of the enclosures located adjacent t...
Page 21 - Seismic Stability Kit
17 150/175kw Modular PDU Installation Seismic Stability Kit Install rear anchoring brackets 1 Secure the floor anchoring bracket to the floor using floor anchoring bolts (not supplied). Use M12 strength class 8.8 or 1/2 inch, grade 5 steel bolts. 2 Secure the back of the other half of the bracket as...
Page 23 - Specifications
19 150/175kw Modular PDU Installation Specifications AC Input Model PDPM150G6F PDPM150L6F PDPM175G6H Nominal voltage 480V, 3W +G 600V, 3W +G 480V, 3W + G Frequency 60 Hz 60 Hz 60 Hz Maximum continuous current 180 A 150 A 214 A Nominal current 178 A 141 A 214 A Recommended current rating of input cir...
Page 26 - Regulatory Agency Approval
150/175kw Modular PDU Installation 22 Regulatory Agency Approval This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC and ICES-003 Rules. These limits are designed to provide reasonable protection against harmful interference...
Page 27 - Radio Frequency Interference
Radio Frequency Interference Note: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment. USA — FCC This equipment has been tested and found to comply with the limits for a Class A digital device...
Page 28 - APC Worldwide Customer Support
5/2012 990-4384 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquart...