Page 3 - About this Manual
150kW InfraStruXure PDU—Operation and Configuration i About this Manual This manual is intended for end-users of a 150 kW InfraStruXure PDU. It covers the operation and quick-configuration of the PDU, and includes basic InfraStruXure system operation. For additional information about the InfraStruXu...
Page 5 - Contents
Contents 150kW InfraStruXure PDU—Operation and Configuration iii Safety ......................................................................1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . ....
Page 9 - Safety; Overview; Save these instructions
150kW InfraStruXure PDU—Operation and Configuration 1 Safety Overview Save these instructions This manual contains important instructions that must be followed during installation, operation, and configuration of the InfraStruXure PDU. Safety symbols used in this manual Cross-reference symbols used ...
Page 10 - Warnings; Installation/maintenance
2 150kW InfraStruXure PDU—Operation and Configuration Warnings Receiving/moving Do not tilt the PDU greater than 45° from its vertical axis. Never lay the PDU on its side. Installation/maintenance Only a certified electrician can: • Connect the PDU to its power source • Connect a switch to the EPO i...
Page 11 - Total power off procedure; Main Input
Safety: Warnings 150kW InfraStruXure PDU—Operation and Configuration 3 Total power off procedure 1. Set the PDU Main Input switch to OFF. 2. Set the upstream circuit breaker of the power source to OFF. Emergency Power Off (EPO) Hazardous voltage from the branch circuit must be isolated from the 24 V...
Page 12 - EMI
Safety: Warnings 4 150kW InfraStruXure PDU—Operation and Configuration EMI This equipment has been tested and found to comply with the limits for Class A digital devices, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference whe...
Page 13 - InfraStruXure PDU Components
150kW InfraStruXure PDU—Operation and Configuration 5 Overview InfraStruXure PDU Components The APC 150 kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 150 kW, accepts 480 V or 600 V 3-phase input, and distributes 208 V 3-phase...
Page 14 - InfraStruXure PDU; Front view; PDU power cables
6 150kW InfraStruXure PDU—Operation and Configuration InfraStruXure PDU Front view The PDU power cables feed equipment racks; they are fed through the knockout panels on the top of the PDU. There are the following two options for PDU power cables: multi-circuit power cables that terminate with an ...
Page 15 - Main Output
Overview: InfraStruXure PDU 150kW InfraStruXure PDU—Operation and Configuration 7 Front view (interior) The Main Output circuit breaker protects the distribution circuit breaker panels. The optional sub-feed output circuit breakers offer a means to distribute higher blocks of power to other equi...
Page 16 - Rear view; document pocket
Overview: InfraStruXure PDU 8 150kW InfraStruXure PDU—Operation and Configuration Rear view The document pocket provides storage of documents related to the InfraStruXure PDU.
Page 17 - PDU monitoring unit
Overview: InfraStruXure PDU 150kW InfraStruXure PDU—Operation and Configuration 9 Rear view (interior) The PDU monitoring unit receives signals from several current and voltage monitoring boards that report to a central board assembly located in the PDU monitoring unit. The monitoring unit has one...
Page 19 - Display port; Branch Current Monitor
Overview: InfraStruXure PDU 150kW InfraStruXure PDU—Operation and Configuration 11 The Display port (RJ-45) connects the PDU monitoring unit to the display interface. The Power LED indicates whether the monitoring unit is receiving power. Use the Console port (DB-9) to connect a laptop compute...
Page 20 - User connection plate; ethernet port; input contact connections; relay output connections; EPO
Overview: InfraStruXure PDU 12 150kW InfraStruXure PDU—Operation and Configuration User connection plate For a description and location of the user connection plate, see ( ) on page 6. For clarity, the user connection plate in the illustration below is shown in greater detail. Connect the InfraS...
Page 21 - PDU Display Interface
150kW InfraStruXure PDU—Operation and Configuration 13 PDU Display Interface Overview Use the display interface to configure settings, set alarm thresholds, and provide audible and visual alarms. ESC ? LoadPowered Chec kLog Bypass Alarm Load Powered LED When green, all output pha...
Page 22 - Top-level status screens; Navigating through screens
PDU Display Interface: Overview 14 150kW InfraStruXure PDU—Operation and Configuration Top-level status screens After system start-up, the display interface displays a brief start-up screen and then scrolls automatically and continuously through four screens of basic status information. Press the Up...
Page 23 - Password-protected screens
PDU Display Interface: Overview 150kW InfraStruXure PDU—Operation and Configuration 15 On some screens, continue arrows ( indicate that there are additional screens to view in the category. Press the Up or Down arrow key to view the additional screens. Password-protected screens When configuring...
Page 25 - Output Voltage
150kW InfraStruXure PDU—Operation and Configuration 17 Volt-Meter Screen From the Volt-Meter screen, you can select the following items: Output Voltage Displays each phase-to-phase output voltage (e.g., L1-2 for phase L1 to phase L2) and each phase-to-neutral output voltage (e.g., L1 for phase L1 to...
Page 26 - Contacts Screen
18 150kW InfraStruXure PDU—Operation and Configuration Contacts Screen The PDU can monitor external contact closure events. Possible applications include the following: • Magnetic contact switches• Window foil• Tamper switches• Heat detectors• Water sensors• Pressure sensors• Building smoke and fire...
Page 28 - How to connect contacts to the PDU monitoring unit.
PDU Display Interface: Contacts Screen 20 150kW InfraStruXure PDU—Operation and Configuration How to connect contacts to the PDU monitoring unit. 1. Choose one or more contact number (s) on the User/EPO contacts port on the user connection plate to which you will connect the contacts. The user conne...
Page 29 - Breakers Screen; Open; Closed
150kW InfraStruXure PDU—Operation and Configuration 21 Breakers Screen Use the Breakers screen to view the status of the system and PDU circuit breakers. Main Input Reports status of PDU Main Input breaker ( Open or Closed ). Under normal operation, this switch is Closed .
Page 30 - Alarms Screen; View Active Alarms; Alarms; Entire Log; Clear Log
22 150kW InfraStruXure PDU—Operation and Configuration Alarms Screen View Active Alarms Use this option of the Alarms screen to display active alarms (alarms that have not been resolved). Scroll through the list to view each active alarm. Alarm/Event Log Use this option of the Alarms screen to acces...
Page 31 - Alarm Setup
PDU Display Interface: Alarms Screen 150kW InfraStruXure PDU—Operation and Configuration 23 Alarm Setup Use this option of the Alarms screen to access the following options: Alarm Beeper Use this option of the Alarms screen to turn the alarm beeper ON or OFF. Loading Limits Configure the following i...
Page 32 - PDU Alarms; All Possible
PDU Display Interface: Alarms Screen 24 150kW InfraStruXure PDU—Operation and Configuration PDU Alarms This table lists all alarms that can be generated by the InfraStruXure PDU, as displayed by the All Possible Alarms option, with numeric variables between the < > characters. Logged alarms wi...
Page 33 - Panel Screen; Branch Ckt Loading; Branch Ckt Limits
150kW InfraStruXure PDU—Operation and Configuration 25 Panel Screen Branch Ckt Loading You can display Branch Ckt Loading (Branch Circuit Loading) status if the option to measure current at the distribution circuit breakers is installed. You can view data for each individual panel position on the di...
Page 34 - Panel Configuration; Pos
PDU Display Interface: Panel Screen 26 150kW InfraStruXure PDU—Operation and Configuration Panel Configuration Configure the branch metering settings for each circuit breaker on the distribution panel, or configure both panels simultaneously. To configure a circuit breaker, select the range that inc...
Page 35 - Global Panel Config; Poles; Apply Now; YES
PDU Display Interface: Panel Screen 150kW InfraStruXure PDU—Operation and Configuration 27 Global Panel Config Configures the same number of poles or circuit breaker ratings for all circuit breakers in both distribution panels simultaneously. For example, if your system uses only 3-pole, 20 amp circ...
Page 36 - Config Screen
28 150kW InfraStruXure PDU—Operation and Configuration Config Screen System/Network Use this option of the Config screen to access these options: System Password • Password : Change the system password required to access protected screens and fields in the display interface. Enter a string of up to ...
Page 37 - Electrical Config
PDU Display Interface: Config Screen 150kW InfraStruXure PDU—Operation and Configuration 29 Electrical Config This option of the Config screen displays information about the electrical service that provides input to the InfraStruXure PDU. All of the values displayed on this screen are set at the fac...
Page 38 - System ID
PDU Display Interface: Config Screen 30 150kW InfraStruXure PDU—Operation and Configuration System ID Use this option of the Config screen to identify your InfraStruXure PDU. The following fields can be configured: Factory Defaults Use this option of the Config screen to reset all InfraStruXure PDU ...
Page 39 - Operation; How to Apply Power to the System; power source
150kW InfraStruXure PDU—Operation and Configuration 31 Operation How to Apply Power to the System 1. Close (turn ON) the main circuit breaker of the power source supplying power to the InfraStruXure PDU. 2. Close (turn ON) the Main Input on the InfraStruXure PDU. 3. Power the PDU distribution circui...
Page 40 - distribution; distribution panel
Operation: How to Apply Power to the System 32 150kW InfraStruXure PDU—Operation and Configuration c. Close (turn ON) the subfeed breakers (if applicable). b. Close (turn ON) the PDU distribution panel circuit breakers. Note When the distribution panel circuit breakers are closed (turned ON), the PD...
Page 41 - How to Ensure Total Power Off
150kW InfraStruXure PDU—Operation and Configuration 33 How to Ensure Total Power Off 1. Open (turn OFF) the main circuit breaker on the power source feeding the PDU. 2. Open (turn OFF) the Main Input on the InfraStruXure PDU. 3. Open (turn OFF) the Main Output circuit breaker and subfeed circuit bre...
Page 43 - Communication Configuration; InfraStruXure PDU Management Options
150kW InfraStruXure PDU—Operation and Configuration 35 Communication Configuration InfraStruXure PDU Management Options Overview You have two management options for the InfraStruXure PDU. You can manage the InfraStruXure PDU along with the rest of your InfraStruXure equipment through the InfraStruXu...
Page 44 - Configuring the InfraStruXure Manager; Connect the InfraStruXure PDU to the InfraStruXure Manager
36 150kW InfraStruXure PDU—Operation and Configuration Configuring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure Manager 1. Connect a Cat-5 network cable to the surge-protected ethernet port on the PDU user connection plate. You can make connections from inside the enc...
Page 45 - Connect the InfraStruXure PDU to your network
150kW InfraStruXure PDU—Operation and Configuration 37 Configuring the Network Management Interface Connect the InfraStruXure PDU to your network 1. Connect a Cat-5 network cable to the surge-protected ethernet port on the PDU user connection plate. You can make connections from inside the enclosure...
Page 46 - TCP/IP configuration methods; Start; Start a Web browser when finished
Communication Configuration: Configuring the Network Management Interface 38 150kW InfraStruXure PDU—Operation and Configuration TCP/IP configuration methods Use one of the following methods to define the TCP/IP settings needed by the InfraStruXure PDU: • Device IP Configuration Wizard (See “Device ...
Page 47 - BOOTP & DHCP configuration
Communication Configuration: Configuring the Network Management 150kW InfraStruXure PDU—Operation and Configuration 39 BOOTP & DHCP configuration The Boot Mode Setting, a TCP/IP option in the InfraStruXure PDU’s Network menu, identifies how the TCP/IP settings will be defined. The possible setti...
Page 48 - User Name
Communication Configuration: Configuring the Network Management Interface 40 150kW InfraStruXure PDU—Operation and Configuration 3. When the InfraStruXure PDU reboots, the BOOTP server provides it with the TCP/IP settings. – If you specified a bootup file name, the InfraStruXure PDU attempts to tran...
Page 49 - DHCP Cookie Is
Communication Configuration: Configuring the Network Management 150kW InfraStruXure PDU—Operation and Configuration 41 See your DHCP server documentation to add code to the Vendor Specific Information option. To disable the APC cookie requirement, see “Local access to the control console” on page 42...
Page 50 - Local access to the control console; Remote access to the control console
Communication Configuration: Configuring the Network Management Interface 42 150kW InfraStruXure PDU—Operation and Configuration Local access to the control console You can use a local computer that connects to the InfraStruXure PDU through the console port on the InfraStruXure PDU monitoring unit t...
Page 51 - Control console
Communication Configuration: Configuring the Network Management 150kW InfraStruXure PDU—Operation and Configuration 43 2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the IP address defined in step 1, use one of the following Ping commands: – Windows com...
Page 52 - Web interface
44 150kW InfraStruXure PDU—Operation and Configuration How to Access a Network Management Interface on a Configured InfraStruXure PDU Web interface As your browser, you can use Microsoft ® Internet Explorer 5.0 (and higher) or Netscape ® 4.0.8 (and higher, except Netscape 6. x ) to access the InfraS...
Page 53 - Telnet for basic access.; SNMP
Communication Configuration: How to Access a Network Management 150kW InfraStruXure PDU—Operation and Configuration 45 Telnet for basic access. Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption. To use Telnet to access an...
Page 54 - FTP and SCP
Communication Configuration: How to Access a Network Management Interface on a Configured InfraStruXure PDU 46 150kW InfraStruXure PDU—Operation and Configuration FTP and SCP You can use FTP (enabled by default) or Secure CoPy (SCP) to transfer new firmware to the InfraStruXure PDU, or to access a c...
Page 57 - Customizing and Updating the PDU; Important Safety Instructions; in the hazards of live electrical installation.
150kW InfraStruXure PDU—Operation and Configuration 49 Customizing and Updating the PDU Important Safety Instructions Warn in g APC does not recommend that you perform maintenance of the PDU while it is receiving input power. However, due to the critical nature of data center loads, this may occur. ...
Page 58 - PDU Orderable Part List; Breakers
50 150kW InfraStruXure PDU—Operation and Configuration PDU Orderable Part List Breakers PD1P20ABBSD single- pole, 20-amp breaker PD3P20ABBSD three- pole, 20-amp breaker PD1P50ABBSD single-pole, 50-amp breaker PD3P80ABBSD three- pole, 80-amp breaker PD2P20ABBSD two-pole, 20-amp breaker PD3P100ABBSI t...
Page 59 - Power Cables
Customizing and Updating the PDU 150kW InfraStruXure PDU—Operation and Configuration 51 Power Cables 30 A, 3-wire power cables 20 A, 3-wire power cables SKU Number Description SKU Number Description PDW49L6-30C 49-foot power cable PDW47L21-20R 47-foot power cable PDW51L6-30C 51-foot power cable PDW4...
Page 60 - Add a circuit breaker on the PDU; Add a power cable to the PDU
52 150kW InfraStruXure PDU—Operation and Configuration How to Add Circuit Breakers and Power Cables Add a circuit breaker on the PDU 1. Snap and bolt the new circuit breaker into a position on the panel. 2. Remove the corresponding plastic blanking plate on the front panel of the PDU. Add a power ca...
Page 63 - How to attach the circuit breaker to the mounting brackets
Customizing and Updating the PDU 150kW InfraStruXure PDU—Operation and Configuration 55 How to attach the circuit breaker to the mounting brackets 1. Mount the circuit breaker according to the instructions provided by the manufacturer. 2. Remove the blanking plate from the door of the PDU and replac...
Page 64 - How to connect the sub-feed cable to the circuit breaker; neutral wire
Customizing and Updating the PDU 56 150kW InfraStruXure PDU—Operation and Configuration How to connect the sub-feed cable to the circuit breaker 1. Use a knockout punch to create an appropriately-sized hole in either the top or bottom gland plate on the PDU through which you will route the sub-feed ...
Page 66 - How to connect contacts to the PDU monitoring unit
Customizing and Updating the PDU 58 150kW InfraStruXure PDU—Operation and Configuration How to connect contacts to the PDU monitoring unit 1. Choose one or more contact number(s) on the User/EPO contacts port on the user connection plate to which you will connect the contacts. The user connection pl...
Page 67 - Connecting the switch.; Configuring and testing.; Test
150kW InfraStruXure PDU—Operation and Configuration 59 How to Connect an EPO Switch to the PDU and Test the Switch Overview Connecting the switch. The Emergency Power Off (EPO) switch connects to the PDU user connection plate. The figure on the right shows the location of the user connection plate o...
Page 68 - – Contact Closure—Normally Open; Normally
Customizing and Updating the PDU 60 150kW InfraStruXure PDU—Operation and Configuration Connect an EPO switch to the user connection plate and test the switch 1. Connect the switch to the EPO connection point terminals located on the bottom side of the PDU user connection plate. Read the label next ...
Page 70 - Safety warnings
Customizing and Updating the PDU 62 150kW InfraStruXure PDU—Operation and Configuration Safety warnings Hazardous voltage from the branch circuit must be isolated from the 24 VAC, 24 VDC, and contact closure. 24 VAC and 24 VDC are considered Class 2 circuits as defined in Article 725 of the National...
Page 71 - How to Download Firmware Updates; From a local computer
150kW InfraStruXure PDU—Operation and Configuration 63 How to Download Firmware Updates From a local computer 1. Select a serial port at the local computer, and disable any service that uses that port. 2. Use the configuration cable to connect the selected port to the console port on the PDU monitor...
Page 73 - Specifications; 50 kW InfraStruXure PDU
150kW InfraStruXure PDU—Operation and Configuration 65 Specifications 150 kW InfraStruXure PDU Electrical PD150G6F PD150L6F Input Nominal voltage 480 V, 3-phase 600 V, 3-phase Voltage AC 3-phase, 3-wire 3-phase, 3-wire Frequency 60 Hz , ±3 Hz 60 Hz, ±3 Hz Max. current per phase 200 A 150 A Load capa...
Page 75 - Product Information; Warranty; InfraStruXure Standard Warranty
150kW InfraStruXure PDU—Operation and Configuration 67 Product Information Warranty InfraStruXure Standard Warranty APC warrants that all components of the InfraStruXure system will be free from defect in material and workmanship for a period of two years from the date of start up when start up has ...
Page 77 - APC Three-Phase Systems
150kW InfraStruXure PDU—Operation and Configuration 69 Life-Support Policy APC Three-Phase Systems American Power Conversion Corporation (APC) and its affiliates and subsidiaries worldwide do not recommend the use of any of their products in life-support applications where failure or malfunction of ...
Page 78 - How to Obtain Service; How to contact APC
70 150kW InfraStruXure PDU—Operation and Configuration How to Obtain Service How to contact APC Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit any customer...
Page 79 - Index
Index 150kW InfraStruXure PDU—Operation and Configuration 71 A Agency approvals , 64 Alarm beeper , 23 Alarm LED , 13 Alarm relay map , 19 Alarm setup , 23 Alarm types , 24 Alarm/event log , 22 Alarms screen , 22 – 24 Applying power to the system , 31 – 32 Armed LED , 10 B BOOTP configuration , 39 B...
Page 84 - APC Worldwide Customer Support
*990-1984* APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headquarters) C...