Page 2 - STANDARDS
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM E. The UPS and associated equipment shall operate in conjunction with a primary power supply and an output distribution system to provide quality uninterrupted power for mission critical, electronic equip...
Page 4 - with no additional filters
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.2 SYSTEM CHARACTERISTICS A. System Capacity: The system shall be rated for .8 Pf output in the following frame sizes: 1. 8 kVA/ 6.4kW - Can be configured with up to (3), 3.2kW power modules for N+1 2. 1...
Page 5 - Output Power Factor Rating: The UPS output shall be .8 lagging
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1) >130% for 4 seconds 2) 105% continuous 3) <130% Continuous at N+1 b. Bypass Operation: 1) 100A continuous 8. System AC-AC Efficiency: >90% at 100% load 10. Output Power Factor Rating: The UPS ...
Page 6 - INVERTER
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2. In cases where the source voltage to the UPS is nominal and the applied UPS load is equal to or less than 100% of UPS capacity, input current shall not exceed 130% of UPS output current, while providin...
Page 7 - BYPASS
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.7 AUTOMATIC BYPASS A. As part of the UPS, a system automatic bypass switch shall be provided. The system automatic bypass shall provide a break <11Ms transfer of the critical load from the Inverter o...
Page 11 - REMOVABLE INPUT/OUPUT ELECTRICAL TERMINAL
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM B. The battery jars housed within each removable battery module shall be of the Valve Regulated Lead Acid (VRLA) type. C. The UPS shall incorporate a battery management system to continuously monitor the ...
Page 12 - REMOTE UPS MONITORING
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on reserve mode. 2. The UPS shall also be capabl...
Page 14 - Verify proper charger operation.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 8. Verify proper charger operation. 9. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted start-up, operational training for site personnel shall inclu...