APC Central Air Conditioning System - Manuals
APC Central Air Conditioning System – Manual in PDF format online.
Manuals:
Manual APC Central Air Conditioning System
Summary
Contents NetworkAIR IR Operation, Maintenance, and Troubleshooting i Operation ................................................................1 Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Using the Display . . . . . . . . . . . . . . . . . . . . . . ....
NetworkAIR IR Operation, Maintenance, and Troubleshooting 1 Operation Display Interface Item Function ! Major Alarm LED When red, a major alarm condition exists. " Minor Alarm LED When yellow, a minor alarm condition exists. # Check Log LED When yellow, at least one new major alarm, minor alarm,...
2 NetworkAIR IR Operation, Maintenance, and Troubleshooting Using the Display The first time you apply power to the NetworkAIR IR In-row Precision Air Conditioner the display initializes and runs an LED and alarm-tone test. Scrolling status screens After start-up, the interface displays the firmware...
Operation: Using the Display NetworkAIR IR Operation, Maintenance, and Troubleshooting 3 Main menu screen On any top-level status screen, press the E NTER or E SC key to open the main menu screen. Navigating the interface Selector arrows. Press the up or down arrow key to move the selector arrow ! t...
Operation: Using the Display 4 NetworkAIR IR Operation, Maintenance, and Troubleshooting Password entry The Module has two levels of password protection: • User password for users who need to change basic and environmental settings • Service password for users who need to modify settings that contro...
Operation: Using the Display NetworkAIR IR Operation, Maintenance, and Troubleshooting 5 Stop the System Path: Main Menu > On/Off To stop the System, select the On/Off option on the main menu and change the setting to Off . Note Change the setting to Off to shut down all modes of operation and th...
6 NetworkAIR IR Operation, Maintenance, and Troubleshooting Set Up System Configuration The System configuration options are set at the factory and may be modified during the commissioning of the Modules in the System. System Options Path: Main > Setup > System # > System Config > System...
Operation: Set Up System Configuration NetworkAIR IR Operation, Maintenance, and Troubleshooting 7 # PCIOMs. Set the number of Programmable Customer Input/Output Modules (PCIOMs) installed in the user interface box. This setting controls the number of input contacts and output relays available in th...
Operation: Set Up System Configuration 8 NetworkAIR IR Operation, Maintenance, and Troubleshooting System Delays Path: Main > Setup > System # > System Config > System Delays The System delays protect the Modules in the System from excessive wear and damage, and keep the modes from worki...
Operation: Set Up System Configuration NetworkAIR IR Operation, Maintenance, and Troubleshooting 9 Building management Path: Main > Setup > System # > System Config > Building Management If you are using a building management system with your NetworkAIR IR In-row Precision Air Conditione...
10 NetworkAIR IR Operation, Maintenance, and Troubleshooting Options for Fluid-Cooled Modules Water-cooled Modules have settings for the valves and piping needed to accommodate the heat of rejection method. The NetworkAIR IR In-row Precision Air Conditioner provides cooling by using a fluid coil wit...
Operation: Options for Fluid-Cooled Modules NetworkAIR IR Operation, Maintenance, and Troubleshooting 11 Valve Types Path: Main > Setup > System # > System Config > Valve Types Set the type of valves installed in your piping system. Each valve can be either two-way or three-way. Economiz...
Operation: Options for Fluid-Cooled Modules 12 NetworkAIR IR Operation, Maintenance, and Troubleshooting Coil Fluid Temp Activation Threshold and Deadband Path: Main > Setup > System # > System Config > Coil Fluid Options The selections for Coil Fluid Options help control the optional Mu...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 13 Set Up Contacts and Relays The System can monitor external contact closure events. Possible applications include: • Magnetic contact switches• Window foil• Tamper switches • Heat detectors• Water sensors• Pressure sensors• Building smoke a...
Operation: Set Up Contacts and Relays 14 NetworkAIR IR Operation, Maintenance, and Troubleshooting Action. Set the System controller to respond to the change of status for an input in one of the following ways: Output relays Path: Main > Setup > System # > Input/Output > Output Relays Th...
Operation: Set Up Contacts and Relays NetworkAIR IR Operation, Maintenance, and Troubleshooting 15 Action. The Action field changes as you scroll through the list of events that can be mapped to this relay. Remove indicates that the event is already associated with this relay. Add indicates that the...
16 NetworkAIR IR Operation, Maintenance, and Troubleshooting Set Up Module Configuration The Module configuration settings help the controller determine which components are available and how the Module should operate. Configure Module Paths: Main > Setup > Module > Main Module > Module ...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 17 Set Up Module Control The Module Control options are configured and tuned during the commissioning of each Module. Calibrate airflow manually Nom Coil DP: Set the nominal coil differential pressure. Blower Spd. Adjust the frequency of the ...
Operation: Set Up Module Control 18 NetworkAIR IR Operation, Maintenance, and Troubleshooting Reset variable frequency drive Paths: Main > Setup > Module > Main Module > Module Control > Reset VFD # Main > Setup > Module > Expansion Module > Module Control > Reset VFD #...
Operation: Set Up Module Control NetworkAIR IR Operation, Maintenance, and Troubleshooting 19 Reset compressors Paths: Main > Setup > Module > Main Module > Module Control > Reset Compressors Main > Setup > Module > Expansion Module > Module Control > Reset Compressors ...
20 NetworkAIR IR Operation, Maintenance, and Troubleshooting Control the Environment The System controls the room environment by engaging one of four modes: Cool, Dehumidify, Reheat, or Humidify. These modes may work differently depending on the options and equipment installed in your Modules. How t...
Operation: Control the Environment NetworkAIR IR Operation, Maintenance, and Troubleshooting 21 Dehumidify. Dehumidify mode is controlled by the dehumidify PID controller. The PID controller adjusts the output as required to maintain the temperature at the setpoint. Humidify. The steam cylinder humi...
Operation: Control the Environment 22 NetworkAIR IR Operation, Maintenance, and Troubleshooting Deadbands Path: Main > Control Environment > Deadbands The deadband is the sensitivity range for a setpoint. It is the value above or below the setpoint at which the mode outputs at full capacity. A...
Operation: Control the Environment NetworkAIR IR Operation, Maintenance, and Troubleshooting 23 PID controls Path: Main > Setup > System # > System Config > PID Controls The Proportional plus Integral plus Derivative (PID) loop is used to control the output of the cool, reheat, and dehum...
Operation: Control the Environment 24 NetworkAIR IR Operation, Maintenance, and Troubleshooting How to tune the PIDs A qualified service technician must tune the PID loops to optimize the performance of each mode. The units shown are for temperature. In the dehumidify loop, the units are in percent ...
Operation: Control the Environment NetworkAIR IR Operation, Maintenance, and Troubleshooting 25 Humidification sensitivity Path: Main > Setup > System # > System Config > Humid. Sensitivity Humid. Sensitivity. The humidifier sensitivity band is the percentage of relative humidity below t...
26 NetworkAIR IR Operation, Maintenance, and Troubleshooting Set Up Alarms Set alarms to alert you to abnormal temperatures or humidity levels and the number of hours certain components have been in operation. Alarms will also alert you to malfunctions; however, malfunction alarms are not user-defin...
Operation: Set Up Alarms NetworkAIR IR Operation, Maintenance, and Troubleshooting 27 Maint intervals Path: Main > Setup > System # > Alarms > Maint Intervals The System records the number of hours each of the eight components in each Module has operated. Set the maintenance interval for...
28 NetworkAIR IR Operation, Maintenance, and Troubleshooting Set Up Group Up to four NetworkAIR Systems can be connected to form a redundant Group. Joining Systems together to form a Group provides the following: • Redundancy• A way for other Systems in the Group to assist with the room load• Demand...
Operation: Set Up Group NetworkAIR IR Operation, Maintenance, and Troubleshooting 29 Grp Smoke Alrm. Share smoke alarms among the Systems in this Group. If the Group Smoke Alarm setting is On , all Systems in the Group will shut down if a smoke alarm occurs in one System. Comm Loss Failover. Decide ...
Operation: Set Up Group 30 NetworkAIR IR Operation, Maintenance, and Troubleshooting Configure the list of System Failure Events . If a System failure event occurs, the System in which it occurs transitions to the failed state, and a backup System is engaged if available. Event. Scroll through the l...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 31 Set Up the Display Set display settings, including the time and date, temperature units, passwords, and time-out settings. You can also reset settings to their default values and download new firmware. Password & Time-out Path: Main &g...
Operation: Set Up the Display 32 NetworkAIR IR Operation, Maintenance, and Troubleshooting Pressure units. Set the units of measure for pressure readings and settings to either English (psig) or metric (kPa). Adjust display Path: Main > Setup > System # > Display > Display Adjust Set the...
Operation: Set Up the Display NetworkAIR IR Operation, Maintenance, and Troubleshooting 33 5. In your terminal emulator, ensure that the connection is active (HyperTerminal will display a series of “C” characters) and send the file using the XMODEM protocol. 6. When the download is complete, the scr...
34 NetworkAIR IR Operation, Maintenance, and Troubleshooting Set Up Network Configuration Configure the network settings for Network Management Card from the display interface. The management card allows for remote control and configuration of the NetworkAIR IR In-row Precision Air Conditioner. Netw...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 35 View Status Readings The display interface has several options for viewing the status of the System, its Modules, and the environment being controlled. The status readings for Modules are available under the Main Module and Expansion Modul...
Operation: View Status Readings 36 NetworkAIR IR Operation, Maintenance, and Troubleshooting About Module. View identifying information that is helpful when obtaining service: • Manufacturer Name• Model Number• Date of Manufacture• Serial Number• Firmware Revision• Hardware Revision Humidifier Statu...
Operation: View Status Readings NetworkAIR IR Operation, Maintenance, and Troubleshooting 37 Group status Path: Main > Status > Group The Group Status screen includes information about the member Systems of the Group and their roles. Group Status. View the assigned role and current state of ea...
38 NetworkAIR IR Operation, Maintenance, and Troubleshooting Respond to Alarms When an alarm is triggered, the Main Module alerts you through the display by the following methods: • Alarm beeper• Major or Minor Alarm LED• Active alarm screen• Alarm/Event log Major or minor alarm LEDs When an alarm i...
Operation: Respond to Alarms NetworkAIR IR Operation, Maintenance, and Troubleshooting 39 Clear active alarms Path: Main > Respond to Alarms > Clear Active Alarms Clears all active alarms. If the conditions that caused the alarm still exist, those conditions cause the alarm to be regenerated. ...
Operation: Respond to Alarms 40 NetworkAIR IR Operation, Maintenance, and Troubleshooting Alarm messages and suggested actions Displayed Alarm Message Action Required Air Block Interlock Open • Verify that the air block is in place.• Confirm that the wiring connections for the air block interlock ar...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 47 Network Management Card Quick Configuration The NetworkAIR IR In-row Precision Air Conditioner is shipped with a Network Management Card that provides for the management of the Air Conditioner over your network. You must set up the Network...
Network Management Card: Quick Configuration 48 NetworkAIR IR Operation, Maintenance, and Troubleshooting TCP/IP configuration methods Use one of the following methods to define the TCP/IP settings needed by the Network Management Card: • APC Device IP Configuration Wizard (See “APC Device IP Config...
Network Management Card: Quick Configuration NetworkAIR IR Operation, Maintenance, and Troubleshooting 49 With Boot Mode set to DHCP & BOOTP (the default setting), the Network Management Card attempts to discover a properly configured server. It first searches for a BOOTP server, then a DHCP ser...
Network Management Card: Quick Configuration 50 NetworkAIR IR Operation, Maintenance, and Troubleshooting DHCP. You can use a RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the Network Management Card. 1. A Network Management Card sends out a DHCP request that uses the fo...
Network Management Card: Quick Configuration NetworkAIR IR Operation, Maintenance, and Troubleshooting 51 Local access to the control console You can use a local computer that connects to the NetworkAIR IR System through the serial port on the control board to access the control console. Whenever po...
Network Management Card: Quick Configuration 52 NetworkAIR IR Operation, Maintenance, and Troubleshooting Remote access to the control console From any computer on the same subnet as the Network Management Card, you can use ARP and Ping to assign an IP address to a Network Management Card, and then ...
Network Management Card: Quick Configuration NetworkAIR IR Operation, Maintenance, and Troubleshooting 53 TCP/IP settings, select the Boot Mode menu. Select Manual boot mode , and then press E SC to return to the TCP/IP menu. (Changes will take effect when you log out.) 4. Set the System IP , Subnet...
54 NetworkAIR IR Operation, Maintenance, and Troubleshooting How to Access a Configured Unit Overview After the Network Management Card is running on your network, you can use the interfaces summarized here to access the NetworkAIR IR In-row Precision Air Conditioner. Web interface As your browser, ...
Network Management Card: How to Access a Configured Unit NetworkAIR IR Operation, Maintenance, and Troubleshooting 55 Telnet for basic access. Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption. To use Telnet to access a N...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 57 How to Recover From a Lost Password You can use a local computer, a computer that connects to the Network Management Card or other device through the serial port to access the control console. 1. Select a serial port at the local computer,...
58 NetworkAIR IR Operation, Maintenance, and Troubleshooting How to Upgrade Firmware For you to be able to use FTP to upgrade a single Network Management Card over the network: • The Network Management Card must be connected to the network.• The FTP server must be enabled at the Network Management C...
Network Management Card: How to Upgrade Firmware NetworkAIR IR Operation, Maintenance, and Troubleshooting 59 5. Upgrade the AOS. For example: ftp> bin ftp> put apc_hw02_aos_225.bin 6. When FTP confirms the transfer, type quit to close the session. 7. Wait 20 seconds, and then repeat step 2 th...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 61 Maintenance Monthly Preventive Maintenance Photocopy and use the pages in this section during the maintenance procedures and save them for future reference. Prepared by: _________________________________ Model Number: _____________________...
Maintenance: Monthly Preventive Maintenance 62 NetworkAIR IR Operation, Maintenance, and Troubleshooting Cleanliness * Check the condition of return air filters. Replace them if necessary. * Check the condition of the drain pan and remove any accumulation of debris in the pan. Mechanical * Ensure th...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 63 Quarterly Preventive Maintenance Photocopy and use the pages in this section during the maintenance procedures, and save them for future reference. Perform all the Monthly Preventive Maintenance items AND the items below. Prepared by: ____...
Maintenance: Quarterly Preventive Maintenance 64 NetworkAIR IR Operation, Maintenance, and Troubleshooting Functional tests * Verify the following modes of operation: • Full cooling • Full reheat • Humidification • Dehumidification * Verify the operation of these actuators: • Chilled water • Hot wat...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 65 Semi-Annual Preventive Maintenance Photocopy and use the pages in this section during the maintenance procedures and save them for future reference. Perform all the Monthly/Quarterly Preventive Maintenance items AND the items below. Prepar...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 67 Troubleshooting Refrigeration Problem Possible Cause Corrective Action Controls are erratic or inoperative • Incorrect secondary voltage. • Ensure that the control transformer secondary voltage is within +/- 10% of 24 VAC. • Remote shutdow...
Troubleshooting: Semi-Annual Preventive Maintenance NetworkAIR IR Operation, Maintenance, and Troubleshooting 69 hlj Problem Possible Cause Corrective Action Humidifier inoperative • Water supply is not on.• Electrical connections are loose. • Humidifier fuse is open.• Relative humidity is above the...
NetworkAIR IR Operation, Maintenance, and Troubleshooting 71 Warranty Limited Product Warranty for APC Products The limited warranty provided by American Power Conversion Corporation (“APC”) in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or in...
Limited Product Warranty for APC Products 72 NetworkAIR IR Operation, Maintenance, and Troubleshooting Assignment of warranties APC will assign to you any warranties which are made by manufacturers and suppliers of components of the APC Product and which are assignable. Any such warranties are assig...
74 NetworkAIR IR Operation, Maintenance, and Troubleshooting Warranty Procedures Claims You will need the model number of the Product, the serial number, and the date purchased. A technician will also ask you to describe the problem. If it is determined that the Product will need to be returned to A...
Warranty Procedures NetworkAIR IR Operation, Maintenance, and Troubleshooting 75 Parts • APC warrants the parts of their systems for 1 year from the date of commissioning or 18 months from the ship date. This warranty only covers the cost of the part and not the labor for installation. • Calls for w...
*990-2260-001* APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headquarter...
APC Manuals
-
APC AR8163ABLK
Manual
-
APC 1500 VA
Manual
-
APC PRO 1200/1500
Manual
-
APC DP300E Series
Manual
-
APC 1500RMXL2U
Manual
-
APC 1400VA XL
Manual
-
APC VA 1000
Manual
-
APC SUA24XLBP
Manual
-
APC 1000
Manual
-
APC RBC9
Manual
-
APC 450
Manual
-
APC 2000
Manual
-
APC RBC9I
Manual
-
APC AP9604S
Manual
-
APC AP9554
Manual
-
APC RS 540W
Manual
-
APC Smart-UPS 1000
Manual
-
APC H10
Manual
-
APC SURTA2000XL
Manual
-
APC 4075KVA208V
Manual