APC ACPCW40-150 - Manuals
APC ACPCW40-150 – Manual in PDF format online.
Manuals:
Manual APC ACPCW40-150
Summary
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development pl...
Contents InRoom Precision AC Tech Data Manual i Overview ..................................................................................................... 1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Scalable Solution fo...
ii InRoom Precision AC Tech Data Manual InRoom Nomenclature Voltage B: 208-230V G: 380-415VK: 460-480V M: 575-600V Z: 400V Phase/Hertz A: 3/60 B: 3/50 Reheat X - None, E - Electric Humidification X - None, E - Immersed Electrode Mains Input Selection 0 - Standard Disconnect, na2 8 68a Refrigerant H:...
1 InRoom Precision AC Tech Data Manual Overview General The InRoom product family is an assemble to order (ATO) line of perimeter air conditioning systems that provide precision cooling for data centers and server rooms.Precision environmental close control requirements now reach far beyond the conf...
InRoom Precision AC Tech Data Manual 2 Scalable Solution for Critical Environments Temperature and Humidity Design Conditions Maintenance of temperature and humidity design conditions is critical to the smooth operation of a technology room. Based on ASHRAE TC9.9, the recommended design conditions f...
3 InRoom Precision AC Tech Data Manual Standard Features Insulated Panels The frame is constructed of 16 gauge steel sheet metal for maximum strength. All exterior panels and corner posts on the frame are powder coated for durability and an attractive finish. The side panels are double wall construc...
InRoom Precision AC Tech Data Manual 4 Optional Features Humidifier The humidifier utilizes a pure steam generator specifically designed for precision environmental close control. The pure steam eliminates contaminating mineral deposits, potentially harmful bacteria, white dust, and excessive humidi...
5 InRoom Precision AC Tech Data Manual Condensate Pump Model # ACAC75107 ACAC75107 ACAC76106 Hz 60 60 50 Height mm (in) 259 (10 1/8) 259 (10 1/8) 210 (8 1/4) Width mm (in) 152 (6) 152 (6) 132 (5 1/4) Length 304 (12) 304 (12) 295 (11 1/2) Outlet mm (in) 13 (1/2) 13 (1/2) 6 (1/4) Volts 230 460 400 Amp...
InRoom Precision AC Tech Data Manual 6 Upflow Discharge Plenums for 50 Hz and 60 Hz InRoom Cooling Units Note: Plenums are delivered completely assembled. Upflow discharge plenums Cabinet size SKU Width mm (in) Depth mm (in) Height mm (in) 1 ACPL75100 1000 (39.37) 900 (35) 500 (19.7) 2 ACPL75101 140...
7 InRoom Precision AC Tech Data Manual Downflow Discharge Plenums for 50 Hz InRoom Cooling Units Note: • All three sub-base plenum models are attached to the cooling unit with 4x M10 screws.• Sub-base plenums with grills are equipped with adjustable horizontal fins to direct exiting air. • The ple...
InRoom Precision AC Tech Data Manual 8 Standard Floorstands for InRoom 60Hz Cooling Units Cabinet size Model Height mm (in) Width mm (in) Depth mm (in) 1 ACFS76000 254 (10) 960 (37.8) 864 (34) ACFS76001 305 (12) ACFS76002 381 (15) ACFS76003 457 (18) ACFS76004 609 (24) 2 ACFS76005 254 (10) 1359 (53.5...
9 InRoom Precision AC Tech Data Manual Bowling Alley Floorstands for InRoom 60Hz Cooling Units Cabinet size Model Height mm (in) Width mm (in) Depth mm (in) 1 ACFS76033 305 (12) 960 (37.8) 864 (34) ACFS76032 381 (15) ACFS76031 457 (18) ACFS76030 609 (24) 2 ACFS76037 305 (12) 1359 (53.5) 864 (34) ACF...
InRoom Precision AC Tech Data Manual 10 Floorstands for InRoom 50 HzCooling Units Cabinet size Model Height mm (in) Width mm (in) Depth mm (in) 1 ACFS76025 250-500 (10-20) 960 (37.8) 864 (34) 2 ACFS76026 250-500 (10-20) 1359 (53.5) 864 (34) 3 ACFS76027 250-500 (10-20) 1712 (67.4) 864 (34) 4 ACFS7602...
11 InRoom Precision AC Tech Data Manual Condensers Air cooled condensers are designed to reject heat from refrigerant based cooling equipment and are designed to be installed outdoors. The condensers are self-contained in a lighweight aluminum cabinet designed for mounting to a horizontal surface. T...
InRoom Precision AC Tech Data Manual 12 InRoom Standard Condensers - 60 Hz * Condenser connections may not represent actual line sizing.** Dimensions are overall. Electrical enclosure and fan guard are included. Actual fan guard height is 4 in. Actual electrical enclosure depth is 6.5 in. InRoom Rem...
InRoom Precision AC Tech Data Manual 14 InRoom High Temperature Condensers - 60 Hz * Condenser connections may not represent actual line sizing.** Dimensions are overall. Electrical enclosure and fan guard are included. Actual fan guard height is 4 in. Actual electrical enclosure depth is 6.5 in. In...
15 InRoom Precision AC Tech Data Manual InRoom Condensers - 50 Hz * Condenser connections may not represent actual line sizing. InRoom Remote Outdoor Condenser Data, 97°F ambient, 120°F condensation - R407CInRoom Cabinet Size 1 2 3 4 5 Condenser Model (Qty) ACCD76002 ACCD76003 ACCD76002 (2) ACCD7600...
InRoom Precision AC Tech Data Manual 16 Receivers Conformance. Each receiver conforms to UL, CSA or ASME requirements for 450 psi maximum working pressure. Models with an internal diameter under six inches are UL listed. All larger models are made according to ASME code and labeled appropriately. Pu...
17 InRoom Precision AC Tech Data Manual InRoom Receivers - 50 Hz InRoom Cabinet Size 1 2 3 4 5 50 Hz Air-Cooled Condenser Model ACCD76002 ACCD76003 ACCD76002 (2) ACCD76003 (2) ACCD76011 (2) 50 Hz Receiver Model (Qty) ACAC76101 ACAC7610 2 ACAC76103 (2) ACAC76104 (2) ACAC76105 (2) Max Refrigerant Char...
InRoom Precision AC Tech Data Manual 18 Display Interface The display interface is standard on each system. The display interface provides precision control for the demanding requirements of these environments: • Data centers• Control rooms• Clean rooms • Switch rooms • UPS rooms The easy-to-use dis...
19 InRoom Precision AC Tech Data Manual InRoom Model Sizes Different variations of the InRoom product range are defined by the airflow direction, the number of refrigerant circuits, and the type of cooling system. There are five cabinet sizes. The front service access for all cabinet sizes of the In...
InRoom Precision AC Tech Data Manual 20 InRoom Cooling Unit Configurations Fluid Cooled (Glycol) InRoom Fluid Cooled (Glycol) systems are completely charged and factory tested in a sealed system for reliability. In mid to low ambient climates, an economizer coil can be used to increase efficiency an...
21 InRoom Precision AC Tech Data Manual The InRoom Fluid Cooled (Glycol) System with Chilled Water System is a combination of a factory sealed glycol system and a chilled water system and contains two separate cooling coils. The controller microprocessor manages the systems to allow the glycol syste...
23 InRoom Precision AC Tech Data Manual 60Hz Performance Specifications Chilled Water (CW) – 60Hz Chilled Water PCW400 Cabinet Size 1 PCW660 Cabinet Size 2 PCW900 Cabinet Size 3 PCW1100 Cabinet Size 4 PCW1500 Cabinet Size 5 26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH Total - kW (BTU/hr) 53.6 (182...
27 InRoom Precision AC Tech Data Manual MultiCool – Air Cooled (DX) with CW – 60Hz Operational Mode: Air Cooled (DX) Net Cooling Capacity PACW211 Cabinet Size 1 PACW311Cabinet Size 2 PACW452Cabinet Size 3 PACW612Cabinet Size 4 PACW862Cabinet Size 5 26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH Tota...
43 InRoom Precision AC Tech Data Manual 60Hz InRoom Electrical Specifications Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data With Reheat and Humidification Without Reheat and Humidification Compressor Data Model Size Airflow Pattern Cooling System Voltage (3ph/60Hz) MCA MOP Power (kW) MCA...
45 InRoom Precision AC Tech Data Manual 50Hz Performance Specifications Chilled Water (CW) - 50Hz Net Cooling Capacity PCW400 Cabinet Size 1 PCW660 Cabinet Size 2 PCW900 Cabinet Size 3 PCW1100 Cabinet Size 4 PCW1500 Cabinet Size 5 26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH Total - kW (BTU/hr) 53...
InRoom Precision AC Tech Data Manual 50 Operational Mode: Chilled Water Net Cooling Capacity - 7.2°C (45°F) EWT PACW211 Cabinet Size 1 PACW311 Cabinet Size 2 PACW452 Cabinet Size 3 PACW612 Cabinet Size 4 PACW862 Cabinet Size 5 26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH Total - kW (BTU/hr) 34.3 (...
InRoom Precision AC Tech Data Manual 62 50Hz InRoom Electrical Specifications Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data Chilled Water (CW) Electrical Data With Reheat and Humidification Without Reheat and Humidification Compressor Data Model Size Airflow Pattern Cooling System Voltag...
63 InRoom Precision AC Tech Data Manual General Specifications Technical Specifications Application Limits The InRoom precision air conditioning units operate within the following ranges: Design Conditions Return air conditions for evaporator capacity (DX): 24°C (75°F) 50% RHReturn air conditions fo...
InRoom Precision AC Tech Data Manual 64 Transporting and Storage Delivery of the unit The cooling unit is mounted on a pallet, wrapped in plastic film, and surrounded with cardboard for added protection. The unit must be transported in the upright position. PAXXX models are delivered with 1 kg. (2.2...
65 InRoom Precision AC Tech Data Manual Guidelines for Installation Room preparation During the design of the room, consideration should be given to the following factors: ease of entry for the system, floor-loading factors, and accessibility of piping and wiring.The room must be sealed with a vapor...
InRoom Precision AC Tech Data Manual 66 Chilled Water Power Supply Inlet Location Illustration Number Cabinet Size Airflow Direction 1 and 2 Downflow 1 and 2 Upflow 3 through 5 Downflow 3 through 5 Upflow na3 02 2a
67 InRoom Precision AC Tech Data Manual Piping Connections Downflow Chilled Water Cooling Units Note: The 70 mm (2 3/4 in) pipe size on models CPW1100 and CPW1500 is decreased after the screw connection to 64 mm (2 1/2 in) diameter for the external pipe connection. PCW400 View from the bottom of the...
InRoom Precision AC Tech Data Manual 68 PCW660 View from the bottom of the unit * Dimensions are in mm (in). Item Description Power wire inlet, 10 mm (0.375 in) pilot hole Water outlet, 42 mm (1 5/8 in) ID Control wire inlet, 10 mm (0.375 in) pilot hole Water inlet, 42 mm (1 5/8 in) ID Con...
InRoom Precision AC Tech Data Manual 72 Upflow Chilled Water Cooling Units On upflow cooling units the supply and return pipes and power cables can be introduced from either the left or right side through openings in the side wall. The actual connection points are on the right side. Dimensions are i...
73 InRoom Precision AC Tech Data Manual Refrigerant Piping Dimensions in mm (in). Considerations The refrigerant connections are located near the compressor and are labelled pressure pipe and liquid pipe . Models containing two circuits will be labelled pressure pipe 1 and pressure pipe 2 . To ensur...
InRoom Precision AC Tech Data Manual 74 InRoom Guide Specifications PART 1 GENERAL 1.01 SUMMARY A. The InRoom environmental control system shall be designed specifically for precision temperature and humidity control applications. It will automatically monitor and control heating, cooling, humidifyi...
75 InRoom Precision AC Tech Data Manual PART 2 PRODUCT 2.01 STANDARD COMPONENTS A. CABINET CONSTRUCTION 1. Exterior panels: Shall be 16 gauge steel sheet metal for maximum strength. All exterior panels and frame are powder coated for durability. Front panels shall have removable hinges with a lockin...
77 InRoom Precision AC Tech Data Manual E. ELECTRICAL PANEL 1. The control voltage shall be 24 VAC, class 2 circuit. The electrical panel shall contain contactors, starters, overload protection devices, and input power disconnects. The panel shall be located in the front of the unit for available ac...
79 InRoom Precision AC Tech Data Manual 2.02 OPTIONAL COMPONENTS A. FLOORSTAND 1. The heavy gauge floor stand shall raise the unit above the subfloor to match the height of the raised floor. Heights are available from 254 mm (10 in) to 610 mm (24 in) with 76 mm (3 in) increments and shall be adjusta...
InRoom Precision AC Tech Data Manual 80 H. SECONDARY POWER SUPPLY 1. 50 Hz cooling units shall have a secondary power supply option that is controlled automatically to switch from a main power supply to a secondary power source in the event of a power outage using a digital electronic controller. 2....
81 InRoom Precision AC Tech Data Manual PART 3 INDIVIDUAL SYSTEMS 3.01 AIR-COOLED A. The indoor unit shall consist of an evaporator section including evaporator coil, EC fan package, controls, electrical section, and compressor. 3.02 CONDENSER A. Outdoor Propeller Fan Condenser (60Hz): The outdoor c...
InRoom Precision AC Tech Data Manual 82 3.03 WATER-COOLED A. The water-cooled system shall consist of an evaporator section including evaporator coil, EC Fan package, controls, electrical section, compressor, and water-cooled condenser. The condenser shall be stainless steel brazed plate design and ...
83 InRoom Precision AC Tech Data Manual 3.09 FLUID COOLER A. Outdoor Fluid Cooler: The fluid cooler casing shall be of aluminum, and all structural supports, coil frame, motor-drive supports, and mounting legs shall be made of galvanized steel. The fluid cooler coil shall have copper tubes expanded ...
InRoom Precision AC Tech Data Manual 84 Warranty One-Year Factory Warranty The limited warranty provided by American Power Conversion (APC ® ) in this Statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your busi...
85 InRoom Precision AC Tech Data Manual IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR ...
InRoom Precision AC Tech Data Manual 86 Warranty Procedures Claims To obtain service under the warranty, contact APC Customer Support (see the back cover of this manual for contact information). You will need the model number of the Product, the serial number, and the date purchased. A technician wi...
9/2009 990-3299A-001 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headq...
APC Manuals
-
APC AR8163ABLK
Manual
-
APC 1500 VA
Manual
-
APC PRO 1200/1500
Manual
-
APC DP300E Series
Manual
-
APC 1500RMXL2U
Manual
-
APC 1400VA XL
Manual
-
APC VA 1000
Manual
-
APC SUA24XLBP
Manual
-
APC 1000
Manual
-
APC RBC9
Manual
-
APC 450
Manual
-
APC 2000
Manual
-
APC RBC9I
Manual
-
APC AP9604S
Manual
-
APC AP9554
Manual
-
APC RS 540W
Manual
-
APC Smart-UPS 1000
Manual
-
APC H10
Manual
-
APC SURTA2000XL
Manual
-
APC 4075KVA208V
Manual