Page 3 - Content; How to Access Summary Screens from the External Bypass
Symmetra MW with External Bypass Static Switch Operation Manual - 990- Content Overview .......................................................................... 1 Navigation Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Display Symbols and Buttons . ....
Page 5 - Overview; Navigation Tree
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 1 Overview Navigation Tree The UPS display is the user interface to the UPS system, and is located in the control section. This LCD touch-screen display is used to configure the system, monitor the system, and change the...
Page 6 - Display Symbols and Buttons; Navigation symbols
2 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 Display Symbols and Buttons Navigation symbols Screen symbols Home: Go to the top of the hierarchy. Back: Go to the previous screen. Help: Access further details on the current screen. Operation: Go to the Operation sc...
Page 7 - Buttons
Overview: Display Symbols and Buttons Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 3 Buttons ON button: Press this button to switch ON the UPS or the External Bypass Static Switch. OFF button: Press this button to switch OFF the UPS or the External Bypass Stati...
Page 10 - How to start a web-based remote session
6 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 How to Access the APC Symmetra MW Remote Display The read-only display screens can be accessed via an Internet Browser by typing the IP address of the Symmetra MW display into the browser’s address field. Configuration...
Page 11 - Operation; Operation Modes; Normal operation
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 7 Operation Operation Modes Normal operation During online operation, the critical load is supported by the inverters. While the UPS system is operating in this mode, a single-line diagram will appear on the screen. The ...
Page 12 - Static bypass operation
Operation: Operation Modes 8 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 Static bypass operation During static bypass operation, the critical load is supplied directly by utility power. A single-line diagram will appear on the screen with an orange line indicating...
Page 13 - Operation Procedures; How to access screens protected by the user-password
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 9 Operation Procedures How to access screens protected by the user-password How to start up the system from manual bypass operation Note: The UPS Startup screen on this page shows an example of a generic start-up sequenc...
Page 14 - How to shut down the system from normal to manual bypass operation
Operation: Operation Procedures 10 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 Press the Startup button. Press inside the password field and type in the user password using the keyboard on the screen. Complete with Enter . The UPS Startup screen appears with t...
Page 15 - How to transfer from normal to static bypass operation
Operation: Operation Procedures Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 11 Press the Shutdown button. Press inside the password field and type in the user password using the keyboard on the screen. Complete with Enter . Follow the procedure on the screen w...
Page 17 - Configuration; How to Configure the System
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 13 Configuration How to Configure the System The UPS is configured from the password-protected user configuration area of the display. Note: On installation, the user password is set to apc. Press the Operation button ...
Page 18 - How to change the password
Configuration: How to Configure the System 14 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 How to change the password Press the Password Settings button on the User Configuration screen to access the Password Settings screen. Change the User Password: – Press t...
Page 19 - How to configure the Modbus Settings screen
Configuration: How to Configure the System Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 15 Change the touch-screen settings: – Brightness: Place the finger on the indicator and slide it left or right to the desired setting. – Contrast: Place the finger on the ind...
Page 20 - How to configure the Regional Settings screen; How to configure the Network Configuration screens
Configuration: How to Configure the System 16 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 How to configure the Regional Settings screen Press the Regional Settings button on the User Configuration screen to access the Regional Settings screen. Change the regio...
Page 23 - How to configure the Display Settings
Configuration: How to Configure the System Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 19 Note: The APC Remote Monitoring Service (RMS) will not be activated until the RMS Team has been contacted. The contact details can be found at http://rms.apc.com. – Enable AP...
Page 24 - How to configure the Battery Test Settings screen
Configuration: How to Configure the System 20 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 Change the display settings: – Enable APC Q breaker prefix: Use this checkbox to enable or disable the APC Q breaker prefix. – Enable audible alarms: Use this checkbox to e...
Page 25 - Maintenance; Predictive Maintenance Screens; How to access Predictive Maintenance screens
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 21 Maintenance Predictive Maintenance Screens The Predictive Maintenance screens display the stress status and the Expected Remaining Lifetime (ERL) of the critical components of the Symmetra MW UPS system. Warning: Only...
Page 26 - Inverter AC Capacitors screen; Top Fans screen
Maintenance: Predictive Maintenance Screens 22 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 Inverter AC Capacitors screen The Inverter AC Capacitor screen displays the actual status and Expected Remaining Lifetime (ERL) of the Inverter AC Capacitors. You can sort t...
Page 27 - Inverter Fans screen; Main Static Switch Fans screen
Maintenance: Predictive Maintenance Screens Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 23 Inverter Fans screen The Inverter Fans screen displays the actual status and Expected Remaining Lifetime (ERL) of the Inverter Fans. You can sort the data by pressing any of...
Page 28 - How to Change the Air Filters
24 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 How to Change the Air Filters Check the air filters at regular intervals (every three months under normal working conditions) for accumulated dust on the surface facing the finishing panels. Change all filters at the ...
Page 29 - Troubleshooting; Alarm Types; Alarm button; How to silence the alarm
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 25 Troubleshooting Alarm Types The color of the top of the screen changes from blue to red when an alarm situation occurs and the alarm symbol is shown at the top of the screen. Alarm button Alarm levels There are three ...
Page 30 - How to view active alarms
Troubleshooting: Alarm Types 26 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 How to view active alarms Note: The Active Alarms screen includes a recommended action for resolving each problem. How to view the event log The event log can be accessed either by pressin...
Page 32 - APC Worldwide Customer Support
06/2008 990-1377D-001 *990-1377D-001* APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Go to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com...