Page 2 - Specification guide; Operating principles
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 2 1. UPS definition 1.1. Purpose The purpose of this specification is to define the design, manufacture and testing characteristics required in view of supplying, putt...
Page 3 - Sizing and general characteristics
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 3 All power and control electronics shall be accessible from the front of the UPS. 2.6. Battery maintenance For safe maintenance on the battery, the system shall inclu...
Page 4 - Electrical characteristics
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 4 4. AC sources 4.1. Normal AC source (rectifier input) The normal AC source supplying the UPS shall, under normal operating conditions, have the following characteris...
Page 6 - Mechanical characteristics
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 6 initiated transfer shall also be possible. If the bypass power is outside the specified tolerances or is not synchronized with the inverter, automatic transfer of th...
Page 7 - Environment conditions
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 7 6.5. Safety For the safety of maintenance personnel, the cabinet shall be provided with a manually operated mechanical bypass designed to isolate the rectifier, char...
Page 8 - Battery management
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 8 9. Battery management Batteries are components whose service life is sensitive to operating conditions, i.e. particular care is required for their management. In add...
Page 10 - Standards and tests
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 10 - Ethernet 10/100 Mbps using one of the protocols below: XML-Web for direct UPS connection to an intranet network, without connection to a server, capable of supply...
Page 11 - Functional components - organization of supplier services
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 11 ω Inspection of incoming components, tests on discrete subassemblies ω Complete functional checks on termination of manufacture. The equipment shall be subject to b...
Page 12 - Further services
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 12 16. Further services Required services include: ω Supply of the UPS and any accessory parts or elements ω Carriage-paid UPS transportation and delivery to the site....
Page 13 - Appendix. Check list
Specification guide Single UPS, three-phase, 160 to 500 kVA (cont.) APC by Schneider Electric Edition - 01/2010 Single UPS spec - p. 13 Appendix. Check list Type of UPS Total rated power (kVA) at PF 0.9 kVA kW Manufacturer Range of products Operating mode (IEC 62040-2) double conversion yes no Opera...