Page 3 - Introduction; NSTALLATION; Read the safety information sheet before installation.; Unpacking
1 Introduction The APC Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large dist...
Page 4 - Hardwiring; Wiring must be performed by a qualified electrician.; Switch the UPS input circuit breaker (see; Adhere to all; XLTW; XLI
2 Hardwiring Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring. 2. Switch the UPS input circuit breaker (see A ) and utility circuit breakers OFF. 3. Remove the access panel (see B )...
Page 8 - Serial Port; EPO Option; TVSS Screw; for the information on the
6 B ASIC C ONNECTORS Serial Port Power management software and interface kits can be used with the UPS. Use only interface kits supplied or approved by APC. Ethernet Port Connect the UPS to the network. (Located on the Network Management Card.) EPO Terminal The optional Emergency Power Off (EPO) fea...
Page 9 - PERATION; Indicator Description; Troubleshooting; Feature Function; Press this button to turn off the UPS.
7 O PERATION F RONT D ISPLAY P ANEL Indicator Description Online The UPS is drawing utility power and performing double conversion to supply power to connected equipment (see Troubleshooting ). On Battery The UPS is supplying battery power to the connected equipment. Bypass The UPS is in bypass mode...
Page 10 - On Battery Operation
8 Feature Function Normal /Bypass Manually switch connected equipment to bypass mode, so that utility power is sent directly to connected equipment. Battery operation is not available while the UPS is in bypass mode. (See Troubleshooting. ) Cold Start This is not a normal condition. Supply immediate...
Page 13 - Adhere to national and local electrical codes when wiring.; CL2: Class 2 cable for general use
11 EPO (Emergency Power Off) Option The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to national and local electrical codes when wiring. The switch should be connected in a normally open switch contact. External voltage is not required; the switch is ...
Page 14 - Terminal Mode to Configure UPS Parameters
12 Terminal Mode to Configure UPS Parameters Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial port on the back of the UPS. 1. Open a terminal program. Example: HyperTerminal • From the Desktop, go to Start => Programs ...
Page 15 - Use caution when handling heavy battery modules.; Transporting the UPS
13 M AINTENANCE , S ERVICE , W ARRANTY , AND T RANSPORTING Replacing the Battery Module(s) This UPS has easy to replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your d...
Page 16 - ROUBLESHOOTING; for assistance with complex UPS problems.
14 T ROUBLESHOOTING Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON Batteries are not connected properly. Check that the battery conne...
Page 18 - Service; Limited Warranty
16 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com . N...
Page 19 - Regulatory Agency Approvals and Radio Frequency Warnings; BSMI
17 R EGULATORY I NFORMATION Regulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V MODELS This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable...
Page 20 - Declaration of Conformity
Page 21 - APC Worldwide Customer Support; Global support searching APC Knowledge Base and using e-support.
19 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. • www.apc.com (Corporate Headquarters) Conne...