Page 3 - Contents; IMPORTANT SAFETY INSTRUCTIONS
Contents Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation i Safety ............................................................................... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ...
Page 5 - Safety; IMPORTANT SAFETY INSTRUCTIONS - SAVE
1 Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Safety IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS Warning: • ALL safety instructions in the Safety Sheet (990-2822) must be read, understood, and followed when installing the UPS system. Failure to do so...
Page 9 - Prepare for Cables
5 Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Prepare for Cables Remove the front panel 1. Turn the screw to the right to the unlocked position. 2. Pull the top of the front panel away from the UPS. 3. Lift the front panel free of the two slots at the bottom of ...
Page 12 - Anchor the UPS and additional XR Battery or UPS
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 8 Anchor the UPS and additional XR Battery or UPS Enclosure(s) (optional) Note: Enclosures can be kept apart or assembled and anchored with interconnection plates and brackets: SUVTOPT004: 352 mm (13.85 in) UPS enclosu...
Page 15 - Run the Cables; Connect Power in Installations with Busbars
11 Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Run the Cables Connect Power in Installations with Busbars Warning: Before carrying out the steps below, you must follow the Total Power Off procedure in the Operation manual. Install isolators See “Specifications” ...
Page 20 - Connect Power in Installations with Cables
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 16 Connect Power in Installations with Cables Install power cables See “Recommended cable sizes” on page 23 . Install power cables between the UPS and the XR Battery Enclosure. 1. In the UPS, feed the cable up through ...
Page 22 - Connect Communication Cables
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 18 Connect Communication Cables 1. Feed the cable from pin connection J106 in the UPS down through the conduit (if appliccable).2. Run the cable up into the XR conduit and connect it to pin connection J200 in the XR Ba...
Page 23 - Connect the EPO
19 Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Connect the EPO Connect the EPO to the UPS and the XR Battery Enclosure 1. Connect the EPO (Emergency Power Off) to J108 in the UPS and to J203 in the XR Battery Enclosure by guiding the cable through conduits. 2. C...
Page 24 - Final Mechanical Assembly; Level the Enclosures (L-shaped Floor Anchoring
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 20 Final Mechanical Assembly Level the Enclosures (L-shaped Floor Anchoring Brackets) and Install Batteries Note: The leveling feet and the L-shaped floor anchoring bracets (reuse of transportation brackets) are used i...
Page 26 - Reinstall the Enclosure Plates
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 22 Reinstall the Enclosure Plates Reinstall the cable landing cover plates and the bottom plates 1. Reinstall the cable landing cover plates on the XR Battery Enclosure(s)2. Install the upper part of the conduit box (i...
Page 27 - Specifications
23 Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Specifications Battery voltage and current Recommended cable sizes Note: Power terminal lug diameter: minimum 6 mm (0.2 in). Torque value: 45 lbf-in/7 Nm. Note: Use Molex lug type or equivalent, and follow the manuf...
Page 28 - Post-Installation Checklist
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation 24 Post-Installation Checklist Use the following checklist to verify that the XR Battery Enclosure has been installed correctly: Note: If a problem occurs, call Customer Support (see the back cover). See also the Opera...
Page 32 - APC Worldwide Customer Support
11/2009 990-1740D-001 *990-1740D-001* APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com...