Page 2 - Copyright Notice; Bosch; Notice of Liability
ICP-CC488 | Installation Guide | Notices EN | 2 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc. (“ Bosch ”). All rights are reserved. You may download a single copy of this publication...
Page 3 - Contents
ICP-CC488 | Installation Guide | Contents EN | 3 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Contents 1.0 Introduction ......................................................8 1.1 ICP-CC488 Features .......................................8 1.2 Quick Start........................................
Page 6 - Figures
ICP-CC488 | Installation Guide | Contents EN | 6 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 24.4 New Zealand Telepermit Notes................ 100 24.5 A-Tick........................................................... 101 25.0 Programming Sheets .................................. 101 25.1 I...
Page 8 - Features
ICP-CC488 | Installation Guide | 1.0 Introduction EN | 8 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 1.0 Introduction Congratulations on selecting the ICP-CC488 Control Panel for your installation. Take the time to read through this guide and familiarize yourself with the outstanding operat...
Page 9 - Start; Set the Date and Time
ICP-CC488 | Installation Guide | 1.0 Introduction EN | 9 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 1.2 Quick Start The following steps allow you to use the ICP-CC488 Control Panel with factory default values. The default values allow the control panel to communicate in the Contact ID form...
Page 10 - Codepad Indicators; Table 3
ICP-CC488 | Installation Guide | 2.0 Codepad Indicators EN | 10 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 1.2.3 Zone Types There are thirteen zone types to choose from when programming zones for the ICP-CC488 Control Panel. Refer to Section 14.3 Zone Programming for more information. Tabl...
Page 11 - Codepad Indicators
ICP-CC488 | Installation Guide | 2.0 Codepad Indicators EN | 11 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 MAINS Indicator The MAINS indicator displays whether the system’s AC MAINS supply is normal or failed. When programming in Installer’s Programming Mode or using a Master Code function...
Page 12 - Table 7; Table 8
ICP-CC488 | Installation Guide | 2.0 Codepad Indicators EN | 12 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 • Section 3.5 to arm the system in STAY Mode 2. • Section 5.1.5 to use the Installer Code to set zones to be automatically isolated in STAY Mode 2. • Section 5.2.6 to use the Master C...
Page 13 - ICP-CP516 Sixteen Zone Codepads
ICP-CC488 | Installation Guide | 2.0 Codepad Indicators EN | 13 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 10: Area On/Off Indicators Indicator Definition On The area is armed in AWAY Mode or STAY Mode 1. Off The area is disarmed. Area Display Indicators The group of four Area Displa...
Page 14 - System Operations; Arming the System in AWAY Mode; Section 18.6 Consumer; Arming the System in STAY Mode 1; on page 63 for more
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 14 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 3.0 System Operations This section explains the general operations of the system: arming and disarming the system in the three modes, isolating zones, initiating codepad alarms, and de...
Page 16 - Codepad Duress Alarm; Showing Audible Alarm Buttons; Panic; on
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 16 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 The indicators for any zones that are programmed to be automatically isolated in STAY Mode 2 flash until the Exit Time expires. At the end of Exit Time, the zone indicators are extingu...
Page 17 - Fire; System Options 2; Medical; Options 2; Zones; Section 13.3 User Code Priority
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 17 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 3.9 Codepad Fire Alarm An audible codepad Fire Alarm activates when a user presses [4] and [6] on the remote codepad simultaneously. A distinct fire sound emits through the horn speake...
Page 18 - System Operations; Fault Analysis Mode; Section 15.5 Zone Status –
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 18 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 5. Press [AWAY]. Two beeps sound and the system returns to the disarmed state. The indicators for the selected zones continue to flash until the next time the system is disarmed. Examp...
Page 19 - AC MAINS Failure
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 19 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 14: System FAULT indicators Indicator Fault Description 1 Low battery This fault registers when the system detects a low capacity backup battery. The system automatically perform...
Page 20 - Remote Radio Transmitter; Transmitter
ICP-CC488 | Installation Guide | 4.0 Remote Radio Transmitter Operations EN | 20 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 15: Fault Analysis Conditions Zone Indicator Fault Description Hold Down Button Zone Indicator Fault Condition 1 System fault 1 1 Low battery 2 Date and time 3 ...
Page 22 - System Functions; Installer Code Functions; Table 19: Installer Code Functions; Add or Delete RF Wireless Devices
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 22 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 To delete a remote radio User Code: 1. Enter the Master Code and press [1][AWAY]. Three beeps sound and the STAY and AWAY indicators flash. 2. Enter the user number (9 to 16) you want t...
Page 23 - To disable domestic dialing:
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 23 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Example To program RF wireless device number 3 whose 9-digit ID number is 000094946, enter [1 2 3 4 0][AWAY][3][AWAY] [0 0 0 0 9 4 9 4 6][AWAY] To delete an RF wireless device: 1. Enter...
Page 24 - System Functions; To program the telco arming sequence:
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 24 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 21: Codepad Indicators When Changing Phone Numbers Zone Indicators MAINS Digit 1 2 3 4 5 6 7 8 Indicator 0 X 1 X 2 X 3 X 4 X 5 X 6 X 7 X 8 X 9 X X * X X # X X Pause X X Break X X ...
Page 27 - Master Code Functions; User Code Priority
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 27 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 5.2 Master Code Functions Master Code functions allow those users that have the appropriate priority level to perform certain supervisory level functions. You can use these functions on...
Page 28 - Section 9.0 Domestic Dialing
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 28 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 27: User Numbers Displayed by the Codepad Indicators User Zone Indicators Number 1 2 3 4 5 6 7 8 1 X 2 X 3 X 4 X 5 X 6 X 7 X 8 X Example To delete user code number 3, enter: [2 5 ...
Page 32 - User Code Functions; Functions; Arm the System in AWAY Mode
ICP-CC488 | Installation Guide | 5.0 System Functions EN | 32 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 The alarm memory plays back in this order: Table 33: Event Memory Playback Sequence Indication Event 1 All indicators off except MAINS System disarmed 2 Zone 4 and AWAY indicators light...
Page 34 - Remote Arming by; To remotely arm your system by telephone:
ICP-CC488 | Installation Guide | 6.0 Remote Arming by Telephone EN | 34 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 To determine the area to which the codepad belongs: 1. Press and hold [8] until two beeps sound. A zone indicator lights to show the area to which the codepad belongs. Zone 1 ...
Page 35 - To move to a different programming location:; with; To connect the programming key:
ICP-CC488 | Installation Guide | 7.0 Programming EN | 35 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 When you enter Installer’s Programming Mode, you are automatically positioned at Location 000, the first digit of the Primary Telephone Number for Receiver 1. The codepad indicators show the...
Page 36 - Programming Option Bits; Example; Programming; Table 36: Installer’s Programming Mode; To test the programming key:
ICP-CC488 | Installation Guide | 7.0 Programming EN | 36 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 If you do not enter Installer’s Programming Mode first, connecting the CC891 Programming Key to the control panel when the programming key memory is blank corrupts the control panel’s memory...
Page 39 - Disable Factory Defaults
ICP-CC488 | Installation Guide | 7.0 Programming EN | 39 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Example (Auto Step Enabled) To enter the Primary Telephone Number 02 (pause) 9672 1055 when auto step is enabled: 1. Press [0 #]. You are positioned at Location 000 (the Primary Telephone Nu...
Page 40 - Alarm Link Software; Connect
ICP-CC488 | Installation Guide | 8.0 Alarm Link Software EN | 40 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 If you are required to disable the ability restore the control panel to its default settings, a special procedure eliminates the possibility of accidentally setting this option. You ...
Page 41 - Link; – Enable Upload/Download Using Alarm Link
ICP-CC488 | Installation Guide | 8.0 Alarm Link Software EN | 41 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 • Program the Call Back Telephone Number in Locations 159 to 174 (refer to Section 11.9 on page 51). • Disable Option 1 in Location 180 (refer to Section 8.2 Alarm Link Options on pa...
Page 42 - Domestic Dialing; Refer to; Dialing; To acknowledge domestic dialing:
ICP-CC488 | Installation Guide | 9.0 Domestic Dialing EN | 42 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 2 – Enable Alarm Link Call Back If this option is selected and a callback telephone number is programmed, the remote programming computer must be connected to the telephone line program...
Page 43 - Dialer Reporting Formats; Formats; Section 11.4 Transmission Format for Receiver 1
ICP-CC488 | Installation Guide | 10.0 Dialer Reporting Formats EN | 43 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 9.2 Setting Up and Programming Domestic Reporting Programming the control panel for domestic reporting is extremely simple when using the Installer’s Programming Command 965. R...
Page 45 - Basic Pager Reporting Format
ICP-CC488 | Installation Guide | 10.0 Dialer Reporting Formats EN | 45 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 42: 4 + 2 Transmission Code Descriptions Code Description SSSS Subscriber ID Number A Alarm C H Channel Number 1 0 Zero T Trouble B Bypass E AC Fail Code 1 st digit AC AC...
Page 48 - Basic Pager Display Information; on page; through; Dialer Information; To program a telephone number:
ICP-CC488 | Installation Guide | 11.0 Dialer Information EN | 48 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 10.2 Basic Pager Display Information The Pager format supports only eight zones. Subscriber ID Number This is the identification number of the control panel and is programmed in Loca...
Page 51 - Disarming
ICP-CC488 | Installation Guide | 11.0 Dialer Information EN | 51 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Table 46: Telco Arm/Disarm Dialing Digits Digit Required Number to Program Digit Required Number to Program terminator 0 8 8 1 1 9 9 2 2 0 10 3 3 * 11 4 4 # 12 5 5 4 sec pause 13 6 6...
Page 52 - Telephone Line Fault Options; on page 36 for more; Dialer Options; on page 36 for; Options; – Dialer Reporting Functions Allowed
ICP-CC488 | Installation Guide | 12.0 Dialer Options EN | 52 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Program the Ring Count to 14 to enable Answering Machine Bypass in the secondary mode. In this case, call the control panel and allow the phone to ring no more than twice and hang up. Wa...
Page 53 - – Open/Close Reports Only if Previous Alarm
ICP-CC488 | Installation Guide | 12.0 Dialer Options EN | 53 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 2 – Remote Arming by Telephone Allowed If you select this option, you can remotely arm the system using a standard telephone by pressing [*] on your touch-tone telephone. Refer to Sectio...
Page 54 - Codes
ICP-CC488 | Installation Guide | 13.0 Access Codes EN | 54 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 2 – Lockout Telephone Line Fail Alarm Selecting this option allows an audible alarm only once per arming cycle when the control panel detects the telephone line is cut or disconnected. Thi...
Page 55 - User Code Priority; Table 47: Priority Levels; Arm Only
ICP-CC488 | Installation Guide | 13.0 Access Codes EN | 55 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Location 185 to 264 Location Default User Code 1 185 2 186 5 187 8 188 0 Priority Level 189 10 User Code 2 190 to 193 15 Priority Level 194 2 User Code 3 195 to 198 15 Priority Level 199 2...
Page 56 - Zone Information; Day Alarm Information; Resistor
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 56 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Master Code Functions The user has access to all Master Code functions. Refer to Section 5.2 Master Code Functions on page 26 for more information. 14.0 Zone Information 14.1 Day Alarm...
Page 58 - Time
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 58 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Figure 13: Split EOL Resistors Using Two N/O Contacts 2 3 1 4 5 6 7 8 8 1 – +12 V 2 – Zone Input 3 – Zone 4 – EOL 3k3 5 – EOL 6K8 6 – EOL 1K5 7 – EOL 4K7 8 – N/O 14.3 Zone Programming ...
Page 59 - You can program Zones 1 to 16 as any zone type.
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 59 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Location 267 to 378 (continued) Location Default Zone #07 (Default = Instant) Zone Type 309 0 Zone Pulse Count 310 0 Zone Pulse Count Time 311 0 Zone Options 1 312 1 Zone Options 2 313...
Page 60 - Section 18.3 System Options 3
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 60 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 14.3.2 Zone Types The zone types are listed in Table 48 . Table 48: Zone Types Zone Type Description 0 Instant 1 Handover 2 Delay-1 3 Delay-2 4 Reserved 5 Reserved 6 24-Hour Medical 7 ...
Page 63 - Guard Timer for STAY
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 63 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 5 – Latching Arm in STAY Mode 1 The system is armed in STAY Mode 1 when using the latching keyswitch input. Arming the system in AWAY Mode or disarming the system is not permitted from...
Page 64 - Swinger Shutdown Count for Siren; Swinger Shutdown Count for Dialer; Section
ICP-CC488 | Installation Guide | 14.0 Zone Information EN | 64 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 When isolating 24-Hour Zones, the system automatically sends a Zone Bypass Report when the zone is selected to be isolated. All non-24-Hour zones send a Bypass Report only when the sys...
Page 65 - System Reporting; Zone Status – Zone Tamper Report; Section 14.2 EOL Resistor Value; Zone Status – Walk Test Report; Zone Status – Bypass Reports; Section 3.11 Isolating Zones; Zone Status – Trouble Reports
ICP-CC488 | Installation Guide | 15.0 System Reporting Information EN | 65 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 When the Swinger Shutdown Count is reached, all zones that were activated are locked out according to their individual lockout settings. If Lockout Dialer is enabled for an...
Page 67 - RF Receiver Trouble Restore; Select Option 2 in Location 178 (refer to; Codepad Duress Report; Section 18.7 Consumer Options 3; Codepad Panic Report; Section 18.2 System Options 2
ICP-CC488 | Installation Guide | 15.0 System Reporting Information EN | 67 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 An RF Receiver Trouble Report (Contact ID Event Code 355) is sent to the base station receiver when the RF receiver registers one of these events: RF Signal Jamming (Point ...
Page 70 - Test Reporting Dialer Options; Programmable Outputs; Table 54: Output Parameters
ICP-CC488 | Installation Guide | 16.0 Programmable Outputs EN | 70 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 When programming Test Report options, specify the hour and minute of the day the report is required, and how often to send the report. Test reports are reported on a daily basis fr...
Page 71 - Programmable Outputs; Redirecting Outputs to the; ,0 Communications Failure; Event
ICP-CC488 | Installation Guide | 16.0 Programmable Outputs EN | 71 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 16.1 Redirecting Outputs to the Codepad Buzzer Multiple output event types can be directed to the codepad buzzer so that the buzzer can indicate a number of events. To redirect an ...
Page 73 - horn speakers. Refer to
ICP-CC488 | Installation Guide | 16.0 Programmable Outputs EN | 73 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 1,7 Sensor Watch Alarm This output operates when the Sensor Watch Count is reached. Refer to Section 14.3.5 Zone Options 1 on page 61 for more information on programming zones for ...
Page 76 - Polarity
ICP-CC488 | Installation Guide | 16.0 Programmable Outputs EN | 76 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Set DIP Switch 2 to the ON position for the Area 2 codepad to operate correctly. Refer to Figure 16 on page 76 for the location of the DIP switches on the back of the codepad. Figu...
Page 77 - Timing; on page 77. The multiplier; Polarities; System Event Timers
ICP-CC488 | Installation Guide | 17.0 System Event Timers EN | 77 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 10 – Normally Low, One-Shot Open This one-shot polarity is normally 0 V and switches to open circuit when the event occurs. The output switches back to 0 V when the time parameter e...
Page 78 - Timers; Timer; Section 3.13 Fault Descriptions
ICP-CC488 | Installation Guide | 17.0 System Event Timers EN | 78 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 17.1 Programming Entry/Exit Timers There are two programming locations for Entry Timer 1, Entry Timer 2, Exit Time for AWAY Mode, and Entry Guard Time for STAY Mode. The first locat...
Page 79 - Lockout
ICP-CC488 | Installation Guide | 17.0 System Event Timers EN | 79 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 The Sensor Watch Time counter is active only when the control panel is disarmed. If the system is disarmed for 8 hours a day and the Sensor Watch Time is programmed for 1 day, a zon...
Page 80 - To set the date and time:; System and Consumer; Section 7.3 Programming Option Bits; – Smart Lockout Allowed
ICP-CC488 | Installation Guide | 18.0 System and Consumer Options EN | 80 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 For partitioned ICP-CC488 Control Panels, both areas are automatically disarmed at the same time each day. 17.14 Kiss-Off Wait Time Location 490 Default 3 Increments of 500 ...
Page 81 - System and Consumer Options; Section 15.16 Codepad Panic Report
ICP-CC488 | Installation Guide | 18.0 System and Consumer Options EN | 81 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 4 – Strobe Indications for Radio Arm/Disarm This option allows the strobe to indicate when the system is armed and disarmed when remotely operating the system using the DSRF...
Page 83 - EOL Resistor Value; Radio Input Options
ICP-CC488 | Installation Guide | 18.0 System and Consumer Options EN | 83 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Program the time that the control panel automatically arms itself in Locations 482 to 485 (refer to Section 17.12 Auto Arming Time on page 79). Set the Auto Arming Pre-Alert...
Page 84 - Codepad; Figure 17: ICP-CP500PW Master Partitioned; Using Codepads in a Partitioned; Operations
ICP-CC488 | Installation Guide | 19.0 Partitioning EN | 84 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 19.0 Partitioning The ICP-CC488 Control Panel includes the partitioning feature, which can effectively transform your single control panel into two separate areas. Normally, arming and dis...
Page 85 - Partitioning; and; Allocations
ICP-CC488 | Installation Guide | 19.0 Partitioning EN | 85 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 19.3.1 Partitioning Options 1 Location 500 Default 0 1 First to open/last to close reporting 2 Area 1 codepad connected to data terminal 4 Reset sirens from any area allowed 8 Master codep...
Page 86 - User Code Allocations
ICP-CC488 | Installation Guide | 19.0 Partitioning EN | 86 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 19.4.1 Zone Allocations for Areas 1 and 2 Location 502 to 517 Location Default Zone 1 LED – Area 1 Codepad 502 0 Zone 2 LED – Area 1 Codepad 503 0 Zone 3 LED – Area 1 Codepad 504 0 Zone 4 ...
Page 87 - Connections
ICP-CC488 | Installation Guide | 19.0 Partitioning EN | 87 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 19.6.1 Setting Up the Master Partitioned Codepad as the Main Codepad To use the CP5 Master Partitioned (CP500P) codepad as the main codepad in a partitioned system, connect the codepad to ...
Page 88 - RF Information; ) the codepad zone indicator
ICP-CC488 | Installation Guide | 20.0 RF Information EN | 88 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Figure 21: Connections for CP-5 Master Partitioned Codepad and CP-5 Area Addressable Codepad 1 – Data 2 – CLK 3 – +12 V 4 – GND 5 – Master Partitioned Codepad 6 – Addressable Area Codepa...
Page 89 - RF Device Mapping Option; Default; Default RF Device Mapping; to map; Using Hexadecimal Values for RF; Section 20.2 RF Device
ICP-CC488 | Installation Guide | 20.0 RF Information EN | 89 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 8 – Enable RF Jamming Monitor If this option is selected, the RF receiver monitors the background RF levels. If this level reaches a preset limit, the receiver assumes it is being jammed...
Page 90 - RF Device Signal Strength (Devices; Optional Equipment; Section 18.4 System Options 4
ICP-CC488 | Installation Guide | 21.0 Optional Equipment EN | 90 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Then, find the RF device number in Section 20.3 (for devices 1 through 8) on page 89 or Section 20.4 (for devices 9 through 16) on page 89. Use the device’s corresponding location (6...
Page 92 - Terminals and Descriptions; Descriptions; Table 63: Terminal Descriptions
ICP-CC488 | Installation Guide | 22.0 Terminals and Descriptions EN | 92 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 22.0 Terminals and Descriptions 22.1 Terminal Descriptions Table 63: Terminal Descriptions Terminal Description EARTH Connect this terminal to the green wire on the TF008 Plu...
Page 93 - Glossary Of Terms; Term
ICP-CC488 | Installation Guide | 22.0 Terminals and Descriptions EN | 93 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 22.2 Glossary Of Terms Table 64: Glossary Term Description 24-hour zone A monitored input where tamper switches and emergency switches can be connected. If one of these switc...
Page 99 - Jamming
ICP-CC488 | Installation Guide | 23.0 Appendices EN | 99 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 23.0 Appendices 23.1 Appendix A – Telephone Anti- Jamming There are many companies that import American-designed products claiming to have anti-jamming, and they push this feature as if it w...
Page 100 - Specifications; Statement; Table 65: Specifications; Software Version Number; New Zealand Telepermit Notes
ICP-CC488 | Installation Guide | 24.0 Specifications EN | 100 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Select Option 1 (Send Test Reports only if the system is armed) in Location 428 (refer to Section 18.5 Consumer Options 1 on page 82) and then set the Test Report Time to be in the midd...
Page 101 - Programming Sheets
ICP-CC488 | Installation Guide | 25.0 Programming Sheets EN | 101 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 • Disconnect this equipment immediately if it becomes physically damaged and arrange for its disposal or repair. • The transmit level from this device is set at a fixed level, so th...
Page 112 - Notes
ICP-CC488 | Installation Guide | Index EN | 112 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Notes
Page 113 - Index; AC Mains
ICP-CC488 | Installation Guide | Index EN | 113 Bosch Security Systems, Inc. | 12/08 | F01U089457-02 Index A AC Mains Fail In 1 Hour ......................................................... 81 Ignore Fail Indication ............................................ 82 Access Codes Installer Code ..........