PART NO. 37-5382E

Replaces 37-5382D

0943

F92-0737

Natural to Unregulated L.P. Gas

Conversion Kit

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

Installer: Save these instructions for future use!

This conversion kit shall be installed by a qualified
service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements
of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a fire, ex-
plosion, or production of carbon monoxide may result,
causing property damage, personal injury, or loss of
life. The qualified service agency performing the work
assumes the responsibility for the proper conversion
of this appliance with this kit.

APPLICATION

This regulated Natural Gas to unregulated L.P. Gas conversion
kit allows the 36C, 36E and 36J Series gas valves to be used
on L.P. gas applications,

PROVIDED an external regulator is

used and the inlet pressure does not exceed 14” W.C. This
conversion kit is for use on all single stage, fast and slow
open models only.

TO CONVERT FROM NATURAL TO L.P. GAS

1. Remove regulator cover screw.
2. Insert the spring (provided in the conversion kit) through the

hole in the center of the plastic regulator adjustment screw.

3. Insert the blocking pin (provided in the conversion kit) down

into the center of the spring.

4. Replace the regulator cover screw.
5. Attach the WARNING label (provided in the kit) to the gas valve

where it can be readily seen. Also attach the small round L.P.
label to the top of the regulator cover screw.

6. If present pilot burner is to be used, the pilot orifice must be

replaced.

Conversion back to Natural Gas use may be made at a later date
by removing the spring and blocking pin (installed in steps 2 and
3, above) and removing the WARNING and L.P. labels.

Figure 1. 36C model

Regulator

Cover Screw

Spring

Blocking Pin

Plastic Regulator

Adjustment Screw

Figure 2. 36E model

Regulator

Cover Screw

Spring

Blocking Pin

Plastic Regulator

Adjustment Screw

Figure 4. Contents of kit

VALVE CONVERTED FOR USE ON L.P.

GAS. REGULATOR BLOCKED OPEN.

EXTERNAL REGULATOR REQUIRED.

IMPROPER OPERATION COULD RESULT

IN DEATH OR SERIOUS INJURY.

WARNING

!

SOUPAPE CONVERTIE POUR USAGE

SUR GAZ DE PÉTROLE LIQUÉFIÉ.

RÉGULATEUR BLOQUÉ EN POSITION

OUVERTE. RÉGULATEUR EXTERNE

NÉCESSAIRÉ. UN FONCTIONNEMENT

INAPPROPRIÉ PEUT PROVOQUER LA

MORT OU DES BLESSURES GRAVES.

MISE EN GARDE

!

WARNING Label

Blocking

Pin

Spring

L.P. Label

LP

White-Rodgers is a division

of Emerson Electric Co.

WARNING

!

Regulator Cover
Screw

Blocking Pin

Spring

Plastic Regulator
Adjustment Screw

Figure 3. 36J model