White Rodgers 96-TBF Series - Manual
White Rodgers 96-TBF Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
www.white-rodgers.com
25
REFRIGERATION
BI-DIRECTIONAL
HEAT PUMP DRIERS
96-TBF BI-DIRECTIONAL HEAT PUMP DRIERS
Bi-Directional Driers Designed to Provide Complete Protection to Your Heat Pump
or Reverse Cycle System. This Compact Design Filters Contaminants, Removes
Moisture & Acids During the Cooling & Heating Cycles During Winter and Summer.
Internal Check Valves Prevent the Release of Collected Contaminants When the Heat
Pump Cycles from the Heating to Cooling Modes
FEATURES
• Proven, nylon internal check valves.
• Solid block desiccant core: a composite of molecular sieve and activated alumina.
• Provides high moisture, organic and inorganic acid removal.
• The addition of charcoal to the desiccant core allows for the removal of wax that
may occur at low evaporator temperatures.
• Nickel plated SAE flare and solid copper ODF fittings.
• Corrosion resistant paint.
SPECIFICATIONS
Maximum Working Pressure . . . . . . . . . . 500 psig
Minimum Burst Pressure . . . . . . . . . . . . . 2500 psig
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . .
U.L. file number SA7175
C.S.A. file number LR100624
INSTALLATION NOTE
: The drier may be installed in any position in the reversing liquid line.
SELECTION NOTE
: Given the proper liquid line size, connection type and tonnage of the
refrigerant system, the correct drier may be selected using the chart below. Choosing a unit size
with sufficient water capacity to reduce moisture content of the system to a safe level should be
considered.
➀
Flow Capacity
Model
Connections
Dimension
Tons @ 2 psi
▲
P
Number
size & type
A
B
R-22
96-TBF083
3/8 SAE
6.28 2.63
6.6
96-TBF083S
3/8 ODF
5.63 2.63
7.4
96-TBF163
3/8 SAE
6.97 2.63
6.7
96-TBF163S
3/8 ODF
6.3 2.63
7.5
96-TBF164
/2 SAE
7.22 2.63
.2
96-TBF164S
/2 ODF
6.34 2.63
.7
96-TBF165S
5/8 ODF
6.63 3.09
2.4
SELECTION: CONNECTIONS, DIMENSIONS, FLOW CAPACITIES
96-TBF
96-TBF Series
Dimensional Drawing
➀
All ratings in accordance with ARI standard 70-86: 2.9 lbs./min./ton for R-22
96-TBF
SERIES
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.