  • Page 2 – DIAL SETTING; Setting the High Limit; NOTE; WIRING AND OPERATION; CAUTION
  • Page 3 – SERVICING; TERMINAL DESIGNATIONS CROSS REFERENCE
  • Page 4 – DESCRIPTION; COMMANDE À RELAIS POUR EAU CHAUDE; INSTRUCTIONS D’INSTALLATION; SPÉCIFICATIONS; ATTENTION; AVERTISSEMENT; INSTALLATION
  • Page 5 – CÂBLAGE ET UTILISATION; POINTS DE CONSIGNE
  • Page 6 – Gaine no
Loading the manual

WHITE-RODGERS

Printed in U.S.A.

PART NO. 37-5488A

Replaces 37-2935-1

37-9333

-1

9512

TYPE 8B43A-601

RELAY-HOT WATER CONTROL

For Use With Line Voltage Primary Control

(Suitable for External Zone Valve Load)

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300,

FAX (314) 577-1517

9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

R

DESCRIPTION

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

These Relay-Hot Water Controls combine into a single
enclosure: a high limit control, low limit-circulator control,
circulator relay, transformer, together with terminals for
wiring. They are for use on boilers equipped with tankless
domestic coil.

Although these controls are designed for use with a line
voltage gas valve or oil burner control, they may also be
used with low voltage primary controls.

The internal transformer supplies power for operating the
relay coil and systems zoned with motorized water valves.

ELECTRICAL DATA
Input Voltage:
120V.A.C., 60Hz
Circulator Motor:

120V.A.C.

8F.L.A.

48L.R.A.

Burner Circuit:

120V.A.C.

8F.L.A.

48L.R.A.

Ignition Trans.:

3.0 Amps

Burner Motor: 7F.L.A. 42L.R.A. or 125 VA Pilot Duty

Motorized Valve: 1.2A. Max.
Room Thermostat:

Set adjustable heat anticipator at 0.25 Amps. For fixed
anticipation thermostats, use 0.20 to 0.30 Amp. heater.

SPECIFICATIONS

To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.

If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor, electrician, or someone famil-
iar with basic electricity and wiring.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

PRECAUTIONS

CAUTION

Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.

WARNING

If the boiler manufacturer recommends a control location,
then follow such recommendations. Otherwise, locate
the control as close to the top of the boiler as possible, but
not in the same section of the boiler that has fittings for
domestic hot water. Never locate the control near a return
pipe to the boiler.

THERMAL DATA
Range: High Limit
- 140

°

to 240

°

F (60

°

to 116

°

C)

Low Limit / Circ. - 100

°

to 200

°

F (38

°

to 94

°

C)

Differential: High Limit - 10

°

F Fixed (5.5

°

C)

Low Limit / Circ. - 10

°

to 35

°

F Adj. (5.5

°

to 19

°

C)

Switch Action: High Limit - Open on rise

Low Limit / Circ. - SPDT

Well: 1/2" or 3/4" Thread Size

INSTALLATION

Install control as follows:

1. Install well securely into proper tapping.

2. Remove control cover. Then loosen the two screws

holding well clamp to back of case. NOTE: Loosen
until ends of screws are flush with well clamp for
easiest assembly.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - DIAL SETTING; Setting the High Limit; NOTE; WIRING AND OPERATION; CAUTION

2 INSTALLATION CONT. 3. Insert sensing bulb into well, forming capillary so bulb bottoms in well. Raise control onto well, slippingflange on well between back of case and well clamp.Be sure well fits snugly into hole in case. Then tightenwell clamp screws evenly and securely. Do not dent or bend the...

Page 3 - SERVICING; TERMINAL DESIGNATIONS CROSS REFERENCE

3 ZONING FOR WATER VALVES Fig. 4 T1 T2 Z1 Connect Z to 1, T1 to 2, and T2 to 3 on water zone valvesas shown. Refer to sheet packed with water valves forcomplete wiring information. For water valves other thanWhite-Rodgers, consult the valve manufacturer for wiringdetails. ZONING WITH CIRCULATORS All...

Page 4 - DESCRIPTION; COMMANDE À RELAIS POUR EAU CHAUDE; INSTRUCTIONS D’INSTALLATION; SPÉCIFICATIONS; ATTENTION; AVERTISSEMENT; INSTALLATION

WHITE-RODGERS Imprimé aux É.-U.A. PIÈCE NO 37-5488A Remplace 37-2935-1 37-9333 -1 9512 WHITE-RODGERS DIVISIONEMERSON ELECTRIC CO.9797 REAVIS RD., ST. LOUIS, MO. 63123(314) 577-1300, Télécopieur : (314) 577-1517 9999 HWY. 48, MARKHAM, ONT. L3P 3J3(905) 475-4653, Télécopieur : (905) 475-4625 R DESCRIP...