White Rodgers 50a55-286 - Manual
White Rodgers 50a55-286 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – SPECIFICATIONS; Flame Current Requirements:; Minimum current to insure flame detection: 1; OPERATING TEMPERATURE RANGE:; Surface mount multipoise; maximum; Flame Establishing Time:
- Page 3 – approved for minimum ambient temperatures of -40; WARNING; CAUTION
- Page 4 – TYPICAL SYSTEM WIRING DIAGRAM
- Page 5 – TYPICAL SYSTEM WIRING TABLE
- Page 7 – DIAGNOSTIC FEATURES; The LED will also flash once at power-up.; SYSTEM LOCKOUT AND; SYSTEM LOCKOUT FEATURES
- Page 8 – MOUNTING HOLE TEMPLATE; FOR MOUNTING HOLE LOCATIONS
GENERAL PRECAUTION
!
Application of this type of control may cause
flame rollout on initial start-up and could cause
personal injury and/or property damage.
Replace only with exact model number, includ-
ing dash number. Failure to use exact replace-
ment control could cause personal injury and/or
property damage.
If in doubt about whether your wiring is millivolt, line, or low
voltage, have it inspected by a qualified heating and air
conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause im-
proper and dangerous operation.
This control is not intended for use in locations
where it may come in contact with water. Suit-
able protection must be provided to shield the
control from exposure to water (dripping, spray-
ing, rain, etc.).
Do not use on circuits exceeding specified volt-
age. Higher voltage will damage control and
could cause shock or fire hazard.
Do not short out terminals on gas valve or pri-
mary control to test. Short or incorrect wiring will
damage thermostat and could cause personal
injury and/or property damage.
Printed in U.S.A.
50A55-286
Integrated Furnace Control
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
Operator: Save these instructions for future use!
INSTALLATION INSTRUCTIONS
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
The 50A55-286 is an automatic gas interrupted ignition
control that employs a microprocessor to continually
monitor, analyze, and control the proper operation of the
gas burner, inducer, and fan.
Signals interpreted during continual surveillance of the
thermostat and flame sensing element initiate automatic
ignition of the burner, sensing of the flame, and system
shut-off during normal operation.
These controls incorporate system fault analysis for quick
gas flow shut-off, coupled with automatic ignition retry
upon sensing a fault correction.
WHITE-RODGERS
PRECAUTIONS
CAUTION
!
WARNING
!
CONTENTS
Description ......................................................... 1
Precautions ........................................................ 1
Specifications ..................................................... 2
Installation .......................................................... 3
Mounting & Wiring
Operation ........................................................... 6
PART NO. 37-6101A
9919
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 SPECIFICATIONS ELECTRICAL RATINGS [@ 77 ° F (25 ° C)]: Input Voltage: 25 VAC 50/60 Hz Max. Input Current @ 25 VAC: 0.45 amp Relay Load Ratings: Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pfIgnitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive) Flame Current Requirements: Minimum current to insure f...
3 MOUNTING AND WIRING Do not use on circuits exceeding specifiedvoltage. Higher voltage will damage controland could cause shock or fire hazard. To prevent electrical shock and/or equipmentdamage, disconnect electric power to system atmain fuse or circuit breaker box until installationis complete. F...
4 TRTH MV MV GND FP HLO HLI PS C R G W Y EAC N HUM N XFMR N LINE N CIR N IGN IND IND N IGN N HUM EAC XFMR LINE PARK PARK HEAT COOL IGNITOR Y W G R THERMOSTAT GAS VALVE HIGH LIMIT (N. C.) THERMAL ROLLOUT (N. C.) AUX. HIGH LIMIT (N. C.) PRESSURE SWITCH (N. O.) FLAME SENSOR PROBE COMPRESSOR CONTACTOR E...