White Rodgers 47D40-801 - Manual

White Rodgers 47D40-801

White Rodgers 47D40-801 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
Page: / 4
Loading the manual

47D40-801

Demand Defrost Control

INSTALLATION INSTRUCTIONS

The 47D40-801 control is a microprocessor-based demand
defrost controller intended for Rheem heat pump systems.
This controller uses basic differential temperature means to
detect degradation of system performance due to ice build-up
on the outdoor coil. The controller uses “self-calibrating” prin-
ciples to calibrate to the heat pump system. The defrosting is
performed by reversing the refrigerant direction of flow.
The 47D40-801 is meant to replace the following controllers
in Rheem heat pump systems:

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

Operator: Save these instructions for future use!

DESCRIPTION

www.white-rodgers.com

www.emersonclimate.com

PART NO. 37-7200A

1039

47D40-801

PRECAUTIONS

WARNING

!

• To prevent electrical shock and/or equipment damage,

disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.

• This control is not intended for use in locations where

it may come in direct contact with water. Suitable
protections must be provided to shield the control from
exposure to water (dripping, spraying, rain, etc.)

• Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper or loss of
heat pump operation and/or shock hazard.

• Following installation or replacement, follow appliance

manufacturer’s recommended installation/service

instructions to insure proper operation.

• Do not use on circuits exceeding specified voltage.

Higher voltage will damage control and could cause
shock or fire hazard.

If in doubt about whether your wiring is millivolt, line or low
voltage, have it inspected by a qualified heating and air
conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could
cause the control to malfunction.

CAUTION

!

• This control is intended only for Rheem heat pump

systems.

• Replace 47D40-801 control as a unit - no user service

-

able parts.

CONTENTS

Description ................................................................ 1
Precautions .............................................................. 1
Specifications ........................................................... 2
Operation .................................................................. 2
Installation ................................................................ 3

47-21517-16
47-21517-17
47-21517-18
47-21517-23
47-21517-24
47-21517-11
47-21517-14
47-21517-13

47-21517-82
47-21517-88
47-102685-01
47-102685-03
47-102684-01
47-102684-03
47-102684-83

DDL-013102-1RH
DDL-017002-2RH
DDL-017102-1RH
DDL-017702-1RH
DDL-117702-3RH
DDL-013002-0RH
DDL-013002-1RH

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other White Rodgers Models

All White Rodgers Other