White Rodgers 36C03 - Manual

White Rodgers 36C03

White Rodgers 36C03 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – WARNING; CAUTION
  • Page 3 – Pilot gas; Figure 2. Gas valve side view; Figure 1. Typical gas valve piping
  • Page 4 – Energize valve to ignite main burner.; Figure 8. Pressure regulator adjustment; Figure 7. Pilot gas adjustment
  • Page 5 – FOR YOUR SAFETY READ BEFORE LIGHTING; LIGHTING INSTRUCTIONS; Indicator; Figure 9. Gas Cock Knob
  • Page 6 – NOTES
Loading the manual

Pilot Gas Outlet:

Located at outlet end of the valve

Type of Gas

Suitable for all domestic heating gases

Pressure Rating: 1/2 lb. per sq. in.

Pressure Regulator Adjust Range (Typical, See

Control Label):
Natural Gas: 2.5 to 5.0" W.C.
LP Gas:

7.5 to 12" W.C.

Ambient Temperature: -40° to 175°F

Thermocouple:

(24V & 120V types): Use W-R Type HO6

(.750V Quick Drop Out Power Unit for
36D34 models only):
Use W-R Type H19E

Pilot Generator (.750 volt types):

Use W-R Type G01A-32

Mounting: Any position except upside-down

PIPE SIZES/CAPACITIES

Pipe Size

(inches)

Capacity (BTU/hr) at

1” pressure drop across valve

1

2

” x

3

8

1

2

” x

1

2

1

2

” x

3

4

3

4

” x

3

4

100,000
230,000
230,000
280,000

162,000
372,600
372,600
453,600

Nat. Gas

(1000 BTU/cu. ft.,

64 Sp. Gr.)

LP Gas

(2500 BTU/cu. ft.,

1.53 Sp. Gr.)

INLET BOSS
UP OR DOWN

UPRIGHT

LEFT OR RIGHT

Upright, 90

°

from upright or vertical

NOTE: Control shown may not be identical

to replacement control.

ON

OFF

www.white-rodgers.com

PART NO. 37-5781D

Replaces 37-5781C

0909

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.

The 36C03, 36C13 and 36D34 complete gas controls
combine into a single compact package the functions of 3-
position gas cock, pressure regulator, 100% shut-off
automatic pilot, and main operator. Separate models are
available for use on 24 VAC, 120 VAC and .750 VDC
systems. These controls can be mounted in any orienta-
tion except upside down.

MODELS AVAILABLE

Model No.

Voltage

36C03

36C03A

36C03U

36C13

36C13A

36C13U
36D34U

Current

.23 Amp

.035 Amp

DC

.23 Amp

.035 Amp

DC
DC

24 volts

120 volts

.750 volts

24 volts

120 volts

.750 volts
.750 volts

Gas

Nat.
Nat.
Nat.

LP
LP
LP

Nat./LP

OFF

PILOT

ON

ECO

Terminals

OFF

P

IL

OT

ON

The 36C03 and 36C13 models are also available without
pressure regulator as a Model 36C10.

The 36D34 model is limited to .750 VDC applications and
is equipped with a "quick drop out" power unit for vented
gas hearth products.

Operator: Save these instructions for future use!

DESCRIPTION

SPECIFICATIONS

36C03, 36C10, 36C13 and 36D34

Combination Gas Valves

(24 Volt, 120 Volt and .750 Volt Models)

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WARNING; CAUTION

2 1. Do not short out terminals on gas valve orprimary control to test. Short or incorrectwiring can cause equipment damage, prop-erty damage, and/or personal injury. 2. This control is not intended for use in loca-tions where it may come in direct contactwith water. Suitable protection must be pro-...

Page 3 - Pilot gas; Figure 2. Gas valve side view; Figure 1. Typical gas valve piping

3 INSTALLATION (cont’d) PILOT GAS CONNECTION Install fitting into pilot gas outlet (see fig. 2), turning untilfinger-tight. Insert clean, deburred tubing all the waythrough the fitting. While holding the tubing securely,slowly tighten fitting until you feel a slight "give". Tightenthe fittin...

Page 4 - Energize valve to ignite main burner.; Figure 8. Pressure regulator adjustment; Figure 7. Pilot gas adjustment

4 INSTALLATION (cont’d) ENERGY CUT OFF (E.C.O.) CONNECTION A five-function valve uses the two E.C.O. terminals that areconnected to the magnetic assembly where the thermo-couple connects to the 36C valve line interrupter. Connect the leads from the E.C.O. terminals to the E.C.O.device on the furnace...

Other White Rodgers Models

All White Rodgers Other