“Slimline” level-Temp

SilenT operATor

(normally open)

inSTAllATion inSTrucTionS

DeScripTion

These Level-Temp Silent Operator relays are designed for use
on electric heating equipment in conjunction with White-Rodgers
low voltage thermostats. They are especially suitable for use on
baseboards, wall insert heaters, etc. Some models also have
an inductive rating to permit them to be used on motor loads
where a time delay is desired.
Different models of these Silent Operator relays are available
for voltage inputs of 120, 208, 240, 277, 347 or 600 volts. Since
these relays are equipped with a self-contained transformer, the
supply voltage used must agree with the voltage rating of the relay.
When required, two or more of these Silent Operator relays can

operator: Save these instructions for future use!

FAilure To reAD AnD FolloW All inSTrucTionS cAreFully BeFore
inSTAllinG or operATinG THiS conTrol coulD cAuSe perSonAl
inJury AnD/or properTy DAmAGe.

be operated by one low voltage heating thermostat. These Silent
Operator relays have been carefully adjusted at the factory. No
attempt should be made to adjust them in the field.

If in doubt about whether your wiring is millivolt, line, or low
voltage, have it inspected by a qualified heating and air condi-
tioning contractor, electrician, or someone familiar with basic
electricity and wiring.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.

WARNING

!

Do not use on circuits exceeding specified voltages.
Higher voltages will damage control and could cause
shock or fire hazard.

CAUTION

!

To prevent electrical shock and/or equipment damage,
disconnect electric power to system, at main fuse or
circuit breaker box, until installation is complete.

SpeciFicATionS

elecTricAl DATA
Switch Action:

Single-Pole, Single-Throw, normally open

Thermal:

Average time delay – 45 seconds

Ambient Temp.:

-20° to 140°F (-24° to 60°C)

room Thermostat:

Set adjustable heat anticipator at 0.2 Amps. For fixed anticipa-
tion thermostats, use 0.15 to 0.25 Amp. heater.

Type

numBer

inpuT

volTAGe /Frequency

THermoSTAT

currenT

A.c. reSiSTive

non-inDucTive

A.c. moTor inDucTive

Full loAD

locKeD roTor

24A07A-1

120VAC, 60 Hz

0.2A

25A, 3000W, 120V

16A, 120V

96A, 120V

24A07e-1

208VAC, 60 Hz

0.2A

25A, 5200W, 208V

12A, 208V

72A, 208V

24A07G-1

240VAC, 60 Hz

0.2A

25A, 6000W, 240V

12A, 240V

72A, 240V

24A07Z-1

277VAC, 60 Hz

0.2A

22A, 6000W, 277V

________

________

24A07Z-8

347VAC, 60 Hz

0.2A

17A, 5900W, 347V

________

________

24A07Z-9

600VAC, 60 Hz

0.2A

12A, 7200W, 600V

________

________

precAuTionS

mounting:

Mounting tabs with several break-offs for 2, 3 or 4 hole mounting.

www.white-rodgers.com

www.emersonclimate.com

pArT no. 37-4709D

Replaces 37-4709C

1209

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WirinG; Always be sure that the; inSTAllATion; WIRING

2 WirinG All wiring should be done in accordance with local and national electrical codes and ordinances. If a wiring diagram is supplied with the heating equipment, follow those instructions. If none is available, several diagrams are presented on this sheet which show different wiring meth-ods for...

Page 3 - All wiring should be performed; Fig. 5. Typical Wiring Diagram to “Sequence” two or more loads; NOTE; CAUTION

3 WirinG conT. In operation, a circuit is completed through the bimetal heater as the low voltage room thermostat closes its contacts. In approximately 45 seconds, the warping ac-tion of the heater closes the line voltage snap-switch to energize the heating load. When the thermostat opens its contac...