  • Page 2 – SPECIFICATIONS; Flame Current Requirements:; maximum
  • Page 3 – WARNING; INSTALLATION; Arrow on; MOUNTING PANEL
  • Page 4 – When replacing original 63K8901 board in; PROCEDURE 2
  • Page 5 – OPERATION; OPTION SWITCHES; HEAT MODE; These ignitors are spe-; PROCEDURE 3; Disconnect all electric power and shut off gas
  • Page 6 – COOL MODE; will never override the precautionary features.); do one of; not; Interrupt the 24 VAC power at the control for at least; DIAGNOSTIC FEATURES; TROUBLESHOOTING
  • Page 7 – GLOSSARY
Loading the manual

21D83M-843

Integrated Single Stage

Furnace Control Replacement Kit

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

PRECAUTIONS

INSTALLATION INSTRUCTIONS

Kit includes:
1 – 50A66-843 ignition control board
1 – Wiring harness (9-pin to 12-pin)
1 – Wiring harness (4-pin to 6-pin)
1 – Mounting panel
4 – Stand-off fasteners
1 – Circuit breaker
1 – 4" blue wire
2 – Wiring diagrams

www.white-rodgers.com

www.emersonclimate.com

PART NO. 37-7337B

Replaces 37-7337A

1244

Installation should be done by a qualified heating and air
conditioning contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
Following installation or replacement, follow manufacturer’s
recommended installation/service instructions to ensure
proper operation.

WARNING

!

Failure to comply with the following warnings

could result in personal injury or property damage.

FIRE HAZARD

• Do not exceed the specified voltage.
• Replace existing control with exact model

and dash number.

• Protect the control from direct contact with

water (dripping, spraying, rain, etc.).

• If the control has been in direct contact with

water, replace the control.

• Label all wires before disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation.

• Route and secure wiring away from flame.

SHOCK HAZARD

• Disconnect electric power before servicing.
• Ensure proper earth grounding of appliance.
• Ensure proper connection of line neutral and

line hot wires.

EXPLOSION HAZARD

• Shut off main gas to appliance until installa

-

tion is complete.

CAUTION

!

Do not short out terminals on gas valve or primary

control. Short or incorrect wiring may damage

the thermostat.

The kit includes the 50A66-843 which is an automatic gas

interrupted ignition control that employs a microprocessor

to continually monitor, analyze, and control the proper

operation of the gas burner, inducer, and fan.
These controls incorporate system fault analysis for quick

gas flow shut-off, coupled with automatic ignition retry

upon sensing a fault correction.

Lennox

White-Rodgers Page

Reference

10M9301

12L6901

32M8801

56L8401

50A65-120

50A65-121

3

PROCEDURE 1

Figure 1, Picture

1, Table 1, Wiring

Diagram 5001-6973

24L8501

63K8901

97L4801

50A62-120

50A62-121

50A62-820

4

PROCEDURE 2

Figure 1, Picture

2, Table 2, Wiring

Diagram 5001-6972

100925-01

100925-03

17W9201

23W5101

30W2501

69M0801

69M1501

83M00

21D83M-843

50A66-122

50A66-123

5

PROCEDURE 3

The 21D83M-843 kit will replace the following Controls:

Follow instructions for replacement of your model num-
ber under the heading

INSTALLATION.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - SPECIFICATIONS; Flame Current Requirements:; maximum

2 SPECIFICATIONS ELECTRICAL RATINGS [@ 77°F (25°C)]: Input Voltage: 25 VAC 50/60 Hz Max. Input Current @ 25 VAC: 0.45 amp Relay Load Ratings: Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pfIgnitor Relay: 2.0 amp @ 120 VAC 50/60 Hz (resistive)Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VACCirculator Relay: 14...

Page 3 - WARNING; INSTALLATION; Arrow on; MOUNTING PANEL

3 WARNING ! FIRE HAZARD • Do not exceed the specified voltage.• Replace existing control with exact model and dash number. • Protect the control from direct contact with water (dripping, spraying, rain, etc.). • If the control has been in direct contact with water, replace the control. • Label all w...

Page 4 - When replacing original 63K8901 board in; PROCEDURE 2

4 INSTALLATION over the marks. Use the mounting panel as a template to drill 3/16" holes through each of the holes marked "A". Install the replacement control in the freshly drilled holes in the blower access panel. Use aluminum tape to seal the unused holes. B. When replacing original 6...