White Rodgers 2061 - Manual

White Rodgers 2061

White Rodgers 2061 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – PRINCIPLE OF OPERATION; DUCT LAYOUT; NOTE
  • Page 3 – ” minimum clearance between edge of; WIRING
  • Page 4 – CHECKING THE SYSTEM
  • Page 5 – OPERATION; MANUAL OPERATION; CAUTION
  • Page 6 – BYPASS DAMPER; INSTALLATION INSTRUCTIONS
Loading the manual

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398

PART NO. 37-1499B

Replaces 37-1499

9516

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.

Operator: Save these instructions for future use!

INSTALLATION INSTRUCTIONS

WHITE-RODGERS

DESCRIPTION

2061 ZONE-AIR

Two-Wire DAMPER MOTOR

with Access-Mounting Plate

The Type 2061 Damper Motor provides a low-cost system
of zoned temperature control for warm air heating. It is of
the two-wire type, and is specially designed for use with
a two-wire thermostat with .2 Amp heat anticipator.

Each room or zone requires one damper motor and one
thermostat. The thermostat automatically controls the
passage of warm air through the duct by operating the

damper motor which is installed on the duct work to each
room or zone.

This Damper Motor-Thermostat combination may be in-
stalled on present systems for economical conversion to
zone heating. It is ideally suited for split-level and ranch-
type homes having a warm air heating plant.

PRECAUTIONS

WARNING

!

CAUTION

!

Do not exceed the specification ratings.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

Do not use on circuits exceeding 30 volts. Higher
voltage will damage control and could cause
shock or fire hazard.

To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.

Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will burn
out heat anticipator and could cause personal
injury and/or property damage.

Printed in U.S.A.

SPECIFICATIONS

All guarantees are void if these specifications are
exceeded.

Electrical Ratings: The Damper Motor draws .2 Amp

Max. at 25 VAC when in the open position.
Auxiliary Contacts: Do not exceed 2.0 Amp at 25
VAC (terminals 2 and 3).

The Damper Motor draws more than .2 Amp while it
is opening. For this reason, do not use more than the
recommended number of damper motors per trans-
former as shown on page 4.

NOTE

Thermostat: Use two-wire thermostat with .2 Amp

anticipator.

Timings: From full close to full open - Approximately

45 seconds
From full open to full close - Approximately
60 seconds.

Maximum Duct Size: 300 square inches

Maximum Duct Capacity: 1200 cubic feet per

minute.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - PRINCIPLE OF OPERATION; DUCT LAYOUT; NOTE

2 Point “X” (locate exactly opposite 1 ⁄ 2 ” hole) Centerlines of Duct 1 ⁄ 2 ” Dia. Hole #10 Sheet Metal Screws Bearing Plate 15 ⁄ 16 ” 1 3 2 2 4 110-280 or 120-280 Thermostat 2061 Two-Wire Damper Motor INTERNAL WIRING EXTERNAL WIRING Side “A” of Motor Switch Side “B” of Motor Switch Warp Switch Hea...

Page 3 - ” minimum clearance between edge of; WIRING

3 4. Use access-mounting plate as a template. Hold plate against duct and mark the four hole locations forattaching plate to duct. Be sure slotted hole in centerof plate is over point “X” (Fig. 1) and that edge ofplate is parallel with edge of duct. Then drill the fourholes to take #10 sheet metal s...

Page 4 - CHECKING THE SYSTEM

4 2 2 4 1 3 2 2 4 1 3 2 2 4 1 3 S81-0125 Transformer Line G H 2061 Damper Motors White-Rodgers Damper Motor Thermostats (Two-Wire) High Limit Pilot 26A00 Series Low Voltage Diaphragm Gas Valve Typical 3-Zone Gas Fired System Transformer suppliespower for low voltagegas valve as well asdamper motors....

Other White Rodgers Models

All White Rodgers Other